变电站站用变压器高压侧电压缺相故障分析 被引量:2
1
作者 何昌高 宋浩杰 张杰 《安徽电力》 2012年第2期52-53,共2页
在对站用变压器高压侧缺相故障进行分析时,参考了由站变接线及理论公式推导的数据,并以黄山供电公司芳村变电站站用变压器故障为例子以说明,这种方法对现场抢修工作有较大的指导作用。在此类故障的消缺中可以推广。
关键词 变电站 站用变压器 高压侧 电压缺相 故障 电压 分析
下载PDF
高压磁控型电抗器中性点小电抗取值方法 被引量:5
2
作者 李祖明 钟高跃 +1 位作者 石祥建 陈松林 《变压器》 北大核心 2020年第9期18-22,71,共6页
结合输电线路及磁控电抗器电路拓扑结构,推导缺相处的电压表达式,基于此提出针对磁控型电抗器的中性点小电抗取值方法。
关键词 磁控型电抗器 电压 中性点小电抗
下载PDF
A new measuring technique in detecting of high voltage three phase induction motor for single phasing
3
作者 Ali M El-Rifaie Hala M Abdel Mageed 《Journal of Measurement Science and Instrumentation》 CAS 2014年第3期6-11,共6页
Open phase in three phase induction motors is a common fault that can occur as a result of a fuse blowing or a pro- tective device failing on one phase of the motor. This paper introduces a new method,which is based o... Open phase in three phase induction motors is a common fault that can occur as a result of a fuse blowing or a pro- tective device failing on one phase of the motor. This paper introduces a new method,which is based on the transient mea- surement and can distinguish the fault of one phase connecting ground. The method has been proved to be in correspondence with the simulation results by Matlab and LabVIEW in practice, The method has merits of simplicity, accuracy and ease of USe. 展开更多
关键词 high voltage induction motor transient protection single phasing detection
下载PDF
Ferroresonance at Open Phase Operating Conditions of Power Transformers
4
作者 Hani Obeid 《Journal of Energy and Power Engineering》 2012年第10期1714-1717,共4页
The reliability of electric supply to consumers is one of the most important factors that determine the requirements imposed on modem utility companies. This paper presents the results of investigation by computer sof... The reliability of electric supply to consumers is one of the most important factors that determine the requirements imposed on modem utility companies. This paper presents the results of investigation by computer software of the overvoltages resulting from a ferroresonance conditions in MV networks at open phase operating condition with and without connection to earth on source and load sides of distribution transformer. This overvoltage may reach 4.2 pu on one of the HV side of transformer unswitched phases. The results of the study show that ferroresonance overvoltage may be controlled by replacing fuses with circuit breakers on HV side to ensure switching-off all phases. Insertion of resistor or reactor in the neutral of source and loadsides of the transformer with 5% active load will help in suppressing overvoltages. 展开更多
关键词 FERRORESONANCE OVERVOLTAGE open phase operating condition non-linear inductance.