Single-phase low current grounding faults areoften seen in power distribution system of coal mines.These faults are difficult to reliably identify.We propose a new method of single-phase ground fault protection based ...Single-phase low current grounding faults areoften seen in power distribution system of coal mines.These faults are difficult to reliably identify.We propose a new method of single-phase ground fault protection based upon a discernible matrix of the fractal dimension associated with line currents.The method builds on existing selective protection methods.Faulted feeders are distinguished using differences in the zero-sequence transient current fractal dimension.The current signals were first processed through a fast Fourier transform and then the characteristics of a faulted line were identified using a discernible matrix.The method of calculation is illustrated.The results show that the method involves simple calculations, is easy to do and is highly accurate.It is, therefore, suitable for distribution networks having different neutral grounding modes.展开更多
The energy spectra of the ground state for an exciton (X) trapped by a neutral acceptor (A<SUP>0</SUP>) in a quantum dot with a parabolic confinement have been calculated as a function of the electron-to-h...The energy spectra of the ground state for an exciton (X) trapped by a neutral acceptor (A<SUP>0</SUP>) in a quantum dot with a parabolic confinement have been calculated as a function of the electron-to-hole mass ratio σ by using the hyperspherical coordinates. We find that the (A<SUP>0</SUP>,X) complex confined in a quantum dot has in general a larger binding energy than those in a two-dimensional quantum well and a three-dimensional bulk semiconductor, and the binding energy decreases with the increase of the electron-to-hole mass ratio.展开更多
In neutral point indirectly grounded systems, phase-to-ground fault is putting new demands on fault diagnosis technology. Information fusion is applied to detect the phase-to-ground fault, which integrates several sou...In neutral point indirectly grounded systems, phase-to-ground fault is putting new demands on fault diagnosis technology. Information fusion is applied to detect the phase-to-ground fault, which integrates several sources of information, including line current, line voltage, zero sequence current and voltage, and quintic harmonic wave component. This method is testified through the simulation of Matlab. Simulation results show that the precision and reliability of the detection has been greatly increased.展开更多
This paper mainly is study on power system working state with neutral point different grounded methods, when the power system is normal working and the single-phase grounding. And further analysis of the different ope...This paper mainly is study on power system working state with neutral point different grounded methods, when the power system is normal working and the single-phase grounding. And further analysis of the different operating modes of voltage and current relationships, expounds the different operation occasions and characteristics.展开更多
In order to limit short-circuit current and satisfy the need of relay setting, only part of the 220 kV power transformer is grounded, so on the neutrals of ungrounded transformers will appear the over-voltage. Current...In order to limit short-circuit current and satisfy the need of relay setting, only part of the 220 kV power transformer is grounded, so on the neutrals of ungrounded transformers will appear the over-voltage. Currently the value of over-voltage on transformer neutral point and the corresponding protection strategy is based on theoretical formula. This article uses the PSCAD/EMTDC software to calculate the over-voltage on the neutral point of 4 ungrounded power transformers in Chongqing 220 kV power grid. The result shows that the power frequency transient over-voltage on the neutrals may reach 178 kV. If the single-phase grounding fault occurs in ungrounded power system, the power frequency over-voltage on the neutrals will be more serious and rise to 138.6 kV. Non-full phase operation may cause serious ferro-resonance over-voltage on the neutrals of no-load transformer, which may last for seconds and may rise to 723.7 kV, causing serious threat to the transformer neutrals and line-side equipment. The article also studies the gap parameter which should be taken on the neutrals of 220 kV transformers at the end.展开更多
This paper presents a mathematical model of three-level voltage PWM rectifier,and derives a power control model from the theory of instantaneous power.In the vector-space,the influences on instantaneous power exercise...This paper presents a mathematical model of three-level voltage PWM rectifier,and derives a power control model from the theory of instantaneous power.In the vector-space,the influences on instantaneous power exercised by all the switching vectors are studied and illustrated separately,then a direct power control(DPC) scheme for three-level PWM rectifier which uses multistage band hysteresis comparator is proposed,and a novel switching table is designed.Meanwhile,the neutralpoint voltage unbalance is inhibited by selecting the redundancy switching states of small voltage vectors.Simulation and experimental results show that the proposed strategy can not only stabilize the DC bus voltage but also realize the unity power factor operation and the balance of neutral-point voltage.Moreover,the proposed method can improve the performance of the three-level rectifier.展开更多
基金Project 50504015 supported by the National Natural Science Foundation of Chinathe Youth Science and Technology Research Program of China University of Mining and Technology (0C060996)
文摘Single-phase low current grounding faults areoften seen in power distribution system of coal mines.These faults are difficult to reliably identify.We propose a new method of single-phase ground fault protection based upon a discernible matrix of the fractal dimension associated with line currents.The method builds on existing selective protection methods.Faulted feeders are distinguished using differences in the zero-sequence transient current fractal dimension.The current signals were first processed through a fast Fourier transform and then the characteristics of a faulted line were identified using a discernible matrix.The method of calculation is illustrated.The results show that the method involves simple calculations, is easy to do and is highly accurate.It is, therefore, suitable for distribution networks having different neutral grounding modes.
基金The project supported by National Natural Science Foundation of China under Grant No.10275014
文摘The energy spectra of the ground state for an exciton (X) trapped by a neutral acceptor (A<SUP>0</SUP>) in a quantum dot with a parabolic confinement have been calculated as a function of the electron-to-hole mass ratio σ by using the hyperspherical coordinates. We find that the (A<SUP>0</SUP>,X) complex confined in a quantum dot has in general a larger binding energy than those in a two-dimensional quantum well and a three-dimensional bulk semiconductor, and the binding energy decreases with the increase of the electron-to-hole mass ratio.
文摘In neutral point indirectly grounded systems, phase-to-ground fault is putting new demands on fault diagnosis technology. Information fusion is applied to detect the phase-to-ground fault, which integrates several sources of information, including line current, line voltage, zero sequence current and voltage, and quintic harmonic wave component. This method is testified through the simulation of Matlab. Simulation results show that the precision and reliability of the detection has been greatly increased.
文摘This paper mainly is study on power system working state with neutral point different grounded methods, when the power system is normal working and the single-phase grounding. And further analysis of the different operating modes of voltage and current relationships, expounds the different operation occasions and characteristics.
文摘In order to limit short-circuit current and satisfy the need of relay setting, only part of the 220 kV power transformer is grounded, so on the neutrals of ungrounded transformers will appear the over-voltage. Currently the value of over-voltage on transformer neutral point and the corresponding protection strategy is based on theoretical formula. This article uses the PSCAD/EMTDC software to calculate the over-voltage on the neutral point of 4 ungrounded power transformers in Chongqing 220 kV power grid. The result shows that the power frequency transient over-voltage on the neutrals may reach 178 kV. If the single-phase grounding fault occurs in ungrounded power system, the power frequency over-voltage on the neutrals will be more serious and rise to 138.6 kV. Non-full phase operation may cause serious ferro-resonance over-voltage on the neutrals of no-load transformer, which may last for seconds and may rise to 723.7 kV, causing serious threat to the transformer neutrals and line-side equipment. The article also studies the gap parameter which should be taken on the neutrals of 220 kV transformers at the end.
基金supported by the Key Program of National Natural Science Foundation of China (Grant No. 51037004)the National Natural Science Foundation of China (Grant No. 51077097)the Key Technologies Research and Development Program of Tianjin (Grant No.11ZCKFGX03300)
文摘This paper presents a mathematical model of three-level voltage PWM rectifier,and derives a power control model from the theory of instantaneous power.In the vector-space,the influences on instantaneous power exercised by all the switching vectors are studied and illustrated separately,then a direct power control(DPC) scheme for three-level PWM rectifier which uses multistage band hysteresis comparator is proposed,and a novel switching table is designed.Meanwhile,the neutralpoint voltage unbalance is inhibited by selecting the redundancy switching states of small voltage vectors.Simulation and experimental results show that the proposed strategy can not only stabilize the DC bus voltage but also realize the unity power factor operation and the balance of neutral-point voltage.Moreover,the proposed method can improve the performance of the three-level rectifier.