Engineering Calculation Method of Electromagnetic Effect on Oil/Gas Pipelines from 1 000 kV AC Transmission Line Having Single-phase Ground Fault
1
作者 ZHANG Wenliang JIANG Jun +1 位作者 GUO Jian LU Jiayu 《高电压技术》 EI CAS CSCD 北大核心 2012年第9期2145-2149,共5页
关键词 交流输电线路 油气管道 故障分析 安全距离
下载PDF
Comparison between open phase fault of arc suppression coil and single phase to earth fault in coal mine distribution network 被引量:3
2
作者 LI Xiao-bo WANG Chong-lin 《Journal of China University of Mining and Technology》 EI 2008年第3期368-372,共5页
When, in a coal mine distribution network whose neutral point is grounded by an arc suppression coil (ASC), a fault occurs in the ASC, compensation cannot be properly realized. Furthermore, it can damage the safe and ... When, in a coal mine distribution network whose neutral point is grounded by an arc suppression coil (ASC), a fault occurs in the ASC, compensation cannot be properly realized. Furthermore, it can damage the safe and reliable run of the network. We first introduce a three-phase five-column arc suppression coil (TPFCASC) and discuss its autotracking compensation theory. Then we compare the single phase to ground fault of the coal mine distribution network with an open phase fault at the TPFCASC using the Thévenin theory, the symmetrical-component method and the complex sequence network respectively. The results show that, in both types of faults, zero-sequence voltage of the network will appear and the maximum magnitude of this zero-sequence voltage is different in both faults. Based on this situation, a protection for the open phase fault at the TPFCASC should be estab-lished. 展开更多
关键词 open phase PROTECTION single phase to ground fault three-phase five-column arc suppression coil (TPFCASC)
下载PDF
基于D-S证据理论的配电网接地故障原因综合辨识模型
3
作者 胡云鹏 都成刚 +4 位作者 齐军 郑日红 阿敏夫 张浩 梁永亮 《中国电力》 CSCD 北大核心 2024年第10期133-142,共10页
单相接地故障(single-phase-to-ground fault,SPGF)是配电网中最常见的故障,严重影响配电系统的可靠性和安全性,准确辨识SPGF可以提高配电网接地故障处理的精细化水平。首先,从故障波形中提取能有效反映不同接地故障原因的多域特征组成... 单相接地故障(single-phase-to-ground fault,SPGF)是配电网中最常见的故障,严重影响配电系统的可靠性和安全性,准确辨识SPGF可以提高配电网接地故障处理的精细化水平。首先,从故障波形中提取能有效反映不同接地故障原因的多域特征组成候选波形特征集,通过多元方差法分析波形特征与接地故障原因的相关性,筛选识别接地故障原因的有效特征;然后,分别设计基于极限学习机和支持向量机的故障原因辨识模型,利用Dempster-Shafer(D-S)证据融合理论对模型的识别结果进行融合,建立了接地故障原因综合辨识模型;最后,基于现场数据对所建立的综合辨识模型的有效性进行了验证,结果表明综合辨识模型优于任何单一辨识模型,验证了该模型的优势和可行性。 展开更多
关键词 接地故障原因 单相接地故障 极限学习机 支持向量机 D-S证据理论
下载PDF
Fault Line Selection Method Considering Grounding Fault Angle for Distribution Network 被引量:1
4
作者 Li Si-bo Zhao Yu-lin +1 位作者 Li Ji-chang Sui Tao 《Journal of Northeast Agricultural University(English Edition)》 CAS 2015年第1期58-65,共8页
In the distribution network system with its neutral point grounding via arc suppression coil, when single-phase grounding fault occurred near zero-crossing point of the phase voltage, the inaccuracy of the line select... In the distribution network system with its neutral point grounding via arc suppression coil, when single-phase grounding fault occurred near zero-crossing point of the phase voltage, the inaccuracy of the line selection always existed in existing methods. According to the characteristics that transient current was different between the fault feeder and other faultless feeders, wavelet transformation was performed on data of the transient current within a power frequency cycle after the fault occurred. Based on different fault angles, wavelet energy in corresponding frequency band was chosen to compare. The result was that wavelet energy in fault feeder was the largest of all, and it was larger than sum of those in other faultless feeders, when the bus broke down, the disparity between each wavelet energy was not significant. Fault line could be selected out by the criterion above. The results of MATLAB/simulink simulation experiment indicated that this method had anti-interference capacity and was feasible. 展开更多
关键词 distribution network single-phase grounding fault fault line selection fault angle wavelet transformation
下载PDF
基于SVMD-IGSA-RBF的井下单相接地故障线路选线方法
5
作者 沈少峰 牛元平 《机电工程技术》 2024年第7期225-230,共6页
为了解决井下小电流接地系统单相接地故障线路选线准确性不高的问题,提出了一种基于SVMD-IGSA-RBF神经网络模型的新型选线方法。首先,通过对故障线路的暂态特征进行分析,利用麻雀算法优化的变分模态分解(SVMD)进行数据特征提取,削弱无... 为了解决井下小电流接地系统单相接地故障线路选线准确性不高的问题,提出了一种基于SVMD-IGSA-RBF神经网络模型的新型选线方法。首先,通过对故障线路的暂态特征进行分析,利用麻雀算法优化的变分模态分解(SVMD)进行数据特征提取,削弱无效特征带来的影响。其次,利用优化算法的搜索系数、内部信息共享和通信机制对传统的引力搜索算法(GSA)进行改进,提高算法性能。然后,在解集中利用改进的引力搜索算法(IGSA)对RBF模型相关的超参数进行优化,并把经过SVMD处理的数据导入模型中,提高模型的收敛速度。最后,进行了MATLAB仿真及算法模型验证,实验证明SVMD-IGSA-RBF模型能够准确地识别故障线路,提高了对故障线路的准确选线。这一方法为井下小电流接地系统的故障诊断和维修提供了一种可靠的工具,具有重要的理论和实际意义。 展开更多
关键词 单相接地 故障特征 模态分解 引力搜索算法 径向基函数神经网络
下载PDF
基于电压-电流分区的灵活接地系统故障保护 被引量:2
6
作者 刘晓 薛永端 +2 位作者 刘萃萃 金鑫 徐丙垠 《电力系统及其自动化学报》 CSCD 北大核心 2023年第4期124-131,共8页
为进一步提升灵活接地(中性点经消弧线圈并联小电阻接地)系统接地保护方案的故障处理水平,保障供电系统安全稳定运行。本文通过分析灵活接地系统不同故障状态(并联小电阻投入前后)下健全区段和故障区段零序电压-电流分布特征,提出了基... 为进一步提升灵活接地(中性点经消弧线圈并联小电阻接地)系统接地保护方案的故障处理水平,保障供电系统安全稳定运行。本文通过分析灵活接地系统不同故障状态(并联小电阻投入前后)下健全区段和故障区段零序电压-电流分布特征,提出了基于电压-电流分区的灵活接地系统单相接地故障保护算法。当线路零序阻抗检测值低于定值时,保护动作,并考虑互感器测量精度的影响,设置最小动作电流及拐点电压,提高了该保护算法的灵敏度和可靠性。本方法原理简单,可有效识别系统所处状态并完成故障定位,不易受线路参数及过渡电阻影响,仿真分析和现场试验均验证了该方法的正确性和实用性。 展开更多
关键词 灵活接地系统 单相接地故障 系统状态辨识 电压-电流分区 故障定位
下载PDF
基于NGO-VMD-DE的单相接地故障信号特征提取 被引量:4
7
作者 王孔贤 邵英 王黎明 《电子测量技术》 北大核心 2023年第4期60-68,共9页
针对电力系统输配电线路发生单相接地故障时,电气设备的电磁环境干扰,故障零序电流成分复杂等原因导致故障特征信息提取困难,变分模态分解参数人为确定导致其对零序电流分解效果差,常用的熵运算慢,鲁棒性差,进而后续选线准确率低的问题... 针对电力系统输配电线路发生单相接地故障时,电气设备的电磁环境干扰,故障零序电流成分复杂等原因导致故障特征信息提取困难,变分模态分解参数人为确定导致其对零序电流分解效果差,常用的熵运算慢,鲁棒性差,进而后续选线准确率低的问题,提出了一种新的基于NGO-VMD-DE的单相接地故障的零序电流故障特征提取方法。首先,通过北方苍鹰优化算法(NGO)优化变分模态分解(VMD)实现零序电流信号的自适应分解,建立了自适应相关系数的本征模态函数(IMF)分量选取准则选取有效分量,然后对选取的分量进行重构,最后对重构后的信号进行散布熵(DE)计算以提取单相接地故障的零序电流故障特征,通过搭建模型进行仿真实验,并与近似熵、样本熵、模糊熵、排列熵等其他特征熵值指标进行对比表明,所提出的故障特征提取方法可以更加准确、有效地表征发生单相接地故障线路的零序电流故障信息。 展开更多
关键词 北方苍鹰优化算法 变分模态分解 相关系数 散布熵 单相接地故障 故障特征提取
下载PDF
Elman-Adaboost集成人工神经网络高压交流输电线路单相接地初始电压行波模量幅值比单端故障测距 被引量:4
8
作者 王勇棋 陈仕龙 +2 位作者 魏荣智 毕贵红 赵四洪 《电力科学与工程》 2023年第9期10-19,共10页
针对现有单端行波故障测距方法对高阻接地故障不灵敏、反射波波头识别不准等问题,提出了一种Elman-Adaboost集成人工神经网络高压交流输电线路单相接地初始电压行波模量幅值比单端故障测距的方法。首先,基于行波衰减原理,通过推导高压... 针对现有单端行波故障测距方法对高阻接地故障不灵敏、反射波波头识别不准等问题,提出了一种Elman-Adaboost集成人工神经网络高压交流输电线路单相接地初始电压行波模量幅值比单端故障测距的方法。首先,基于行波衰减原理,通过推导高压交流输电线路故障距离与线路首端初始暂态电压行波线模分量与零模分量幅值比之间的计算公式,发现两者存在与过渡电阻无关的非线性关系;其次,利用Elman-Adaboost集成人工神经网络拟合初始暂态电压行波线模分量与零模分量小波能量比和故障距离之间的关系,构建集成人工神经网络故障定位模型,通过该模型可直接得到高压交流输电线路故障位置。实验结果表明,方法精度不受过渡电阻影响,测距精度较高。 展开更多
关键词 单相接地 高压交流输电线路 模量幅值比 人工神经网络 单端故障测距
下载PDF
Grounding Systems for Power Supply Facilities
9
作者 Vladimir Anatolevich Konusarov Evgeniy Alekseevich Shutov Tatyana Evgenievna Turukina 《Energy and Power Engineering》 2019年第1期1-14,共14页
The goal of this work is creation of optimal grounding model at the substation 10/0.4 kV of the urban power distribution network. The electric current can pose a major threat to the man’s life and health. In addition... The goal of this work is creation of optimal grounding model at the substation 10/0.4 kV of the urban power distribution network. The electric current can pose a major threat to the man’s life and health. In addition to pose a threat for health, the rise of the short circuit, as a consequence of insulation faults, poses a threat to retirement of electric systems and fire risks. The reliable grounding system design has significant implications for protection of human being as well as for electrical facility protection. The set objective was performed on the base of analytical and software-based methods. Analytical method gives a qualitative indication at each step in analysis. It also allows evaluating the values effect on the result, but the method is not susceptible of tolerable accuracy, that is why analytical method serves as initial approximation in differentiating. Specified estimation can be performed in such software package as MATLAB or ETAP. Software-based estimation is based on the finite element method (FEM), the main advantage of which is the ability to create different forms of grounding and allows obtaining distribution graphs of the step potential on the earth’s surface and touch potential. The calculation results in comparison of analytical and software-based methods taking into account the grounding optimization. There are conclusions on the most effective ground network. 展开更多
关键词 grounding Device Current-Using Equipment Short-Circuit fault single phase-to-ground fault Main STEP Down Substation (MSDS) TN-C TN-S TN-C-S TT IT Indirect Contact STEP Potential FEM IEEE
下载PDF
风电场集电线路单相接地故障柔性电压消弧与动态保护新原理 被引量:1
10
作者 喻锟 杨理斌 +3 位作者 曾祥君 王沾 李理 卓超 《中国电机工程学报》 EI CSCD 北大核心 2024年第5期1789-1801,I0010,共14页
为解决风电场集电系统长期存在的线路单相接地故障处理难题,提出风电场中性点柔性接地方式,理论推导获得柔性接地风电场三序等效电路,与集电线路单相接地故障复合序网模型,建立风电场零序电压柔性调控理论,提出集电线路单相接地故障柔... 为解决风电场集电系统长期存在的线路单相接地故障处理难题,提出风电场中性点柔性接地方式,理论推导获得柔性接地风电场三序等效电路,与集电线路单相接地故障复合序网模型,建立风电场零序电压柔性调控理论,提出集电线路单相接地故障柔性电压消弧方法,可主动将故障点电压及故障残流迅速抑制到零,实现单相接地故障电弧的可靠消除。进一步提出基于零序电流动态增量的高阻故障辨识与保护方法,通过柔性调控零序补偿电流,逐渐放大故障残流,实现永久性单相接地故障的灵敏感知与保护。利用PSCAD/EMTDC搭建含双馈异步风电机(doubly-fedinduction generator,DFIG)的规模化风电场模型,模拟多种运行与故障条件对所提方法进行验证,仿真结果表明,该方法能够在考虑系统不平衡电压的情况下精准调控集电线路故障点电压,实现瞬时性单相接地故障快速可靠消弧,动态感知并持续抑制永久性单相接地故障残流,实现集电线路高阻接地故障的灵敏保护。该技术有望提升风电场运行灵活性与故障防御能力,有力保障新能源电能外送的持续性、可靠性。 展开更多
关键词 集电线路 柔性接地 单相接地故障 电压消弧 动态保护
下载PDF
基于有源消弧暂态衰减信息的配电网接地故障跟踪检测方法 被引量:1
11
作者 刘宝稳 万子雄 +2 位作者 曾祥君 张慧芬 马宏忠 《中国电机工程学报》 EI CSCD 北大核心 2024年第2期464-475,I0003,共13页
现有配电网单相接地故障检测技术缺乏消弧过程的故障程度跟踪与选线能力。该文充分利用消弧过程中的暂态信息,建立考虑线路参数不对称的集总参数等效模型,论证消弧过程零序电压衰减直流特征的物理意义,提出考虑快速消弧的配电网故障检... 现有配电网单相接地故障检测技术缺乏消弧过程的故障程度跟踪与选线能力。该文充分利用消弧过程中的暂态信息,建立考虑线路参数不对称的集总参数等效模型,论证消弧过程零序电压衰减直流特征的物理意义,提出考虑快速消弧的配电网故障检测新方法,对于低、高阻接地故障均有较高的检测灵敏度。实际应用中,仅需观测消弧全补偿电流投切过程中零序电压及零序电流波形,即可实现过渡电阻测量、故障程度跟踪与故障选线,具有瞬时性故障实时跟踪、故障检测与故障消弧同步进行的优势,操作简单、易于实现。仿真实验证实了方法的有效性,为配电网故障检测提供了新的理论依据。 展开更多
关键词 单相接地故障 有源柔性接地 衰减直流特征 过渡电阻辨识 故障选线
下载PDF
基于FTU的配电网单相接地故障定位与恢复方法 被引量:3
12
作者 彭军林 石勇 +2 位作者 于哲 曾先锋 笃峻 《电器与能效管理技术》 2024年第2期72-78,共7页
配电网发生最多的故障是接地故障。针对准确地检测隔离接地故障线路并尽快恢复供电,提出基于配电开关监控终端(FTU)的配电网单相接地故障定位与恢复方法。利用配电网各节点FTU的小波包变换暂态选线及相电流暂态特征选线技术,结合故障路... 配电网发生最多的故障是接地故障。针对准确地检测隔离接地故障线路并尽快恢复供电,提出基于配电开关监控终端(FTU)的配电网单相接地故障定位与恢复方法。利用配电网各节点FTU的小波包变换暂态选线及相电流暂态特征选线技术,结合故障路径自适应处理控制策略,配合首开关延时合闸逻辑,从而实现多分支配电网故障定位与自动隔离恢复。所提方法能够快速选出故障线路并隔离故障区段,有利于故障快速消除,提高系统运行的安全性、可靠性。 展开更多
关键词 单相接地故障 小波包 故障定位 自动隔离恢复 配电开关监控终端
下载PDF
配电网中性点柔性接地装置四象限运行机理与控制方法
13
作者 曾祥君 贺世庚 +4 位作者 喻锟 李理 卓超 杨理斌 李佳政 《中国电机工程学报》 EI CSCD 北大核心 2024年第21期8406-8420,I0007,共16页
针对现有配电网柔性接地装置在进行接地故障处置时,易因网侧能量倒灌而导致直流侧电压失稳,甚至直流电容击穿的问题,分析注入电流与中性点电压间相角差随系统参数的变化规律,揭示系统参数变化对柔性接地装置输出有功功率、能量流向的影... 针对现有配电网柔性接地装置在进行接地故障处置时,易因网侧能量倒灌而导致直流侧电压失稳,甚至直流电容击穿的问题,分析注入电流与中性点电压间相角差随系统参数的变化规律,揭示系统参数变化对柔性接地装置输出有功功率、能量流向的影响机理,阐明造成系统能量倒灌的内在原因。在此基础上,提出一种具备四象限运行功能的柔性接地装置拓扑结构,在整流侧采用电压型三相半桥可控整流拓扑,并经配电变压器接入电网,能够维持能量在装置内双向流通,提升直流侧电压稳定性,同时实现直流侧供电自给。进一步提出基于四象限运行柔性接地装置的多目标复合控制方法,通过dq旋转坐标系下整流双环控制实现装置整流网侧单位功率因数运行及直流侧电压稳定,并由逆变侧控制对中性点电压进行快速精准调控。在PSIM(power simulation)仿真环境与10 kV真型配电网实验场中模拟各种运行和故障工况,对所提装置运行机理和控制方法进行验证,仿真与实验结果表明四象限运行柔性接地装置能有效解决现有柔性接地装置在网侧能量倒灌条件下直流侧电压失稳的问题,提升装置的运行和调控性能,实现接地故障快速安全可靠处置。 展开更多
关键词 四象限运行 控制方法 柔性接地装置 配电网 单相接地故障
下载PDF
基于系统参数优化的对称双极海上风电送端联接变阀侧单相接地故障应力调控方法
14
作者 杨鸣 刘威 +3 位作者 司马文霞 徐狄 袁涛 孙魄韬 《高电压技术》 EI CAS CSCD 北大核心 2024年第10期4640-4654,共15页
为应对海上风电系统送端联接变阀侧单相接地故障引起的换流阀内过电压、过电流及风电场并网点电压跌落共存的问题,提出了一种基于系统参数优化的对称双极海上风电系统故障应力调控方法。首先,构建换流阀的数学模型与风电机组控制模型,... 为应对海上风电系统送端联接变阀侧单相接地故障引起的换流阀内过电压、过电流及风电场并网点电压跌落共存的问题,提出了一种基于系统参数优化的对称双极海上风电系统故障应力调控方法。首先,构建换流阀的数学模型与风电机组控制模型,通过电路分析揭示故障后换流阀过电压和过电流特性、风电场并网点电压跌落特性及其影响规律;其次,根据系统关键参数对故障后电压和电流的影响机制,提出一种基于系统参数优化的故障应力调控方案,即通过系统关键参数优化配置,实现过电压、过电流以及并网点电压跌落的综合调控,显著延长系统故障后换流阀的耐受时间和风电场不脱网运行时间;最后,通过对称双极海上风电经柔性直流系统仿真分析,验证了本文所提出方法对系统故障应力调控的有效性,为海上风电优化设计提供支撑。 展开更多
关键词 优化 对称双极 海上风电 阀侧单相接地故障 过电压 过电流 并网点电压
下载PDF
故障相桥臂转移接地消弧装置直流侧电压控制方法
15
作者 郭谋发 刘鑫斌 +2 位作者 张彬隆 赵国军 郑泽胤 《电力系统保护与控制》 EI CSCD 北大核心 2024年第19期1-14,共14页
为解决传统三相直挂式柔性消弧装置非故障相桥臂承担线电压的问题,提出一种故障相桥臂转移接地的消弧方法。该方法通过开关控制故障相桥臂转移接地,母线电压由故障相桥臂与非故障相桥臂共同承担,三相桥臂共同输出电流,以实现消弧。针对... 为解决传统三相直挂式柔性消弧装置非故障相桥臂承担线电压的问题,提出一种故障相桥臂转移接地的消弧方法。该方法通过开关控制故障相桥臂转移接地,母线电压由故障相桥臂与非故障相桥臂共同承担,三相桥臂共同输出电流,以实现消弧。针对级联H桥直流侧需独立供电的问题,提出分布式电压平衡换流调制方法。该调制方法根据H桥输出状态和电流方向对直流侧电容充放电的影响,有选择地改变H桥的输出状态,进而实现直流侧电压的稳定。使用该调制方法的消弧装置无须在直流侧配备独立供电电源,在消弧过程中能保持H桥直流侧电压稳定。最后,采用Matlab/Simulink仿真软件对所提方法进行验证,仿真结果证明了所提方法的有效性。 展开更多
关键词 单相接地故障 级联H桥变流器 直流侧电压 消弧 转移接地
下载PDF
配电网间歇性重燃电弧模型的建立与断续弧光接地故障特征分析研究 被引量:2
16
作者 张彪 周申培 +4 位作者 吴细秀 侯博文 侯慧 邱进 丁心志 《电网技术》 EI CSCD 北大核心 2024年第5期2207-2217,I0116-I0120,共16页
电弧间歇性重燃是配电网单相接地故障最显著的特征。现有的电弧模型甚少考虑电弧间歇性重燃特性,导致无法精确描述断续弧光接地特征,进而影响继电保护动作。为此,论文提出一种间歇性重燃电弧模型的建立方法,并在此基础上对断续弧光接地... 电弧间歇性重燃是配电网单相接地故障最显著的特征。现有的电弧模型甚少考虑电弧间歇性重燃特性,导致无法精确描述断续弧光接地特征,进而影响继电保护动作。为此,论文提出一种间歇性重燃电弧模型的建立方法,并在此基础上对断续弧光接地故障特征进行了分析。弧道阻抗的随机变化是电弧间歇性重燃的重要标志,故论文重点围绕弧道阻抗变化的随机性和重燃时间间隔的随机性开展间歇性重燃电弧模型的研究。黑盒电弧模型中,Cassie-Mayr联合模型能完整的描述电弧电流从大电流到小电流的变化过程,但存在从大电流变化为小电流的判据模糊,转换过程突变的问题。为此,论文通过引入连续过渡函数解决上述问题。同时,为描述弧道电阻的变化特性,利用Fermi函数对联合模型中Mayr模型和Cassie模型进行权重分配。以改进的Cassie-Mayr单次燃弧模型为基础,根据工频熄弧理论,通过设置燃弧时间长短表征间歇性重燃的随机性,从而建立了间歇性重燃电弧模型。利用该模型,对典型10kV配电网单辐射型网架结构的接地故障进行模拟仿真,采用快速傅里叶变换(fast Fourier transform,FFT)和小波包分析提取了不同条件下故障电压、电流、高次谐波、零序分量以及频率分布等故障特征。研究结果表明:改进后Cassie-Mayr联合模型不但解决了电弧电流从大电流到小电流的转换突变问题,且不同模型权重占比的分配更能准确地表征实际燃弧弧道阻抗变化的随机性;通过设置电弧燃弧时间长短,准确地描述间歇性重燃的随机性;电弧断续时刻为非整数周期下的过电压、过电流幅值高于整数周期;电缆线路增大了故障线路电流,过电流可达3.81~7.20pu,不利于熄弧;大电流系统故障相零序电流主频在0~400Hz,小电流系统故障相零序电流主频在1200~1600Hz。 展开更多
关键词 配电网 单相接地故障 间歇性重燃电弧模型 中性点接地 小波包分析
下载PDF
基于模型识别的有源配电网单相接地故障定位方法 被引量:1
17
作者 许守东 欧阳金鑫 +3 位作者 陈宇捷 陈纪宇 王建 熊小伏 《电力系统保护与控制》 EI CSCD 北大核心 2024年第5期51-60,共10页
分布式电源(distributed generation,DG)大量接入使配电网继电保护面临严峻挑战。单相接地故障发生概率大,但故障信息十分微弱,特别是在DG多样化故障输出特性的影响下,有源配电网单相故障定位的准确性常难以保证。为此,提出了一种基于... 分布式电源(distributed generation,DG)大量接入使配电网继电保护面临严峻挑战。单相接地故障发生概率大,但故障信息十分微弱,特别是在DG多样化故障输出特性的影响下,有源配电网单相故障定位的准确性常难以保证。为此,提出了一种基于模型识别的有源配电网单相接地故障定位方法。分析了配电网单相接地故障下DG的输出特性,建立了在不同故障位置下有源配电网的正序增广网络,构建了故障位置关于馈线出口以及DG输出电流的函数,建立了配电网单相接地故障位置模型,利用不同故障位置下短路电流矢量占比系数的差异性构建了新的故障定位判据。通过将单相接地故障定位问题转化为故障位置模型系数的求解问题,提高了故障定位的准确性和实用性。理论和仿真分析表明,在不同故障位置、不同过渡电阻下均能准确定位单相接地故障,具有原理清晰、故障特征量采集便捷、灵敏性和可靠性高的优点。 展开更多
关键词 配电网 分布式电源 单相接地故障 故障区段定位 故障测距
下载PDF
基于低压侧负序量特征的小电流系统单相接地故障检测方法 被引量:1
18
作者 张明泽 栾文鹏 +1 位作者 艾欣 徐丙垠 《电网技术》 EI CSCD 北大核心 2024年第4期1654-1662,I0079,共10页
随着台区智能终端量测技术的逐步成熟,实现低压侧全息感知的同时,具备对上级中压配网的多点监测能力。提出基于低压侧负序量特征的小电流系统单相接地故障检测方法。分析了中压侧发生单相接地故障后低压侧负序量的变化规律;利用负序电... 随着台区智能终端量测技术的逐步成熟,实现低压侧全息感知的同时,具备对上级中压配网的多点监测能力。提出基于低压侧负序量特征的小电流系统单相接地故障检测方法。分析了中压侧发生单相接地故障后低压侧负序量的变化规律;利用负序电流大小区分故障线路和非故障线路;提出通过负序电压与正序电压的比值系数,多点协同计算对比判断故障点区段位置,且考虑了低压侧不平衡负荷,以及故障点位于线路一端的特殊情况。通过MATLAB软件和动模实验对中低压联合配电系统的仿真计算,验证了所提方法具有良好的鲁棒性和准确性。通过智能配变终端监测上级中压配网负序量信息,实现小电流接地系统故障检测,具有实际应用和推广价值。 展开更多
关键词 故障检测 单相接地故障 小电流系统 低压量测 负序量
下载PDF
基于改进Hough变换的消弧线圈接地配电网故障选线新方法 被引量:3
19
作者 郭亮 屈新宇 +3 位作者 王晓卫 王毅钊 田影 张帆 《中国电力》 CSCD 北大核心 2024年第7期132-142,共11页
针对配电网在电压过零点和高阻故障时刻选线不准确的问题,提出一种适用于谐振接地系统单相接地故障的选线新方法,利用优化后的变分模态分解对各馈线零序功率进行处理,遴选出与原始零序功率相关强度最高的本征模态函数IMF(k),将IMF(k)转... 针对配电网在电压过零点和高阻故障时刻选线不准确的问题,提出一种适用于谐振接地系统单相接地故障的选线新方法,利用优化后的变分模态分解对各馈线零序功率进行处理,遴选出与原始零序功率相关强度最高的本征模态函数IMF(k),将IMF(k)转换为JPG格式的二维图像,再利用Hough变换检测技术,得到故障起始阶段IMF(k)的拟合直线及夹角;对各支路模态量拟合直线夹角进行比对处理,将最小综合相关系数值对应的馈线确定为故障馈线;仿真结果表明:该方法不受接地电阻、故障相角、噪声干扰、数据缺失等因素的影响,验证了所提方法的有效性。 展开更多
关键词 单相接地故障 二维图像 HOUGH变换 综合相关系数 故障选线
下载PDF
基于柔性调控零序电压的不平衡配电网故障检测方法 被引量:2
20
作者 张炜祺 王连辉 +2 位作者 薛永端 徐丙垠 王超 《电力系统保护与控制》 EI CSCD 北大核心 2024年第11期159-169,共11页
在柔性消弧过程中实现故障选线、过渡电阻测量与故障性质判定对现有配电网单相接地故障检测具有重要意义。针对配电网三相对地参数不对称的柔性接地系统,首先分析不平衡零序电压对消弧效果的影响,提出柔性消弧全补偿电流的计算方法。然... 在柔性消弧过程中实现故障选线、过渡电阻测量与故障性质判定对现有配电网单相接地故障检测具有重要意义。针对配电网三相对地参数不对称的柔性接地系统,首先分析不平衡零序电压对消弧效果的影响,提出柔性消弧全补偿电流的计算方法。然后分析正常运行状态下和单相接地故障状态下注入电流和母线零序电压之间的约束关系。结果表明:无论系统处于何种状态,均可通过改变注入电流来柔性调控母线零序电压,进而调控各线路零序电流。并根据柔性调控零序电压前后各线路零序电流的变化规律,提出一种可实现故障选线、过渡电阻测量和故障性质判定的故障检测方法。Matlab/Simulink仿真验证了该方法的有效性和准确性。 展开更多
关键词 单相接地故障 零序电压 三相参数不对称 零序电流 故障选线 过渡电阻测量
下载PDF