期刊文献+
共找到2篇文章
< 1 >
每页显示 20 50 100
FAULT LOCATION ESTIMATION FOR TWO-LINE FAULT INVOLVING DIFFERENT PHASES FROM EACH OF PARALLEL LINES 被引量:1
1
作者 张庆超 李铁 +1 位作者 张尧 宋文南 《Transactions of Tianjin University》 EI CAS 2001年第2期109-112,共4页
A novel numerical algorithm of fault location estimation for double line to ground fault involving different phases from each of two parallel lines is presented in this paper.It is based on the one terminal voltag... A novel numerical algorithm of fault location estimation for double line to ground fault involving different phases from each of two parallel lines is presented in this paper.It is based on the one terminal voltage and current data.The loop and nodal equations comparing faulted phase with non faulted phase of two parallel lines are introduced in the fault location estimation models,in which the source impedance of a remote end is not involved.The effects of load flow and fault resistance on the accuracy of fault location are effectively eliminated,therefore precise algorithms of locating fault are derived.The algorithm is demonstrated by digital computer simulations. 展开更多
关键词 fault location two parallel line line line fault
下载PDF
Fault location of two-parallel transmission line for double phase-to-earth fault using one-terminal data
2
作者 张庆超 段晖 +1 位作者 耿超 宋文南 《Journal of Zhejiang University Science》 CSCD 2003年第5期520-525,共6页
An accurate algorithm for fault location of double phase-to-earth fault on transmission line of direct ground neutral system is presented. The algorithm, which employs the faulted phase network and zero-sequence netwo... An accurate algorithm for fault location of double phase-to-earth fault on transmission line of direct ground neutral system is presented. The algorithm, which employs the faulted phase network and zero-sequence network as fault-location model in which the source impedance at the remote end is not involved, ef-fectively eliminates the effect of load flow and fault resistance on the accuracy of fault location. The algorithm achieves accurate location by measuring only one local end data and is used in a procedure that provides automatic determination of faulted types and phases, and does not require the engineer to specify them. Simulation results showed the effectiveness of the algorithm under the condition of double phase-to-earth fault. 展开更多
关键词 Fault location Transmission line Double phas e-to-earth fault
下载PDF
上一页 1 下一页 到第
使用帮助 返回顶部