A water loop variable refrigerant flow(WLVRF)air-conditioning system is designed to be applied in large-scale buildings in northern China.The system is energy saving and it is an integrated system consisting of a va...A water loop variable refrigerant flow(WLVRF)air-conditioning system is designed to be applied in large-scale buildings in northern China.The system is energy saving and it is an integrated system consisting of a variable refrigerant flow(VRF)air-conditioning unit,a water loop and an air source heat pump.The water loop transports energy among different regions in the buildings instead of refrigerant pipes,decreasing the scale of the VRF air-conditioning unit and improving the performance.Previous models for refrigerants and building loads are cited in this investigation.Mathematical models of major equipment and other elements of the system are established using the lumped parameter method based on the DATAFIT software and the MATLAB software.The performance of the WLVRF system is simulated.The initial investments and the running costs are calculated based on the results of market research.Finally,a contrast is carried out between the WLVRF system and the traditional VRF system.The results show that the WLVRF system has a better working condition and lower running costs than the traditional VRF system.展开更多
The optimum control strategy and the saving potential of all variable chiller plant under the conditions of changing building cooling load and cooling water supply temperature were investigated. Based on a simulation ...The optimum control strategy and the saving potential of all variable chiller plant under the conditions of changing building cooling load and cooling water supply temperature were investigated. Based on a simulation model of water source chiller plant established in dynamic transient simulation program (TRNSYS),the four-variable quadratic orthogonal regression experiments were carried out by taking cooling load,cooling water supply temperature,cooling water flow rate and chilled water flow rate as variables,and the fitting formulas expressing the relationships between the total energy consumption of chiller plant with the four selected parameters was obtained. With the SAS statistical software and MATHEMATICA mathematical software,the optimal chilled water flow rate and cooling water flow rate which result in the minimum total energy consumption were determined under continuously varying cooling load and cooling water supply temperature. With regard to a chiller plant serving an office building in Shanghai,the total energy consumptions under different control strategies were computed in terms of the forecasting function of cooling load and water source temperature. The results show that applying the optimal control strategy to the chiller plant can bring a saving of 23.27% in power compared with the corresponding conventional variable speed plant,indicating that the optimal control strategy can improve the energy efficiency of chiller plant.展开更多
Thickness of falling water film out of tubes is one of critical factors of heat transfer of evaporative air cooler. A new method of resistance measurement was developed to measure thickness of the film. When the resis...Thickness of falling water film out of tubes is one of critical factors of heat transfer of evaporative air cooler. A new method of resistance measurement was developed to measure thickness of the film. When the resistance probe on the tip of micrometer touches the surface and bottom of the film, two corresponding sudden reductions of resistance occurs, and the difference of two graduations on the micrometer displays the thickness of the film. The film thickness of eleven angles was measured in five kinds of water flows and results varies from 0.8933mm to 1.7233 mm. Mean thickness and mean heat transfer coefficient of the film out of the tube was calculated.展开更多
This paper introduces a novel fiat plate solar collector (FPC) using micro heat pipe array (MHPA) as a key element. To analyze the thermal transfer behavior of flat plate solar collector with micro heat pipe array...This paper introduces a novel fiat plate solar collector (FPC) using micro heat pipe array (MHPA) as a key element. To analyze the thermal transfer behavior of flat plate solar collector with micro heat pipe array (MHPA-FPC), an indoor experiment for thermal transfer characteristic of MHPA applied to FPC was conducted by using an electrical heating film to simulate the solar radiation. Different cooling water flow rates, cooling water temperatures, slopes, and contact thermal resistances be- tween the condenser of MHPA and the heat exchanger were tested at different heating powers. The experimental results in- dicate that MHPA-FPC exhibits the enhanced heat transfer capability with increased cooling water flow rate and temperature. Total thermal resistance has a maximum decline of approximately 10% when the flow rate increases from 180 to 360 L h-1 and 38% when the cooling water temperature increases from 20~C to 40~C. When the inclination angle of MHPA-FPC ex- ceeds 30~, the slope change has a negligible effect on the heat transfer performance of MHPA-FPC. In addition, contact thermal resistance significantly affects the heat transfer capability of MHPA-FPC. The total thermal resistances lowers to nearly half of the original level when contact material between the condenser of MHPA and the heat exchanger changes from conductive silicone to conductive grease. These results could provide useful information for the optimal design and operation of MHPA-FPC.展开更多
The film cooling performance of a trunk-branch hole is investigated by numerical simulation in this paper. The geometry of the hole is a novel cooling concept, which controls the vortices-pair existing at the mink hol...The film cooling performance of a trunk-branch hole is investigated by numerical simulation in this paper. The geometry of the hole is a novel cooling concept, which controls the vortices-pair existing at the mink hole outlet using the injection of the branch hole. The trunk-branch holes require easily machinable round hole as compared to the shaped holes. The flow cases were considered at the blowing ratios of 0.5, 0.75, 1.0, 1.5 and 2.0. At the low blowing ratio of 0.5, the vortices-pair at the outlet of the trunk hole is reduced and the laterally coverage of the film is improved. At the high blowing ratio of 2.0, the vortices-pair is killed by the vortex which is produced by the injection of the branch hole. The flow rate of the two outlets becomes more significantly different when the blowing ratio increases from 0.75 to 2.0. The discharge coefficients increase 0.15 and the laterally averaged film effectiveness improve 0.2 as compared to the cylindrical holes. The optimal blowing ratios occur at M=1.0 or M= 1.5 according to the various locations downstream of the holes.展开更多
文摘A water loop variable refrigerant flow(WLVRF)air-conditioning system is designed to be applied in large-scale buildings in northern China.The system is energy saving and it is an integrated system consisting of a variable refrigerant flow(VRF)air-conditioning unit,a water loop and an air source heat pump.The water loop transports energy among different regions in the buildings instead of refrigerant pipes,decreasing the scale of the VRF air-conditioning unit and improving the performance.Previous models for refrigerants and building loads are cited in this investigation.Mathematical models of major equipment and other elements of the system are established using the lumped parameter method based on the DATAFIT software and the MATLAB software.The performance of the WLVRF system is simulated.The initial investments and the running costs are calculated based on the results of market research.Finally,a contrast is carried out between the WLVRF system and the traditional VRF system.The results show that the WLVRF system has a better working condition and lower running costs than the traditional VRF system.
基金Project(G-0805-10156) supported by US Energy Foundation
文摘The optimum control strategy and the saving potential of all variable chiller plant under the conditions of changing building cooling load and cooling water supply temperature were investigated. Based on a simulation model of water source chiller plant established in dynamic transient simulation program (TRNSYS),the four-variable quadratic orthogonal regression experiments were carried out by taking cooling load,cooling water supply temperature,cooling water flow rate and chilled water flow rate as variables,and the fitting formulas expressing the relationships between the total energy consumption of chiller plant with the four selected parameters was obtained. With the SAS statistical software and MATHEMATICA mathematical software,the optimal chilled water flow rate and cooling water flow rate which result in the minimum total energy consumption were determined under continuously varying cooling load and cooling water supply temperature. With regard to a chiller plant serving an office building in Shanghai,the total energy consumptions under different control strategies were computed in terms of the forecasting function of cooling load and water source temperature. The results show that applying the optimal control strategy to the chiller plant can bring a saving of 23.27% in power compared with the corresponding conventional variable speed plant,indicating that the optimal control strategy can improve the energy efficiency of chiller plant.
基金Acknowledgments: The study is one of branches of a key project of Chinese National Programs for Foundation Research and Development, thanks for the supporting from the National Nature Science Foundation. The new method to measure thickness of wager film has applied an utility model patent in China (No. 200620098211.4).
文摘Thickness of falling water film out of tubes is one of critical factors of heat transfer of evaporative air cooler. A new method of resistance measurement was developed to measure thickness of the film. When the resistance probe on the tip of micrometer touches the surface and bottom of the film, two corresponding sudden reductions of resistance occurs, and the difference of two graduations on the micrometer displays the thickness of the film. The film thickness of eleven angles was measured in five kinds of water flows and results varies from 0.8933mm to 1.7233 mm. Mean thickness and mean heat transfer coefficient of the film out of the tube was calculated.
基金financially supported by the Natural Science Foundation of Beijing(Grant No.Z1004020201201)the Opening Funds of State Key Laboratory of Building Safety and Build Environment of China(Grant No.BSBE 2011-07)
文摘This paper introduces a novel fiat plate solar collector (FPC) using micro heat pipe array (MHPA) as a key element. To analyze the thermal transfer behavior of flat plate solar collector with micro heat pipe array (MHPA-FPC), an indoor experiment for thermal transfer characteristic of MHPA applied to FPC was conducted by using an electrical heating film to simulate the solar radiation. Different cooling water flow rates, cooling water temperatures, slopes, and contact thermal resistances be- tween the condenser of MHPA and the heat exchanger were tested at different heating powers. The experimental results in- dicate that MHPA-FPC exhibits the enhanced heat transfer capability with increased cooling water flow rate and temperature. Total thermal resistance has a maximum decline of approximately 10% when the flow rate increases from 180 to 360 L h-1 and 38% when the cooling water temperature increases from 20~C to 40~C. When the inclination angle of MHPA-FPC ex- ceeds 30~, the slope change has a negligible effect on the heat transfer performance of MHPA-FPC. In addition, contact thermal resistance significantly affects the heat transfer capability of MHPA-FPC. The total thermal resistances lowers to nearly half of the original level when contact material between the condenser of MHPA and the heat exchanger changes from conductive silicone to conductive grease. These results could provide useful information for the optimal design and operation of MHPA-FPC.
文摘The film cooling performance of a trunk-branch hole is investigated by numerical simulation in this paper. The geometry of the hole is a novel cooling concept, which controls the vortices-pair existing at the mink hole outlet using the injection of the branch hole. The trunk-branch holes require easily machinable round hole as compared to the shaped holes. The flow cases were considered at the blowing ratios of 0.5, 0.75, 1.0, 1.5 and 2.0. At the low blowing ratio of 0.5, the vortices-pair at the outlet of the trunk hole is reduced and the laterally coverage of the film is improved. At the high blowing ratio of 2.0, the vortices-pair is killed by the vortex which is produced by the injection of the branch hole. The flow rate of the two outlets becomes more significantly different when the blowing ratio increases from 0.75 to 2.0. The discharge coefficients increase 0.15 and the laterally averaged film effectiveness improve 0.2 as compared to the cylindrical holes. The optimal blowing ratios occur at M=1.0 or M= 1.5 according to the various locations downstream of the holes.