失水事故后燃料厂房空气自然循环及氢气分布实验研究 被引量:1
1
作者 陆雨洲 贠相羽 +1 位作者 张会勇 张诗琪 《原子能科学技术》 EI CAS CSCD 北大核心 2020年第5期916-922,共7页
针对乏燃料水池失水、乏燃料裸露的事故情景,通过实验研究了燃料厂房内空气自然循环及氢气分布的基本规律,得到了空间气体温度场及浓度分布实验数据。结果表明,由于空气自然循环的热量输运作用,各区域升温速率随温度的升高而降低;与外... 针对乏燃料水池失水、乏燃料裸露的事故情景,通过实验研究了燃料厂房内空气自然循环及氢气分布的基本规律,得到了空间气体温度场及浓度分布实验数据。结果表明,由于空气自然循环的热量输运作用,各区域升温速率随温度的升高而降低;与外界自然对流通风的简单方式可显著减缓温度上升,实验24 h后加热元件温度低于490℃;喷淋则可迅速降低所覆盖区域温度,空间气体平均温度在喷淋后5 min内下降了100℃。氢气在空气环境中将形成浓度分层,喷淋搅混可在2 min内破坏该分层;对于氢气/蒸汽混合气体,随着蒸汽凝结及外界空气涌入逐渐具有可燃性,喷淋对此无积极作用。基于上述研究结果,提出了能动和非能动的事故缓解措施建议。 展开更多
关键词 乏燃料裸露 冷却水丧失 自然循环 氢气分布 事故缓解
下载PDF
Reliability Enhancement of the Diverse Protection System Regarding Common Cause Failures
2
作者 Yang Gyun Oh Yong Hun Kim +3 位作者 Hyeong Soon Yim Chul Jin Choi Seung Min Baek Sang Jeong Lee 《Journal of Energy and Power Engineering》 2013年第8期1478-1486,共9页
The issue of CCF (common cause failure) in digital I & C (instrumentation and control) systems is of great interest because an increasing number of such systems are implemented in nuclear power plants. For the mi... The issue of CCF (common cause failure) in digital I & C (instrumentation and control) systems is of great interest because an increasing number of such systems are implemented in nuclear power plants. For the mitigation of ATWS (anticipated transients without scram) as well as CCF within the PPS (plant protection system) and the ESF-CCS (engineered safety feature-component control system), the ADPS (advanced diverse protection system) has been developed by KEPCO E & C (KEPCO Engineering and Construction) Company for new nuclear units in Korea. As compared to the DPS (diverse protection system) design of APR1400, the ADPS has a diverse safety injection function considering a LBLOCA (large break loss of coolant accident) concurrent with the CCF of the PPS and ESF-CCS. Besides the function of SIAS (safety injection actuation signal) initiation, several CCF avoidance features, such as the changes of software design classification, communication methods, equipment platform, and man-machine interfaces, are introduced to enhance the reliability of the ADPS. In addition, the ADPS has recently incorporated four redundant channels with 2-out-of-4 voting logics to enhance its fault tolerant capability. Therefore, it is expected that the ADPS can provide an enhanced reliability regarding possible CCFs in the safety-grade digital I & C systems as well as the ADPS itself. 展开更多
关键词 Diverse protection system CCF fault avoidance fault tolerance.