The preliminary design of an arc chamber in the 550 kV SF6 circuit breaker was proposed in accordance with the technicai requirements and design experience. The structural optimization was carried out according to the...The preliminary design of an arc chamber in the 550 kV SF6 circuit breaker was proposed in accordance with the technicai requirements and design experience. The structural optimization was carried out according to the no-load flow field simulation results and verified by no-load pressure measurement. Based on load simulation results such as temperature field variation at the arc area and the tendency of post arc current under different recovery voltage, the second optimal design was completed and its correctness was certificated by a breaking test. Results demonstrate that the interrupting capacity of an arc chamber can be evaluated by the comparison of the gas medium recovery speed and post arc current growth rate.展开更多
断路器的弧后电流是断路器开断性能的重要参量,为了获取高精度、低干扰的弧后电流,本文提出了一种基于真空开关、转移电阻、保护间隙和高精度电流传感器构成的弧后电流测量方法,其中真空开关负责导通大电流,在电流过零前电流转移到转移...断路器的弧后电流是断路器开断性能的重要参量,为了获取高精度、低干扰的弧后电流,本文提出了一种基于真空开关、转移电阻、保护间隙和高精度电流传感器构成的弧后电流测量方法,其中真空开关负责导通大电流,在电流过零前电流转移到转移电阻上,然后利用高精度电流传感器间接测量弧后电流。建立了弧后电流装置的电流转移过程模型,分析了电流转移完成时刻和转移电流峰值受转移电阻、电流大小和真空开关刚分时刻的影响。基于仿真得到弧后电流测量装置的参数,设计了弧后电流测量装置样机,对转移电阻进行了特殊无感设计并与保护间隙实现配合保护。最后进行了10 k V真空断路器在合成回路试验中的弧后电流测量,在开断5 k A电流时,弧后电流峰值为500 m A左右,脉宽5μs,弧后测量干扰小,波形平滑。对比试验结果和前人研究成果,验证了基于电流转移原理的弧后电流测量装置的可行性和准确性。展开更多
多断口真空断路器的串联断口间动态介质恢复协同作用对其弧后特性、开断能力有影响。为此搭建了双断口真空断路器试验样机,进行了合成回路试验,旨在得到双断口真空断路器的动态介质恢复协同特性。研究了不同间隙、不同触头结构、不同均...多断口真空断路器的串联断口间动态介质恢复协同作用对其弧后特性、开断能力有影响。为此搭建了双断口真空断路器试验样机,进行了合成回路试验,旨在得到双断口真空断路器的动态介质恢复协同特性。研究了不同间隙、不同触头结构、不同均压电容对动双断口真空断路器开断能力的影响,得到了不同组合方式下的开断增益特性,试验结果表明:双断口真空断路器最佳的组合方式是横纵组合方式且横磁触头在高压侧,这是由于这种组合电压分布更加均匀,由于真空间隙的变化影响电压分布特性,进而得到横纵组合方式最佳的间隙配合特性。通过试验得到了不同触头结构灭弧室的组合均压电容大小对开断能力的影响,均压电容选取在500~2 000 p F为宜,且两个纵向磁场触头结构组合在同期动作下开断能力最强。展开更多
文摘The preliminary design of an arc chamber in the 550 kV SF6 circuit breaker was proposed in accordance with the technicai requirements and design experience. The structural optimization was carried out according to the no-load flow field simulation results and verified by no-load pressure measurement. Based on load simulation results such as temperature field variation at the arc area and the tendency of post arc current under different recovery voltage, the second optimal design was completed and its correctness was certificated by a breaking test. Results demonstrate that the interrupting capacity of an arc chamber can be evaluated by the comparison of the gas medium recovery speed and post arc current growth rate.
文摘断路器的弧后电流是断路器开断性能的重要参量,为了获取高精度、低干扰的弧后电流,本文提出了一种基于真空开关、转移电阻、保护间隙和高精度电流传感器构成的弧后电流测量方法,其中真空开关负责导通大电流,在电流过零前电流转移到转移电阻上,然后利用高精度电流传感器间接测量弧后电流。建立了弧后电流装置的电流转移过程模型,分析了电流转移完成时刻和转移电流峰值受转移电阻、电流大小和真空开关刚分时刻的影响。基于仿真得到弧后电流测量装置的参数,设计了弧后电流测量装置样机,对转移电阻进行了特殊无感设计并与保护间隙实现配合保护。最后进行了10 k V真空断路器在合成回路试验中的弧后电流测量,在开断5 k A电流时,弧后电流峰值为500 m A左右,脉宽5μs,弧后测量干扰小,波形平滑。对比试验结果和前人研究成果,验证了基于电流转移原理的弧后电流测量装置的可行性和准确性。
文摘多断口真空断路器的串联断口间动态介质恢复协同作用对其弧后特性、开断能力有影响。为此搭建了双断口真空断路器试验样机,进行了合成回路试验,旨在得到双断口真空断路器的动态介质恢复协同特性。研究了不同间隙、不同触头结构、不同均压电容对动双断口真空断路器开断能力的影响,得到了不同组合方式下的开断增益特性,试验结果表明:双断口真空断路器最佳的组合方式是横纵组合方式且横磁触头在高压侧,这是由于这种组合电压分布更加均匀,由于真空间隙的变化影响电压分布特性,进而得到横纵组合方式最佳的间隙配合特性。通过试验得到了不同触头结构灭弧室的组合均压电容大小对开断能力的影响,均压电容选取在500~2 000 p F为宜,且两个纵向磁场触头结构组合在同期动作下开断能力最强。