It is important for the safety of transmission system to accurately calculate single-phase earth fault current distribution.Features of double sided elimination method were illustrated.Quantitative calculation of sing...It is important for the safety of transmission system to accurately calculate single-phase earth fault current distribution.Features of double sided elimination method were illustrated.Quantitative calculation of single-phase earth fault current distribution and case verification were accomplished by using the loop method.Influences of some factors,such as single-phase earth fault location and ground resistance of poles,on short-circuit current distribution were discussed.Results show that:1) results of the loop method conform to those of double sided elimination method;2) the fault location hardly influences macro-distribution of short-circuit current.However,current near fault location is evidently influenced;and 3) the short-circuit current distribution is not so sensitive to the ground resistance of poles.展开更多
建立了避雷线全线绝缘架设的输电线路雷击模型,研究了雷电流幅值、杆塔接地电阻和杆塔档距对杆塔处雷电流分配特性的影响规律。研究结果发现:雷电流较小的情况下,雷电流分配主要受避雷线绝缘间隙击穿个数的影响;如雷电流幅值为1 k A时,...建立了避雷线全线绝缘架设的输电线路雷击模型,研究了雷电流幅值、杆塔接地电阻和杆塔档距对杆塔处雷电流分配特性的影响规律。研究结果发现:雷电流较小的情况下,雷电流分配主要受避雷线绝缘间隙击穿个数的影响;如雷电流幅值为1 k A时,避雷线绝缘架设和直接接地时的分流系数最大差别为9%;雷电流幅值大于20 k A,击穿间隙个数等于或大于5个时,雷电流分配不再受避雷线绝缘架设的影响,而是主要受杆塔接地电阻的影响。因此计算线路的耐雷水平时不需要考虑避雷线绝缘架设的影响。展开更多
文摘It is important for the safety of transmission system to accurately calculate single-phase earth fault current distribution.Features of double sided elimination method were illustrated.Quantitative calculation of single-phase earth fault current distribution and case verification were accomplished by using the loop method.Influences of some factors,such as single-phase earth fault location and ground resistance of poles,on short-circuit current distribution were discussed.Results show that:1) results of the loop method conform to those of double sided elimination method;2) the fault location hardly influences macro-distribution of short-circuit current.However,current near fault location is evidently influenced;and 3) the short-circuit current distribution is not so sensitive to the ground resistance of poles.
文摘建立了避雷线全线绝缘架设的输电线路雷击模型,研究了雷电流幅值、杆塔接地电阻和杆塔档距对杆塔处雷电流分配特性的影响规律。研究结果发现:雷电流较小的情况下,雷电流分配主要受避雷线绝缘间隙击穿个数的影响;如雷电流幅值为1 k A时,避雷线绝缘架设和直接接地时的分流系数最大差别为9%;雷电流幅值大于20 k A,击穿间隙个数等于或大于5个时,雷电流分配不再受避雷线绝缘架设的影响,而是主要受杆塔接地电阻的影响。因此计算线路的耐雷水平时不需要考虑避雷线绝缘架设的影响。