A novel experimental setup was developed to study the heat extraction of geothermal heat exchanger(GHE)in different operational modes under adiabatic and isothermal boundaries.The experimental setup consists of a sand...A novel experimental setup was developed to study the heat extraction of geothermal heat exchanger(GHE)in different operational modes under adiabatic and isothermal boundaries.The experimental setup consists of a sand trunk,a tailored water chiller,a natural cold source unit,two water boxes containing hot water and cool water,and a data acquisition system.The experimental results indicate that the volume flow rate of the entering water is a main factor affecting the heat extraction;furthermore,the heat extraction value per meter pipe decreases gradually along the heat extraction pipe and increases with the increase of the incoming water volume flow rate.Therefore,this novel experimental setup may be helpful to further study the operation performance of GHE in different types of soil.展开更多
A simplified model for analysis of heat and mass transfer between air stream and flowing down water film in counter-flow plate heat exchanger which serves as an indirect evaporative cooler is theoretically analyzed in...A simplified model for analysis of heat and mass transfer between air stream and flowing down water film in counter-flow plate heat exchanger which serves as an indirect evaporative cooler is theoretically analyzed in this paper. Indirect evaporative cooler is used for sensible cooling of air which then is used for air conditioning purposes. Mathematical model was developed allowing determining heat transfer surface, outlet air temperature and specific humidity of the air being cooled. To make the model simpler some simplifications have been incorporated. The model has high level of correctness and can be used to calculate and design different types of evaporative heat exchangers. Analysis of results of calculations by the help of the developed model prove that the surface of heat exchanger depends on the thickness of water film layer by the regularity of direct proportionality. Moreover, increasing of the water film thickness brings to the decreasing of the efficiency of evaporative type heat exchanger. The model can be used for correct calculation and design of an evaporative cooling air conditioning systems.展开更多
An experiment was carried out to investigate the relation of the maximum velocity of air passing through narrowest passage, mass flux of spray water in one square meter in one hour and the pressure drop of tube bundle...An experiment was carried out to investigate the relation of the maximum velocity of air passing through narrowest passage, mass flux of spray water in one square meter in one hour and the pressure drop of tube bundles. Twelve equations were obtained for the relation. The results show that the pressure drop of the tube bundles increases with increase of the maximum velocity of air and the mass flux of spray water. Comparing the pressure drop of the bare tube bundles with that of the film-enhanced tube bundles, it is found that the pressure drop of the film-enhanced tube bundles is lower about 11% and the surface roughness of the film-enhanced plates is a main factor that influences the pressure drop. The data and method obtained in the paper can be used to compute the pressure drop of the film-enhanced tube bundles and is helpful for selection of fan.展开更多
A grate cooler is key equipment in quenching clinker and recovering heat in cement production. A two-dimensional numerical model based on a 5000 t/d cement plant is proposed to for a study on the gas-solid coupled hea...A grate cooler is key equipment in quenching clinker and recovering heat in cement production. A two-dimensional numerical model based on a 5000 t/d cement plant is proposed to for a study on the gas-solid coupled heat transfer process between the cooling air and clinker in a grate cooler. In this study, we use the Fluent dynamic mesh technique and porous media model through which the transient temperature distribution with the clinker motion process and steady temperature and pressure distribution are obtained. We validate the numerical model with the operating data of the cooling air outlet temperature. Then, we discuss the amount of mid-temperature air outlet and average diameter of clinker particles, which affect the heat effective utilization and cooling air pressure drop in clinker layer. We found that after adding one more mid-temperature air outlet, the average temperature of the air flowing into the heat recovery boiler increases by 29.04℃ and the ratio of heat effective utilization increases by 5.3%. This means heat recovery is more effective on adding one more mid-temperature air outlet. Further, the smaller the clinker particles, the more is the pressure drop in clinker layer; thus more power consumption is needed by the cooling fan.展开更多
基金Sponsored by the National Natural Science Foundation of China (Grant No. 50378024)
文摘A novel experimental setup was developed to study the heat extraction of geothermal heat exchanger(GHE)in different operational modes under adiabatic and isothermal boundaries.The experimental setup consists of a sand trunk,a tailored water chiller,a natural cold source unit,two water boxes containing hot water and cool water,and a data acquisition system.The experimental results indicate that the volume flow rate of the entering water is a main factor affecting the heat extraction;furthermore,the heat extraction value per meter pipe decreases gradually along the heat extraction pipe and increases with the increase of the incoming water volume flow rate.Therefore,this novel experimental setup may be helpful to further study the operation performance of GHE in different types of soil.
文摘A simplified model for analysis of heat and mass transfer between air stream and flowing down water film in counter-flow plate heat exchanger which serves as an indirect evaporative cooler is theoretically analyzed in this paper. Indirect evaporative cooler is used for sensible cooling of air which then is used for air conditioning purposes. Mathematical model was developed allowing determining heat transfer surface, outlet air temperature and specific humidity of the air being cooled. To make the model simpler some simplifications have been incorporated. The model has high level of correctness and can be used to calculate and design different types of evaporative heat exchangers. Analysis of results of calculations by the help of the developed model prove that the surface of heat exchanger depends on the thickness of water film layer by the regularity of direct proportionality. Moreover, increasing of the water film thickness brings to the decreasing of the efficiency of evaporative type heat exchanger. The model can be used for correct calculation and design of an evaporative cooling air conditioning systems.
基金Acknowledgement: The study is supported by the National Nature Science Foundation. Patent code is 200620098211.4.
文摘An experiment was carried out to investigate the relation of the maximum velocity of air passing through narrowest passage, mass flux of spray water in one square meter in one hour and the pressure drop of tube bundles. Twelve equations were obtained for the relation. The results show that the pressure drop of the tube bundles increases with increase of the maximum velocity of air and the mass flux of spray water. Comparing the pressure drop of the bare tube bundles with that of the film-enhanced tube bundles, it is found that the pressure drop of the film-enhanced tube bundles is lower about 11% and the surface roughness of the film-enhanced plates is a main factor that influences the pressure drop. The data and method obtained in the paper can be used to compute the pressure drop of the film-enhanced tube bundles and is helpful for selection of fan.
基金supported by the Horizontal Subject(Grant No.11471501)the National Basic Research Program of China("973"Project)(Grant No.2013CB228305)
文摘A grate cooler is key equipment in quenching clinker and recovering heat in cement production. A two-dimensional numerical model based on a 5000 t/d cement plant is proposed to for a study on the gas-solid coupled heat transfer process between the cooling air and clinker in a grate cooler. In this study, we use the Fluent dynamic mesh technique and porous media model through which the transient temperature distribution with the clinker motion process and steady temperature and pressure distribution are obtained. We validate the numerical model with the operating data of the cooling air outlet temperature. Then, we discuss the amount of mid-temperature air outlet and average diameter of clinker particles, which affect the heat effective utilization and cooling air pressure drop in clinker layer. We found that after adding one more mid-temperature air outlet, the average temperature of the air flowing into the heat recovery boiler increases by 29.04℃ and the ratio of heat effective utilization increases by 5.3%. This means heat recovery is more effective on adding one more mid-temperature air outlet. Further, the smaller the clinker particles, the more is the pressure drop in clinker layer; thus more power consumption is needed by the cooling fan.