The exergy analysis and finite time thermodynamic methods had been employed to analyze the compound condensation process (CCP). It was based on the air-cooling heat pump unit. The cooling capacity of the chiller unit ...The exergy analysis and finite time thermodynamic methods had been employed to analyze the compound condensation process (CCP). It was based on the air-cooling heat pump unit. The cooling capacity of the chiller unit is about 1 kW, and the work refrigerant is R22/R407C/R410A/CO2. The MATLAB/SIMULINK software was employed to build the simulation model. The thermodynamic simulation model is significant for the optimization of parameters of the unit, such as condensation and evaporation temperature and mass flow of the sanitary hot water and size of hot water storage tank. The COP of the CCP of R410A system is about 3% - 5% higher than the CCP of the R22 system, while CCP of the R407C system is a little lower than the CCP of R22 system. And the CCP of CO2 trans-critical system has advantage in the hot supply mode. The simulation method provided a theoretical reference for developing the production of CCP with substitute refrigerant R407C/R410A/CO2.展开更多
Both the modeling and the load regulation capacity prediction of a supercritical power plant are investigated in this paper. Firstly, an indirect identification method based on subspace identification method is propos...Both the modeling and the load regulation capacity prediction of a supercritical power plant are investigated in this paper. Firstly, an indirect identification method based on subspace identification method is proposed. The obtained identification model is verified by the actual operation data and the dynamic characteristics of the system are well reproduced. Secondly, the model is used to predict the load regulation capacity of thermal power unit. The power, main steam pressure, main steam temperature and other parameters are simulated respectively when the unit load is going up and down. Under the actual constraints, the load regulation capacity of thermal power unit can be predicted quickly.展开更多
The PLC and upper computer are used in BOP control system of traditional thermal power plant to monitor the in-situ equipment. It is complicated and wastes labor and resources. It is difficult to maintain and manage t...The PLC and upper computer are used in BOP control system of traditional thermal power plant to monitor the in-situ equipment. It is complicated and wastes labor and resources. It is difficult to maintain and manage them. Beijing GuoDian ZhiShen Control Technology applied the homemade DCS (EDPF-NT System) to the integrated BOP control system of 600-MW supercritical power unit, which offers advantages in efficiency promotion, cost reduction and resource sharing. That also reflects the dominance of EDPF-NT System in performance, price, real-time DUP, network compatibility and communication. This article introduces the main characteristics, structure and configuration of EDPF-NT System, as well as the hierarchical operation, the multi-domain network structure and the private network router developed for Zhuanghe Power Plant.展开更多
Ultra-supercritical(USC) unit is more and more popular in coal-fired power industry.In this paper,closed-loop identification based on subspace model identification(SMI) is introduced for superheated steam temperature ...Ultra-supercritical(USC) unit is more and more popular in coal-fired power industry.In this paper,closed-loop identification based on subspace model identification(SMI) is introduced for superheated steam temperature system of USC unit.Closed-loop SMI is applied to building step response model of the unit directly.The parameters selection method is proposed to deal with the parameter sensitivity and improve the reliability of the model.Finally,the model is used in model identification of real USC unit.展开更多
The experiment was conducted to investigate the heat transfer performance of supercritical CO_2 in a casing heat exchanger by comparing their heat transfer,entropy production unit number,non-dimensional entropy produc...The experiment was conducted to investigate the heat transfer performance of supercritical CO_2 in a casing heat exchanger by comparing their heat transfer,entropy production unit number,non-dimensional entropy production rate and field synergy factor.The results show that both heat transfer and entropy production unit number in four tubes decrease with water temperature increasing.Heat transfer and entropy production unit number in multiple tubes( i. e.,triple straight tube and double helix tube) is higher than their single counterparts; the non-dimensional entropy production rate increases with water temperature. Non-dimensional entropy production rate of triple straight tube and double helix tube is far below the single tube. Field synergy factor of double helix tube is much higher than that of the triple straight tube under the same condition. Further experiment was carried out in double helix tube,under various CO_2 pressure and inlet water temperature,the results are analyzed and reported in this paper.展开更多
文摘The exergy analysis and finite time thermodynamic methods had been employed to analyze the compound condensation process (CCP). It was based on the air-cooling heat pump unit. The cooling capacity of the chiller unit is about 1 kW, and the work refrigerant is R22/R407C/R410A/CO2. The MATLAB/SIMULINK software was employed to build the simulation model. The thermodynamic simulation model is significant for the optimization of parameters of the unit, such as condensation and evaporation temperature and mass flow of the sanitary hot water and size of hot water storage tank. The COP of the CCP of R410A system is about 3% - 5% higher than the CCP of the R22 system, while CCP of the R407C system is a little lower than the CCP of R22 system. And the CCP of CO2 trans-critical system has advantage in the hot supply mode. The simulation method provided a theoretical reference for developing the production of CCP with substitute refrigerant R407C/R410A/CO2.
文摘Both the modeling and the load regulation capacity prediction of a supercritical power plant are investigated in this paper. Firstly, an indirect identification method based on subspace identification method is proposed. The obtained identification model is verified by the actual operation data and the dynamic characteristics of the system are well reproduced. Secondly, the model is used to predict the load regulation capacity of thermal power unit. The power, main steam pressure, main steam temperature and other parameters are simulated respectively when the unit load is going up and down. Under the actual constraints, the load regulation capacity of thermal power unit can be predicted quickly.
文摘The PLC and upper computer are used in BOP control system of traditional thermal power plant to monitor the in-situ equipment. It is complicated and wastes labor and resources. It is difficult to maintain and manage them. Beijing GuoDian ZhiShen Control Technology applied the homemade DCS (EDPF-NT System) to the integrated BOP control system of 600-MW supercritical power unit, which offers advantages in efficiency promotion, cost reduction and resource sharing. That also reflects the dominance of EDPF-NT System in performance, price, real-time DUP, network compatibility and communication. This article introduces the main characteristics, structure and configuration of EDPF-NT System, as well as the hierarchical operation, the multi-domain network structure and the private network router developed for Zhuanghe Power Plant.
基金National Natural Science Foundation of China(No.60974119)
文摘Ultra-supercritical(USC) unit is more and more popular in coal-fired power industry.In this paper,closed-loop identification based on subspace model identification(SMI) is introduced for superheated steam temperature system of USC unit.Closed-loop SMI is applied to building step response model of the unit directly.The parameters selection method is proposed to deal with the parameter sensitivity and improve the reliability of the model.Finally,the model is used in model identification of real USC unit.
基金Hujiang Foundation of China(No.D14003)Yangtze River Delta Technology Joint Research,China(No.10195811000)
文摘The experiment was conducted to investigate the heat transfer performance of supercritical CO_2 in a casing heat exchanger by comparing their heat transfer,entropy production unit number,non-dimensional entropy production rate and field synergy factor.The results show that both heat transfer and entropy production unit number in four tubes decrease with water temperature increasing.Heat transfer and entropy production unit number in multiple tubes( i. e.,triple straight tube and double helix tube) is higher than their single counterparts; the non-dimensional entropy production rate increases with water temperature. Non-dimensional entropy production rate of triple straight tube and double helix tube is far below the single tube. Field synergy factor of double helix tube is much higher than that of the triple straight tube under the same condition. Further experiment was carried out in double helix tube,under various CO_2 pressure and inlet water temperature,the results are analyzed and reported in this paper.