This paper proposes a simple and fast way to determine the direction of a fault in a multi-terminal high voltage direct current(HVDC) grid by comparing the rate of change of voltage(ROCOV) values at either side of the...This paper proposes a simple and fast way to determine the direction of a fault in a multi-terminal high voltage direct current(HVDC) grid by comparing the rate of change of voltage(ROCOV) values at either side of the di/dt limiting inductors at the line terminals. A local measurement based secure and fast protection method is implemented by supervising a basic ROCOV relay with a directional element. This directional information is also used to develop a slower communication based DC line protection scheme for detecting high resistance faults. The proposed protection scheme is applied to a multi-level modular converter based three-terminal HVDC grid and its security and sensitivity are evaluated through electromagnetic transient simulations. A methodology to set the protection thresholds considering the constraints imposed by the breaker technology and communication delays is also presented. With properly designed di/dt limiting inductors,the ability of clearing any DC transmission system fault before fault currents exceeds a given breaker capacity is demonstrated.展开更多
文摘This paper proposes a simple and fast way to determine the direction of a fault in a multi-terminal high voltage direct current(HVDC) grid by comparing the rate of change of voltage(ROCOV) values at either side of the di/dt limiting inductors at the line terminals. A local measurement based secure and fast protection method is implemented by supervising a basic ROCOV relay with a directional element. This directional information is also used to develop a slower communication based DC line protection scheme for detecting high resistance faults. The proposed protection scheme is applied to a multi-level modular converter based three-terminal HVDC grid and its security and sensitivity are evaluated through electromagnetic transient simulations. A methodology to set the protection thresholds considering the constraints imposed by the breaker technology and communication delays is also presented. With properly designed di/dt limiting inductors,the ability of clearing any DC transmission system fault before fault currents exceeds a given breaker capacity is demonstrated.