Voltage source converter based high voltage direct current(VSC-HVDC)can participate in voltage regulation by flexible control to help maintain the voltage stability of the power grid.In order to quantitatively evaluat...Voltage source converter based high voltage direct current(VSC-HVDC)can participate in voltage regulation by flexible control to help maintain the voltage stability of the power grid.In order to quantitatively evaluate its influence on the voltage interaction between VSC-HVDC and line commutated converter based high voltage direct current(LCC-HVDC),this paper proposes a hybrid multi-infeed interaction factor(HMIIF)calculation method considering the voltage regulation control characteristics of VSC-HVDC.Firstly,for a hybrid multi-infeed high voltage direct current system,an additional equivalent operating admittance matrix is constructed to characterize HVDC equipment characteristics under small disturbance.Secondly,based on the characteristic curve between the reactive power and the voltage of a certain VSC-HVDC project,the additional equivalent operating admittance of VSC-HVDC is derived.The additional equivalent operating admittance matrix calculation method is proposed.Thirdly,the equivalent bus impedance matrix is obtained by modifying the alternating current(AC)system admittance matrix with the additional equivalent operating admittance matrix.On this basis,the HMIIF calculation method based on the equivalent bus impedance ratio is proposed.Finally,the effectiveness of the proposed method is verified in a hybrid dual-infeed high voltage direct current system constructed in Power Systems Computer Aided Design(PSCAD),and the influence of voltage regulation control on HMIIF is analyzed.展开更多
Modern power systems,employing an increasing number of converter-based renewable energy sources(RES)and decreasing the usage of conventional power plants,are leading to lower levels of short-circuit power and rotation...Modern power systems,employing an increasing number of converter-based renewable energy sources(RES)and decreasing the usage of conventional power plants,are leading to lower levels of short-circuit power and rotational inertia.A solution to this is the employment of synchronous condensers in the grid,in order to provide sufficient short-circuit power.This results in the increase of the short-circuit ratio(SCR)at transmission system busbars serving as points of interconnection(POI)to renewable generation.Evaluation of the required capacity and grid-location of the synchronous condensers,is inherently a mixed integer nonlinear optimization problem,which could not be done on manual basis considering each type of machine and all bus-bars.This study therefore proposes a method of optimal allocation of synchronous condensers in a hypothetic future scenario of a transmission system fed by renewable generation.Total cost of synchronous condenser installations in the system is minimized and the SCRs at the POIs of central renewable power plants are strengthened.The method has potential for application on larger grids,aiding grid-integration of RES.展开更多
Distinction of weak and strong AC grids for emerging hierarchical-infeed LCC-UHVDC systems is important for planning and operation departments. However, accuracy of earlier distinction methods is limited as they were ...Distinction of weak and strong AC grids for emerging hierarchical-infeed LCC-UHVDC systems is important for planning and operation departments. However, accuracy of earlier distinction methods is limited as they were developed by empirical reasoning without rigorous theoretical analysis. Hence in this letter, hierarchical-infeed interactive effective short-circuit ratio (HIESCR) index is first used for strength evaluation of HIDC systems with complex inter-inverter interactions considered. Boundary HIESCR (BHIESCR) is also introduced in the proposed distinction method of weak and strong AC grids. That is, weak (or strong) AC grids are, respectively, identified when HIESCR is less (or greater) than BHIESCR. Second, it is shown BHIESCR remains almost unchanged as 3.0 versus various system parameters and rated operation variables based on rigorous theoretical analysis. This salient feature makes the proposed method more accurate than earlier methods. Finally, the proposed method is validated by simulations based on the PSCAD/EMTDC program.展开更多
Investigating flexibility and stability boosting transmission expansion planning(TEP)methods can increase the renewable energy(RE)consumption of the power systems.In this study,we propose a bi-level TEP method for vol...Investigating flexibility and stability boosting transmission expansion planning(TEP)methods can increase the renewable energy(RE)consumption of the power systems.In this study,we propose a bi-level TEP method for voltage-source-converter-based direct current(VSC-DC),focusing on flexibility and stability enhancement.First,we established the TEP framework of VSC-DC,by introducing the evaluation indices to quantify the power system flexibility and stability.Subsequently,we propose a bi-level VSC-DC TEP model:the upper-level model acquires the optimal VSC-DC planning scheme by using the improved moth flame optimization(IMFO)algorithm,and the lower-level model evaluates the flexibility through time-series production simulation.Finally,we applied the proposedVSC-DC TEPmethod to the modified IEEE-24 and IEEE-39 test systems,and obtained the optimalVSCDC planning schemes.The results verified that the proposed method can achieve excellent RE curtailment with high flexibility and stability.Furthermore,the well-designed IMFO algorithm outperformed the traditional particle swarm optimization(PSO)and moth flame optimization(MFO)algorithms,confirming the effectiveness of the proposed approach.展开更多
基金supported by the Technology Project of the State Grid Corporation Headquarters Management(Contract No.5100-202158467A-0-0-00).
文摘Voltage source converter based high voltage direct current(VSC-HVDC)can participate in voltage regulation by flexible control to help maintain the voltage stability of the power grid.In order to quantitatively evaluate its influence on the voltage interaction between VSC-HVDC and line commutated converter based high voltage direct current(LCC-HVDC),this paper proposes a hybrid multi-infeed interaction factor(HMIIF)calculation method considering the voltage regulation control characteristics of VSC-HVDC.Firstly,for a hybrid multi-infeed high voltage direct current system,an additional equivalent operating admittance matrix is constructed to characterize HVDC equipment characteristics under small disturbance.Secondly,based on the characteristic curve between the reactive power and the voltage of a certain VSC-HVDC project,the additional equivalent operating admittance of VSC-HVDC is derived.The additional equivalent operating admittance matrix calculation method is proposed.Thirdly,the equivalent bus impedance matrix is obtained by modifying the alternating current(AC)system admittance matrix with the additional equivalent operating admittance matrix.On this basis,the HMIIF calculation method based on the equivalent bus impedance ratio is proposed.Finally,the effectiveness of the proposed method is verified in a hybrid dual-infeed high voltage direct current system constructed in Power Systems Computer Aided Design(PSCAD),and the influence of voltage regulation control on HMIIF is analyzed.
文摘Modern power systems,employing an increasing number of converter-based renewable energy sources(RES)and decreasing the usage of conventional power plants,are leading to lower levels of short-circuit power and rotational inertia.A solution to this is the employment of synchronous condensers in the grid,in order to provide sufficient short-circuit power.This results in the increase of the short-circuit ratio(SCR)at transmission system busbars serving as points of interconnection(POI)to renewable generation.Evaluation of the required capacity and grid-location of the synchronous condensers,is inherently a mixed integer nonlinear optimization problem,which could not be done on manual basis considering each type of machine and all bus-bars.This study therefore proposes a method of optimal allocation of synchronous condensers in a hypothetic future scenario of a transmission system fed by renewable generation.Total cost of synchronous condenser installations in the system is minimized and the SCRs at the POIs of central renewable power plants are strengthened.The method has potential for application on larger grids,aiding grid-integration of RES.
基金supported in part by the National Natural Science Foundation of China(51907067)in part by the Industrial Research Chair Program of the Natural Sciences and Engineering Research Councilof Canada。
文摘Distinction of weak and strong AC grids for emerging hierarchical-infeed LCC-UHVDC systems is important for planning and operation departments. However, accuracy of earlier distinction methods is limited as they were developed by empirical reasoning without rigorous theoretical analysis. Hence in this letter, hierarchical-infeed interactive effective short-circuit ratio (HIESCR) index is first used for strength evaluation of HIDC systems with complex inter-inverter interactions considered. Boundary HIESCR (BHIESCR) is also introduced in the proposed distinction method of weak and strong AC grids. That is, weak (or strong) AC grids are, respectively, identified when HIESCR is less (or greater) than BHIESCR. Second, it is shown BHIESCR remains almost unchanged as 3.0 versus various system parameters and rated operation variables based on rigorous theoretical analysis. This salient feature makes the proposed method more accurate than earlier methods. Finally, the proposed method is validated by simulations based on the PSCAD/EMTDC program.
基金supported by the Science and Technology Project of Central China Branch of State Grid Corporation of China under Grant 52140023000T.
文摘Investigating flexibility and stability boosting transmission expansion planning(TEP)methods can increase the renewable energy(RE)consumption of the power systems.In this study,we propose a bi-level TEP method for voltage-source-converter-based direct current(VSC-DC),focusing on flexibility and stability enhancement.First,we established the TEP framework of VSC-DC,by introducing the evaluation indices to quantify the power system flexibility and stability.Subsequently,we propose a bi-level VSC-DC TEP model:the upper-level model acquires the optimal VSC-DC planning scheme by using the improved moth flame optimization(IMFO)algorithm,and the lower-level model evaluates the flexibility through time-series production simulation.Finally,we applied the proposedVSC-DC TEPmethod to the modified IEEE-24 and IEEE-39 test systems,and obtained the optimalVSCDC planning schemes.The results verified that the proposed method can achieve excellent RE curtailment with high flexibility and stability.Furthermore,the well-designed IMFO algorithm outperformed the traditional particle swarm optimization(PSO)and moth flame optimization(MFO)algorithms,confirming the effectiveness of the proposed approach.