When interrupting short circuit fault by 40.5-kV vacuum circuit breakers, it is significant to eliminate multiple restrike phenomena, which occur frequently and result in high overvoltage and even interruption failure...When interrupting short circuit fault by 40.5-kV vacuum circuit breakers, it is significant to eliminate multiple restrike phenomena, which occur frequently and result in high overvoltage and even interruption failure. A synthetic circuit that can supply a DC recovery voltage after current zero was used to study multiple restrike phenomena in switching. Some key factors including breaking current, clearance between open contacts, electrode structure and contact material, which may affect restrike characteristics, were studied. Under various clearances, the statistical probability of restrike was obtained. As a result, the best scope of clearance between open contacts was found. The performance of CuCr50/50 and CuCr75/25 material were compared. Two kinds of electrode structures, namely 1/2 coil structure and cup-shaped axial magnetic structure, were tested. After a high-current interruption, conditioning effoct was realized and the probability of restrike decreased.展开更多
文摘When interrupting short circuit fault by 40.5-kV vacuum circuit breakers, it is significant to eliminate multiple restrike phenomena, which occur frequently and result in high overvoltage and even interruption failure. A synthetic circuit that can supply a DC recovery voltage after current zero was used to study multiple restrike phenomena in switching. Some key factors including breaking current, clearance between open contacts, electrode structure and contact material, which may affect restrike characteristics, were studied. Under various clearances, the statistical probability of restrike was obtained. As a result, the best scope of clearance between open contacts was found. The performance of CuCr50/50 and CuCr75/25 material were compared. Two kinds of electrode structures, namely 1/2 coil structure and cup-shaped axial magnetic structure, were tested. After a high-current interruption, conditioning effoct was realized and the probability of restrike decreased.