为提高配网供电可靠性,分析了10 k V出线速断保护增加短时延对变压器的影响。分析结果表明,在变压器允许耐受短路电流的冲击下,短时延的增加对绕组热稳定、动稳定影响不大,但短路冲击累积效应会使变压器铜绕组、垫块等产生微小的残余形...为提高配网供电可靠性,分析了10 k V出线速断保护增加短时延对变压器的影响。分析结果表明,在变压器允许耐受短路电流的冲击下,短时延的增加对绕组热稳定、动稳定影响不大,但短路冲击累积效应会使变压器铜绕组、垫块等产生微小的残余形变,应当引起重视。展开更多
基金Project(2013BAB02B05)supported by the National 12th Five-Year Science and Technology Supporting Plan of ChinaProject(2015CX005)supported by the Innovation Driven Plan of Central South University of ChinaProject(2016zzts094)supported by the Fundamental Research Funds for the Central Universities of Central South University,China