Considering the additional electric energy generated after the full operation of the underground hydropower station, the electric energy accommodation of the Three Gorges Project (TGP) is reviewed. It is .focused on...Considering the additional electric energy generated after the full operation of the underground hydropower station, the electric energy accommodation of the Three Gorges Project (TGP) is reviewed. It is .focused on the additional electricity accommodation, based on the research at the earl), stage. The electric energ), accommodation solutions ate recommended as that. based on the cost-benefit analysis of the power distribution area, the additional electric energy of the Three Gorges should be given ptqority to meet the needs at the supply end of Hubei and Chongqing. The results of this research has a reference value on the implementation of the Three Gorges electric power accommodation, after the further optimization of the transmission curves in both wet and dry seasons.展开更多
This study constructed a mathematic model of a variable frequency centrifugal chiller using Simulink software. By running the simulation, it was discovered that when the other factors are constant, the EER(Energy Effi...This study constructed a mathematic model of a variable frequency centrifugal chiller using Simulink software. By running the simulation, it was discovered that when the other factors are constant, the EER(Energy Efficiency Ratio) of the chiller increases with decreases in the temperature of the cooling water and increases in the temperature of the chilled water. The effect of changes in the cooling water temperature on the EER of the chiller is stronger than that of changes in the chilled water temperature. In addition, as the chiller load decreases, the EER increases until reaching a maximum, after which it decreases. Furthermore, the EER of chillers working under a constant flow rate is slightly higher than that of those working under varying flow rates.展开更多
文摘Considering the additional electric energy generated after the full operation of the underground hydropower station, the electric energy accommodation of the Three Gorges Project (TGP) is reviewed. It is .focused on the additional electricity accommodation, based on the research at the earl), stage. The electric energ), accommodation solutions ate recommended as that. based on the cost-benefit analysis of the power distribution area, the additional electric energy of the Three Gorges should be given ptqority to meet the needs at the supply end of Hubei and Chongqing. The results of this research has a reference value on the implementation of the Three Gorges electric power accommodation, after the further optimization of the transmission curves in both wet and dry seasons.
基金supported by a Grant-in-Aid for Scientific Research through grant number KM200610016003 from the Beijing Municipal Commission of Education
文摘This study constructed a mathematic model of a variable frequency centrifugal chiller using Simulink software. By running the simulation, it was discovered that when the other factors are constant, the EER(Energy Efficiency Ratio) of the chiller increases with decreases in the temperature of the cooling water and increases in the temperature of the chilled water. The effect of changes in the cooling water temperature on the EER of the chiller is stronger than that of changes in the chilled water temperature. In addition, as the chiller load decreases, the EER increases until reaching a maximum, after which it decreases. Furthermore, the EER of chillers working under a constant flow rate is slightly higher than that of those working under varying flow rates.