Modeling method for the current control loop of a grid-connected PWM inverter with the LCL output filter was discussed.Firstly,the current control loop with the LCL inverter-side current as feedback was established.Th...Modeling method for the current control loop of a grid-connected PWM inverter with the LCL output filter was discussed.Firstly,the current control loop with the LCL inverter-side current as feedback was established.Then,parameters of PI controller were calculated on the basis of an equivalent controlled object.Finally,Norton equivalent circuit for the current control loop of grid-connected system was derived by integrating one control equation,which connected the PWM inverter output voltage and the LCL inverter-side current,with two circuit equations,separately using the LCL inverter-side current and the injected current as loop currents.With the induced Norton equivalent circuit,system-level resonant and unstable issues on real grid-connected system applied in weak distributed power systems can be easily analyzed.The validity of substituting Norton equivalent circuit for grid-connected system is verified by simulation and experiment.展开更多
基金Project(51307009)supported by the National Natural Science Foundation of ChinaProject(12JJ4045)supported by Hunan Provincial Natural Science Foundation,China+2 种基金Project(2011KFJJ003)supported by the Key Laboratory for Power Technology of Renewable Energy Sources of Hunan Province,ChinaProject(2011kfj14)supported by the Fund of Key Laboratory of Hunan Province about Power System Operation and Control,ChinaProject(454.13S-20)supported by the Enterprises’Postdoctoral Funds of Pudong Area of Shanghai,China
文摘Modeling method for the current control loop of a grid-connected PWM inverter with the LCL output filter was discussed.Firstly,the current control loop with the LCL inverter-side current as feedback was established.Then,parameters of PI controller were calculated on the basis of an equivalent controlled object.Finally,Norton equivalent circuit for the current control loop of grid-connected system was derived by integrating one control equation,which connected the PWM inverter output voltage and the LCL inverter-side current,with two circuit equations,separately using the LCL inverter-side current and the injected current as loop currents.With the induced Norton equivalent circuit,system-level resonant and unstable issues on real grid-connected system applied in weak distributed power systems can be easily analyzed.The validity of substituting Norton equivalent circuit for grid-connected system is verified by simulation and experiment.