A method is proposed to monitor and control Hopf bifurcations in multi-machine power systems using the information from wide area measurement systems (WAMSs). The power method (PM) is adopted to compute the pair of co...A method is proposed to monitor and control Hopf bifurcations in multi-machine power systems using the information from wide area measurement systems (WAMSs). The power method (PM) is adopted to compute the pair of conjugate eigenvalues with the algebraically largest real part and the corresponding eigenvectors of the Jacobian matrix of a power system. The distance between the current equilibrium point and the Hopf bifurcation set can be monitored dynamically by computing the pair of con- jugate eigenvalues. When the current equilibrium point is close to the Hopf bifurcation set, the approximate normal vector to the Hopf bifurcation set is computed and used as a direction to regulate control parameters to avoid a Hopf bifurcation in the power system described by differential algebraic equations (DAEs). The validity of the proposed method is demonstrated by regulating the reactive power loads in a 14-bus power system.展开更多
By considering the static voltage characteristic of the load, we propose a WAMS/SCADA mixed nonlinear method to estimate the voltage of unobservable buses caused by topology change or phasor measurement unit (PMU) mal...By considering the static voltage characteristic of the load, we propose a WAMS/SCADA mixed nonlinear method to estimate the voltage of unobservable buses caused by topology change or phasor measurement unit (PMU) malfunction in a power system. By modeling the load characteristic with data from SCADA, we employed the Gauss-Seidel method to solve the nonlinear equations and estimate the voltage of unobservable buses with the high precision voltages of neighboring buses measured by a PMU. Simulations were carried out on the IEEE 39-bus system, and the results show that this novel method can dynamically and accurately trace the variation of the voltage phasor of the unobservable buses.展开更多
基金the National Natural Science Foundation of China (Nos. 50595414 and 50507018)the National Key Technolo-gies Supporting Program of China during the 11th Five-Year Plan Period (No. 2006BAA02A01)the Key Grant Project of MOE, China (No. 305008)
文摘A method is proposed to monitor and control Hopf bifurcations in multi-machine power systems using the information from wide area measurement systems (WAMSs). The power method (PM) is adopted to compute the pair of conjugate eigenvalues with the algebraically largest real part and the corresponding eigenvectors of the Jacobian matrix of a power system. The distance between the current equilibrium point and the Hopf bifurcation set can be monitored dynamically by computing the pair of con- jugate eigenvalues. When the current equilibrium point is close to the Hopf bifurcation set, the approximate normal vector to the Hopf bifurcation set is computed and used as a direction to regulate control parameters to avoid a Hopf bifurcation in the power system described by differential algebraic equations (DAEs). The validity of the proposed method is demonstrated by regulating the reactive power loads in a 14-bus power system.
基金Project supported by the National Natural Science Foundation of China (Nos. 50507018, 50595414, 50677062, and 60421002)the National Basic Research Program (973) of China (No. 2004CB217902)+1 种基金the National Key Technologies Supporting Program of Chinaduring the 11th Five-Year Plan Period (No. 2006BAA02A01)theKey Grant Project of MOE of China (No. 305008)
文摘By considering the static voltage characteristic of the load, we propose a WAMS/SCADA mixed nonlinear method to estimate the voltage of unobservable buses caused by topology change or phasor measurement unit (PMU) malfunction in a power system. By modeling the load characteristic with data from SCADA, we employed the Gauss-Seidel method to solve the nonlinear equations and estimate the voltage of unobservable buses with the high precision voltages of neighboring buses measured by a PMU. Simulations were carried out on the IEEE 39-bus system, and the results show that this novel method can dynamically and accurately trace the variation of the voltage phasor of the unobservable buses.