An adaptive state feedback predictive control (SFPC) scheme and an expert control scheme are presented and applied to the temperature control of a 1200 kt·a^-1 delayed coking furnace, which is the key equipment...An adaptive state feedback predictive control (SFPC) scheme and an expert control scheme are presented and applied to the temperature control of a 1200 kt·a^-1 delayed coking furnace, which is the key equipment for the delayed coking process. Adaptive SFPC is used to improve the performance of temperature control in normal operation. A simplified nonlinear model on the basis of first principles of the furnace is developed to obtain a state space model by linearization. Taking advantage of the nonlinear model, an online model adapting method is presented to accommodate the dynamic change of process characteristics because of tube coking and load changes. To compensate the large inverse response of outlet temperature resulting from the sudden increase of injected steam of a particular velocity to tubes, a monitoring method and an expert control scheme based on heat balance calculation are proposed. Industrial implementation shows the effectiveness and feasibility of the proposed control strategy.展开更多
基金the State Key Development Program for Basic Research of China(2002CB312200)the National High Technology Research and Development Program of China(2007AA04Z193)
文摘An adaptive state feedback predictive control (SFPC) scheme and an expert control scheme are presented and applied to the temperature control of a 1200 kt·a^-1 delayed coking furnace, which is the key equipment for the delayed coking process. Adaptive SFPC is used to improve the performance of temperature control in normal operation. A simplified nonlinear model on the basis of first principles of the furnace is developed to obtain a state space model by linearization. Taking advantage of the nonlinear model, an online model adapting method is presented to accommodate the dynamic change of process characteristics because of tube coking and load changes. To compensate the large inverse response of outlet temperature resulting from the sudden increase of injected steam of a particular velocity to tubes, a monitoring method and an expert control scheme based on heat balance calculation are proposed. Industrial implementation shows the effectiveness and feasibility of the proposed control strategy.