Primary and secondary networks are treated as a whole in indirect heating systems, and an advanced new temperature-flow regulation method is presented whose flow ratio is greater than 60% in a secondary network and 30...Primary and secondary networks are treated as a whole in indirect heating systems, and an advanced new temperature-flow regulation method is presented whose flow ratio is greater than 60% in a secondary network and 30% in a primary network when under a partial load. Through deducing and optimizing an exponential function flow regulation rule, the formulae of flow regulation and the supply and return water temperatures are obtained, and their relevant curves are plotted. After comparison, it is found that this control method has a huge energy conservation space, and it should therefore be generalized soon.展开更多
文摘Primary and secondary networks are treated as a whole in indirect heating systems, and an advanced new temperature-flow regulation method is presented whose flow ratio is greater than 60% in a secondary network and 30% in a primary network when under a partial load. Through deducing and optimizing an exponential function flow regulation rule, the formulae of flow regulation and the supply and return water temperatures are obtained, and their relevant curves are plotted. After comparison, it is found that this control method has a huge energy conservation space, and it should therefore be generalized soon.