Influences of Resistor-Type Superconducting Fault Current Limiter on Power System Transient Stability with Asymmetrical Short-Circuit Faults 被引量:1
1
作者 Xue-Ping Gu Zhi-Long Yang 《Journal of Electronic Science and Technology of China》 2008年第2期101-107,共7页
The transient stability of a single machine to infinite-busbar power system with resistortype superconducting fault current limiters (SFCL) is analyzed under asymmetrical short-circuit fault conditions. The SFCL is ... The transient stability of a single machine to infinite-busbar power system with resistortype superconducting fault current limiters (SFCL) is analyzed under asymmetrical short-circuit fault conditions. The SFCL is considered to introduce a resistance into the three-phase circuits when faults occur. Based on the power-angle curves for different short-circuit conditions of the single-line to ground, double-line to ground and line to line short-circuit faults, the influences of the SFCLs on transient stability are analyzed in detail. The time-domain simulation of transient stability is carried out to verify the analytical results. 展开更多
关键词 Equal-area criterion power angle curves power systems resistor-type SFCL transientstability.