Total harmonic distortion (THD) is one of the key technical indexes of inverter output voltage. Optimization o f switching points and filter parameters could ensure the switching-point-preset sinusoidal pulse width mo...Total harmonic distortion (THD) is one of the key technical indexes of inverter output voltage. Optimization o f switching points and filter parameters could ensure the switching-point-preset sinusoidal pulse width modulation (SPWM) inverters with low harmonyic content in theory.The THD value would be increased by switching time delay of power devices and control circuit. A new control coecuit with delay time compensation is presented in this paper. With this control scheme, the output of the inverter could be basically identified with the theory given.Test results of experimental circuit verify that the control circuit presented in this paper is feasible. The THD of the inverter output voltage could be reduced to a certain extent by this method.展开更多
文摘Total harmonic distortion (THD) is one of the key technical indexes of inverter output voltage. Optimization o f switching points and filter parameters could ensure the switching-point-preset sinusoidal pulse width modulation (SPWM) inverters with low harmonyic content in theory.The THD value would be increased by switching time delay of power devices and control circuit. A new control coecuit with delay time compensation is presented in this paper. With this control scheme, the output of the inverter could be basically identified with the theory given.Test results of experimental circuit verify that the control circuit presented in this paper is feasible. The THD of the inverter output voltage could be reduced to a certain extent by this method.