Designing a Protection Scheme in Micro-Grid Systems with DG Using Central Protection Unite and Multiple Setting Group Protection Relays
1
作者 Mostafa I. Saleh Gaber El-Saady +1 位作者 Ali M. Yousef El-Noby A. Ibrahim 《Journal of Power and Energy Engineering》 2024年第9期37-49,共13页
Distributed generators now is widely used in electrical power networks, in some cases it works seasonally, and some types works at special weather conditions like photo voltaic systems and wind energy, and due to this... Distributed generators now is widely used in electrical power networks, in some cases it works seasonally, and some types works at special weather conditions like photo voltaic systems and wind energy, and due to this continuous changes in generation condition, the fault current level in network will be affected, this changes in fault current level will affect in the coordination between protection relays and to keep the coordination at right way, an adaptive protection system is required that can adaptive its setting according to generation changes, the fault current level in each case is evaluated using ETAP software, and the required relay setting in each case is also evaluated using Grey Wolf Optimizer (GWO) algorithm, and to select suitable setting which required in each condition, to select the active setting group of protection relay according to generation capacity, central protection unite can be used, and to improve protection stability and minimizing relays tripping time, a proposed method for selecting suitable backup relay is used, which leads to decrease relays tripping time and increase system stability, output settings for relays in all cases achieved our constrains. 展开更多
关键词 Directional Overcurrent Relay Protection Coordination Distributed Generators Central Protection Unite Multiple Setting Group Protection Relay
下载PDF
Serial Failure Diagnosis of a Transmission Line Protection Relaying System by Petri Nets
2
作者 Zhang Zhiming Wang Yue +1 位作者 Tao Ran &Zhou Siyong Dept. of Electronics Engineering, Beijing Institute of Technology, 100081, P. R. China 《Journal of Systems Engineering and Electronics》 SCIE EI CSCD 2001年第1期59-64,共6页
With the development of large-scale complicated modern power systems, the requirement for the associated protection scheme tends to be more stringent and its combination more complex. However, it is very difficult to ... With the development of large-scale complicated modern power systems, the requirement for the associated protection scheme tends to be more stringent and its combination more complex. However, it is very difficult to figure out the factors of failure of such systems. This paper proposes a Petri net model of a transmission line protection relaying system, including three types of relays as well as an automatic reclosing device, and shows how to diagnose serial failure of the system by analyzing invariant sets of the model. Furthermore, it gives four basic types of failure sequences and its execution is much more intuitive and effective than the traditional method. 展开更多
关键词 Electric fault location Electric power system protection Electric relays Failure analysis Mathematical models Petri nets Relay protection
下载PDF
Teaching Protective Relaying Design and Application Using New Modeling and Simulation Tools
3
作者 Jinfeng Ren Mladen Kezunovic 《Journal of Energy and Power Engineering》 2012年第5期762-770,共9页
As the smart grid concepts are emphasized lately, the need to modernize the power engineering education is also well recognized. This paper presents a set of newly developed modeling, simulation and testing tools aime... As the smart grid concepts are emphasized lately, the need to modernize the power engineering education is also well recognized. This paper presents a set of newly developed modeling, simulation and testing tools aimed at better understanding of the design concept and related applications for protective relaying and substation automation solutions for the smart grid. Since the smart grid applications require integration of data from multiple IEDs (intelligent electronic devices), understanding properties of each IED type in detail, as well as their responses to the power system events is needed. In addition, understanding the communication requirements to perform data integration is also important. To illustrate how the mentioned smart grid issues may be taught, the following advanced teaching approaches are presented: (1) Use of modeling and simulation means to better understand interaction between the relays and power system; (2) Use of IED test facilities to better understand performance of physical devices used for protection, monitoring and control; (3) Utilization of communication network modeling tools to simulate the communication network within SAS (substation automation system). Examples showing the use of proposed techniques for teaching the fundamentals and applications are presented. The examples demonstrate the adequacy and efficiency of the proposed techniques. 展开更多
关键词 Smart grid power engineering education MODELING protective relaying SIMULATION lED (intelligent electronic device) SAS (substation automation system).
下载PDF
Reliability testing and reliability analysis of the over-load protective relay 被引量:4
4
作者 ZHAO Jing-ying CHEN Hong-jian +2 位作者 LIU Guo-jin ZHANG Yong WU Pin-hua 《Journal of Zhejiang University-Science A(Applied Physics & Engineering)》 SCIE EI CAS CSCD 2007年第3期475-480,共6页
The over-load protective relay is widely used directly affects the safe running of a motor. The reliability for motor protection. The reliability of the over-load protective relay testing and reliability analysis of t... The over-load protective relay is widely used directly affects the safe running of a motor. The reliability for motor protection. The reliability of the over-load protective relay testing and reliability analysis of the over-load protective relay is an important way to improve the reliability of products. In this paper, the reliability test method of the over-load protective relay is studied, and the reliability tests of the typical products are carried out on a reliability tester developed by authors. In terms of the testing results, the reliability analysis is finished. The failure reasons are found and the measures are put forward to improve the reliability of the products. 展开更多
关键词 Over-load protective relay protective success analysis ratio Sampling and checking plan Reliability testing Reliability analysis
下载PDF
The Automated System of Unified Templates as an Element of Trainability of Microprocessor Relay Protection Devices 被引量:1
5
作者 Viktor Nikolaevich Sizykh Aleksey Vasilyevich Daneev +1 位作者 Maksim Viktorovich Vostrikov Konstantin Vladimirovich Menaker 《Journal of Applied Mathematics and Physics》 2021年第12期3045-3057,共13页
The article discusses the possibility of further modernization of the standard microprocessor relay protection of AC overhead system feeders DPA-27.5-TNF, which is operated on the Trans-Baikal Railway by creating an a... The article discusses the possibility of further modernization of the standard microprocessor relay protection of AC overhead system feeders DPA-27.5-TNF, which is operated on the Trans-Baikal Railway by creating an additional automated system of unified templates necessary for the occurrence of “trainability” elements. The templates will be formed via a separate dedicated channel for transmission, processing and storage of the necessary information, not related to the operation of the terminal, with its subsequent visualization at the workplace of the duty personnel of traction substations, together with information from the “GID” software received via another dedicated wired channel. With the help of such a base of unified preset templates, in the future, it will be possible not only to identify the specific causes of each emergency shutdown but also to reduce their number by dynamically adjusting the existing presets of the standard operation algorithm. 展开更多
关键词 Automated system MICROPROCESSOR Relay Protection Devices FEEDER Traction Substation
下载PDF
A Design of 220 kV Line Protection Action Deduction System Based on Numerical Simulation
6
作者 Tiecheng Li Qingquan Liu +6 位作者 Hui Fan Xianzhi Wang Daming Zhou Junan Guo Lee Li Kun Zhou Yujie Hu 《Energy Engineering》 EI 2022年第5期2105-2134,共30页
Accurate conditions monitoring and early wrong action warnings of relay protection in the Smart Substation is the basic guarantee to realize the normal operation of primary and secondary system of the power grid.At pr... Accurate conditions monitoring and early wrong action warnings of relay protection in the Smart Substation is the basic guarantee to realize the normal operation of primary and secondary system of the power grid.At present,the traditional operation and maintenance monitoring methods of relay protections have poor timeliness,while some automatic monitoring methods have insufficient early warning performance,and lack the online action deduction function independent of the actual device.In this paper,a design method of integrated action deduction system including protection logic reasoning and software and hardware operation condition is proposed.The system can receive real-time operation information of protection online,simulate different types of faults,and output the recording information of sub modules belongs to the action deduction system.It can realize the online monitoring of device faults such as deducing the correctness of setting values at a certain time in the future,giving the wrong action warnings and predicting the probability of them as well,which effectively improves the operation and maintenance efficiency of the secondary system in the intelligent substation. 展开更多
关键词 Intelligent substation numerical simulation relay protection conditions monitoring wrong action warning
下载PDF
Fault Detection and Protection System of Electric Railway Substation
7
作者 Dae-Seok Kang Woo-Sik Won +1 位作者 Byung-Lib Ahn Byeong-Gon Lee 《Journal of Energy and Power Engineering》 2022年第4期147-155,共9页
The industrial power systems are moving to digital networks,and unmanned systems are increasing recently with the technological development of information and communication technology.In particular,reliability of syst... The industrial power systems are moving to digital networks,and unmanned systems are increasing recently with the technological development of information and communication technology.In particular,reliability of system operation is very important for stable power supply.Most industrial power distribution facilities use a 154 kV or 22.9 kV extra HV(high voltage)power system,and a special monitoring system is required because a large loss occurs when an error occurs in the power facility in the field.Although digital protection relay(IED;intelligent electronic device)and FR(fault recorder)are applied to the field to protect the power system,various improvement activities are still ongoing.In this paper,a 22.9 kV high-voltage panel and its test bed,which are widely used in railway stations,tunnels,substations and large plants,were tested as test subjects.The developed fault detection system automatically starts the AL(auto-lock)circuit or outputs an alarm signal to user by monitoring in real time problems such as CT(current transformer)-open and poor-contact that the existing digital protection relay cannot cover.In addition,it is intended to increase the safety and reliability of the power system by blocking various accidents in the system in advance and accurately analyzing the causes of faults with the developed fault detection system. 展开更多
关键词 CT open poor contact fault detection protection relay SUBSTATION HV panel
下载PDF
A Portable Multi-functional Real-time Digital Simulator Dedicated to Protective Relay Testing
8
作者 Liang Zhicheng Ma Xiandong +1 位作者 Wang Haixian Wang Like (Nanjing Automation Research Institute (NARI)) 《Electricity》 1998年第4期27-29,共3页
The paper intfoduces a PC-DSP based real-time digital simulator which is portable in size and aimed at the closed-loop testing of various types of protective relays for their design and application. The simulator can ... The paper intfoduces a PC-DSP based real-time digital simulator which is portable in size and aimed at the closed-loop testing of various types of protective relays for their design and application. The simulator can be widely used in not only concerning utilities but also manufacturers and research / certification institutes because of its many functions. The hardware architecture and software implementation of the simulator are described. The main features and functions of the simulator are also 展开更多
关键词 TIME A Portable Multi-functional Real-time Digital Simulator Dedicated to protective Relay Testing MMI
下载PDF
Reliability analysis for vertical integration of protection,measurement,merge unit,and intelligent terminal device 被引量:1
9
作者 Ying Li Weiquan Wang +3 位作者 Liang Zhang Zhujian Liang Zhenli Xu Yuansheng Liang 《Global Energy Interconnection》 EI CSCD 2023年第6期772-784,共13页
The reliability analysis of vertically integrated protection devices is crucial for designing International Electrotechnical Commission(IEC)61850-based substations.This paper presents the hardware architecture of a fo... The reliability analysis of vertically integrated protection devices is crucial for designing International Electrotechnical Commission(IEC)61850-based substations.This paper presents the hardware architecture of a four-inone vertically integrated device and the information transmission path of each function based on the functional information transmission chain of protection devices,measurement and control devices,merging units,and intelligent terminals.Additionally,a reliability analysis model of the protection device and its protection system is constructed using the fault tree analysis method while considering the characteristics of each module of the vertically integrated device.The stability probability of the protection system in each state is analyzed by combining the state-transfer equations of line and busbar protection with a Markov chain.Finally,the failure rate and availability of the protection device and its protection system are calculated under different ambient temperatures using a 110 kV intelligent substation as an example.The sensitivity of each device module is analyzed. 展开更多
关键词 Vertical integration of secondary system device Reliability of secondary system IEC 61850-based substation Relay protection
下载PDF
Operation Control Method of Relay Protection in Flexible DC Distribution Network Compatible with Distributed Power Supply 被引量:1
10
作者 Zihan Qi 《Energy Engineering》 EI 2023年第11期2547-2563,共17页
A novel operation control method for relay protection in flexible DC distribution networks with distributed power supply is proposed to address the issue of inaccurate fault location during relay protection,leading to... A novel operation control method for relay protection in flexible DC distribution networks with distributed power supply is proposed to address the issue of inaccurate fault location during relay protection,leading to poor performance.The method combines a fault-tolerant fault location method based on long-term and short-term memory networks to accurately locate the fault section.Then,an operation control method for relay protection based on adaptive weight and whale optimization algorithm(WOA)is used to construct an objective function considering the shortest relay protection action time and the smallest impulse current.The adaptive weight and WOA are employed to obtain the optimal strategy for relay protection operation control,reducing the action time and impulse current.Experimental results demonstrate the effectiveness of the proposed method in accurately locating faults and improving relay protection performance.The longest operation time is reduced by 4.7023 s,and the maximum impulse current is limited to 0.3 A,effectively controlling the impact of large impulse currents and enhancing control efficiency. 展开更多
关键词 Compatible distributed power supply FLEXIBILITY DC distribution network relay protection operation control
下载PDF
New Principle for Grounding Fault Feeder Detection in MV Distributions with Neutral Ineffectively Earthed 被引量:3
11
作者 曾祥君 尹项根 +1 位作者 陈德树 张哲 《Journal of Southeast University(English Edition)》 EI CAS 2000年第1期64-69,共6页
A new principle for grounding fault feeder detection based on negative sequence current variation and energy dissipated in the fault point is presented. It has high precision in both isolated systems and resonance ear... A new principle for grounding fault feeder detection based on negative sequence current variation and energy dissipated in the fault point is presented. It has high precision in both isolated systems and resonance earthed systems, even in full compensated systems. And it can be installed at the local control unit of feeder in distribution automation systems, such as field terminal unit (FTU). This principle is verified by EMTP simulator and experimentation. 展开更多
关键词 protective relaying fault detection distribution networks
下载PDF
Overvoltage Suppression for UHV Transmission Lines
12
作者 李永丽 刘太华 +3 位作者 李仲青 景雷 龙英 范建忠 《Transactions of Tianjin University》 EI CAS 2008年第3期222-225,共4页
The overvoltage phenomena of ultra high voltage (UHV) transmission lines are analyzed and verified by EMTDC/PSCAD simulation. Referring to the theoretical analyses and operating experiences of extra high voltage (EHV)... The overvoltage phenomena of ultra high voltage (UHV) transmission lines are analyzed and verified by EMTDC/PSCAD simulation. Referring to the theoretical analyses and operating experiences of extra high voltage (EHV) transmission lines in China and UHV transmission lines in Russia and Japan, the methods to suppress the internal overvoltage in UHV transmission lines by protection and control strategies are discussed. Through the cooperation among the recloser, shunt reactor, tripping and closing resistance, and metal oxide varistor(MOV), the overvoltage can be restrained within an acceptable level. 展开更多
关键词 OVERVOLTAGE RECLOSING relay protection shunt reactors SUPPRESSION UHV transmission lines
下载PDF
Application of double-layer Ether CAT and optical fiber interlock net in short circuit protection
13
作者 Yu-Mei WANG Xue-Bin LIU +1 位作者 Lei WANG Jian-Jun WANG 《Journal of Coal Science & Engineering(China)》 2013年第3期402-406,共5页
The selectivity of short circuit protection of high voltage lines in coal mines cannot be realized by existing protection systems. To solve this problem, a scheme based on double layer Ether CAT and optical fiber inte... The selectivity of short circuit protection of high voltage lines in coal mines cannot be realized by existing protection systems. To solve this problem, a scheme based on double layer Ether CAT and optical fiber interlock net was proposed. The system is mainly composed of double layer Ether CAT, optical fiber interlock net, ground monitoring station, underground control stations and integrated protection devices with Ether CAT communication interface and interlock interface. Double layer Ether CAT and optical fiber interlock net cooperate with each other, when one is interrupted, the other net carl realize selectivity of short circuit protection independently, Results of test show that the system can achieve selectivity of short circuit protection reliably, determine the fault location quickly, shorten troubleshooting time and improve safety and reliability of the power network in coal mines. 展开更多
关键词 coal mines relay protection ETHERNET optical fibers INTERLOCK
下载PDF
Simulation study on delay of end-to-end data communication for protective relaying in substations
14
作者 Huisheng GAO Weiwei JIN Guang LIU 《Frontiers of Electrical and Electronic Engineering in China》 CSCD 2008年第2期246-250,共5页
The end-to-end delay of protective relaying data flow in a substation was studied by dynamic simulation modeling technology.The distribution characteristics of protective relaying data flow and the constitution of the... The end-to-end delay of protective relaying data flow in a substation was studied by dynamic simulation modeling technology.The distribution characteristics of protective relaying data flow and the constitution of the end-to-end delay of messages were analyzed.The simulation model for digital communication between pro-tective relaying equipment and monitoring equipment of interval layer was suggested.The end-to-end delay of pro-tective relaying data flow in different network configurations was analyzed.It is found that the size and interval of the data frame,utilization of the link background and protocols of higher layer are key factors of real-time performance.Detailed analysis results are presented.A proposal for network configuration is suggested to reduce end-to-end delay of pro-tective relaying data flow. 展开更多
关键词 protective relaying OPNET network simu-lation DELAY
原文传递
Comprehensive Automation of Microprocessor Protection Relay Terminals Operated on AC Railways
15
作者 Vostrikov Maksim Viktorovich Daneev Aleksey Vasilyevich +1 位作者 Menaker Konstantin Vladimirovich Sizykh Viktor Nikolaevich 《Journal of Applied Mathematics and Physics》 2022年第2期491-503,共13页
The article discusses the possibility of a potential reduction in the number of operations of microprocessor relay protection of feeders of the contact network of AC railways TsZA-27.5-FKS (FTS) for unknown reasons. R... The article discusses the possibility of a potential reduction in the number of operations of microprocessor relay protection of feeders of the contact network of AC railways TsZA-27.5-FKS (FTS) for unknown reasons. Real statistics on the number of microprocessor relay protection operations at the Buryatskaya traction substation are presented, simulation of the real train situation (in accordance with the regime maps of the throughput capacity of the sections of the Trans-Baikal railway) was carried out in the specialized software complex “KORTES”. Based on the results of the analysis of simulation modeling, the process of forming a unified template of settings using neural network technologies is considered, which characterizes only this specific regular train situation. To protect objects in the event of pre-emergency and emergency modes of operation of the traction power supply system, a variant of changing the standard operation algorithm of the TsZA-27.5-FKS (FTS) terminal by introducing additional blocks for calculating the predictive functions of current and voltage has been proposed. 展开更多
关键词 Automated system MICROPROCESSOR Relay Protection Devices FEEDER Traction Substation
下载PDF
Analysis of Protective Relay Allocation and Operation in 220 kV and Above AC Systems
16
作者 Zhou Zexin Zhang Lie +10 位作者 Lv Pengfei Shen Hua Wang Delin Li Yanfei Liu Yu Wu Chunliang Shen Xiaofan Yang Guosheng Wang Wenhuan Yao Xue Liu Yadong 《Electricity》 2014年第5期1-7,共7页
This paper provides a comprehensive summary of the scale, allocation and operation situation of relay protection equipment of the 220 kV and above AC systems run by the State Grid Corporation of China in 2012 and 2013... This paper provides a comprehensive summary of the scale, allocation and operation situation of relay protection equipment of the 220 kV and above AC systems run by the State Grid Corporation of China in 2012 and 2013. It also analyzes the changing trend of the relevant indices of relay protection during the five years from 2009 to 2013. At the same time, it analyzes in detail two typical relay malfunction events in 2012 and 2013. 展开更多
关键词 power system relay protection statistics and analysis MALFUNCTION
原文传递
A Testing Method for Ratio Restraint Characteristics of Differential Relay Protection of Transformers
17
作者 Cao Zhihui Peng Chunyan Zhou Huaping 《Electricity》 2012年第5期44-47,共4页
In this paper, a method to calculate the slope of the ratio restraint characteristic of a transformer differential relay protection is proposed. The method allows using some concise but effective means to get the slop... In this paper, a method to calculate the slope of the ratio restraint characteristic of a transformer differential relay protection is proposed. The method allows using some concise but effective means to get the slope. Modulating the argument of current output from ONLLY testing equipment can make the relay protection device operate, thus, the data used for calculation would be obtained naturally after several trails. In order to make sure how effective that method could be, some experiment data is given as well. 展开更多
关键词 differential relay slope of ratio restraint characteristic relay testing relay protection of transformer
下载PDF
Influence of DFIG Wind Turbine Protection and Control during Voltage Dip on Circuit Breaker Operation
18
作者 Anssi Salomo Makinen Ontrei Raipala Sami Repo Heikki Tuusa 《Journal of Energy and Power Engineering》 2013年第1期126-138,共13页
This paper analyzes a DFIG (doubly fed induction generator) WT (wind turbine) fault current after a symmetrical network voltage dip. The goal is to identify the factors determining how fast the first zero crossing... This paper analyzes a DFIG (doubly fed induction generator) WT (wind turbine) fault current after a symmetrical network voltage dip. The goal is to identify the factors determining how fast the first zero crossings of the fault current occur. This is an important subject because the ftmdamental property of the CB (circuit breaker) is that it breaks the current when the current is very near zero. The study was conducted using a hardware-in-the-loop test environment constructed using two real time simulators (dSPACE and RTDS) and a commercial protection relay. It is found that the reactive current injection during a voltage dip demanded by the grid codes enhances the operation of the WT protection because the zero crossings of the currents through CB are attained earlier. In addition, the size of the crowbar resistance has a significant influence on the zero crossings. 展开更多
关键词 DFIG reactive current circuit breaker loss of mains relay protection.
下载PDF
Effective Ultra-High-Speed Identification Scheme of Lightning Strikes Suitable for VSC-Based DC Grids 被引量:1
19
作者 Longlong Chen Xiangyu Pei +2 位作者 Xiaoguang Wei Pengzhi Li Guangfu Tang 《CSEE Journal of Power and Energy Systems》 SCIE EI CSCD 2024年第2期548-561,共14页
To ensure their sound and continuous operation to the greatest extent,VSC-based DC girds have extremely stringent requirements for transmission line relay protection.In terms of guaranteeing their reliability,accurate... To ensure their sound and continuous operation to the greatest extent,VSC-based DC girds have extremely stringent requirements for transmission line relay protection.In terms of guaranteeing their reliability,accurate identification of lightning strikes on DC transmission lines is one of the urgent key problems to be solved.An effective ultra-high-speed identification scheme of lightning strikes suitable for the VSC-based DC grid is proposed in this paper.First,an 1-mode reverse voltage traveling wave(RVTW)is constructed applying the pole-mode transformation theory.Next,fault traveling wave propagation characteristics along the DC transmission line are analyzed in depth utilizing Peterson's law.Then,differences of time-frequency electromagnetic transient characteristics of 1-mode RVTWs between disturbances and faults caused by lightning strikes are distinguished in detail by means of the classical wavelet transformation multi-resolution analysis theory.Finally,extensive simulations are carried out to evaluate the performance of the proposed identification scheme,and by which its excellent rapidity,reliability and robustness are validated.Index Terms-Lightning-strike identification,Multi-resolution analysis,Relay protection,Traveling-wave protection,VsC-based DC grid,Wavelet transformation. 展开更多
关键词 Lightning-strike identification Multi-resolution analysis Relay protection Traveling-wave protection VsC-based DC grid Wavelet transformation
原文传递
Traveling Wave Based Single-Phase-to-Ground Protection Method for Power Distribution System 被引量:17
20
作者 Xinzhou Dong Jun Wang +3 位作者 Shenxing Shi Bin Wang Bak Dominik Miles Redfern 《CSEE Journal of Power and Energy Systems》 SCIE 2015年第2期75-82,共8页
Correct detection and identification of single-phase to-ground faults not effectively grounded in distribution systems is a major challenge for protection engineers.This paper proposes a novel traveling wave based pro... Correct detection and identification of single-phase to-ground faults not effectively grounded in distribution systems is a major challenge for protection engineers.This paper proposes a novel traveling wave based protection method to solve this problem.The proposed method compares the polarities of current and voltage traveling waves measured immediately after the fault inception to determine the fault direction.Nuisance tripping is avoided by using the power frequency voltages detected on the busbar to inhibit operation.The power frequency voltages ensure that the system does not mal-operate due to noise and also provide discrimination for phase-to-phase and three-phase faults.The wavelet transform and modulus maxima theories are used to extract the polarity of traveling waves measured at the relaying point.The simulation studies demonstrate correct operation of protection,which is independent of fault distance,fault inception angle,fault path resistance,and the method used for neutral grounding. 展开更多
关键词 Distribution systems relay protection singlephase-to-ground fault traveling wave wavelet transform
原文传递