The protection of distribution networks is facing new challenges from an increasing amount of DG (distributed generation). Even though current technology provides satisfactory solutions to manage this new situation,...The protection of distribution networks is facing new challenges from an increasing amount of DG (distributed generation). Even though current technology provides satisfactory solutions to manage this new situation, LOM (loss-of-mains protection) is still considered problematic. The solution proposed in this paper focuses on the use of a line differential protection relay. It inherently contains a suitable communication channel and provides absolutely selective protection for the feeder. Furthermore, it prevents the feeder relays from false tripping for faults on the neighboring feeder. The present trend in protection communication points towards the use of fiber optics. For line differential protection, this means a fast and high-capacity communication link which enables the implementation of many advanced protection functions. In addition, a solid foundation for such a communication link is offered by the new IEC 61850 standard and Ethernet technologies. The basic functionality of the line differential protection enables the operation of both the feeder protection and the DG protection for any fault on the feeder. Furthermore, basic LOM protection methods can be applied as backup protection for failures on the communication link.展开更多
The paper has presented the impact on the line protection performance with the introduction of MUs (merging units) in the process bus level. The paper begins with the introduction on modem digital substation structu...The paper has presented the impact on the line protection performance with the introduction of MUs (merging units) in the process bus level. The paper begins with the introduction on modem digital substation structure and process bus. Then, the paper describes the performances of different sensors such as CTs (current transformers), CVTs (capacitive voltage transformers), FOCS (fiber optical current transducers) and FOVS (fiber optical voltage transducers). With the use of above transducers together with MUs, the performance of distance protection function and line differential protection function have been investigated and presented. Finally, conclusions based on the study are presented in the paper.展开更多
文摘The protection of distribution networks is facing new challenges from an increasing amount of DG (distributed generation). Even though current technology provides satisfactory solutions to manage this new situation, LOM (loss-of-mains protection) is still considered problematic. The solution proposed in this paper focuses on the use of a line differential protection relay. It inherently contains a suitable communication channel and provides absolutely selective protection for the feeder. Furthermore, it prevents the feeder relays from false tripping for faults on the neighboring feeder. The present trend in protection communication points towards the use of fiber optics. For line differential protection, this means a fast and high-capacity communication link which enables the implementation of many advanced protection functions. In addition, a solid foundation for such a communication link is offered by the new IEC 61850 standard and Ethernet technologies. The basic functionality of the line differential protection enables the operation of both the feeder protection and the DG protection for any fault on the feeder. Furthermore, basic LOM protection methods can be applied as backup protection for failures on the communication link.
文摘The paper has presented the impact on the line protection performance with the introduction of MUs (merging units) in the process bus level. The paper begins with the introduction on modem digital substation structure and process bus. Then, the paper describes the performances of different sensors such as CTs (current transformers), CVTs (capacitive voltage transformers), FOCS (fiber optical current transducers) and FOVS (fiber optical voltage transducers). With the use of above transducers together with MUs, the performance of distance protection function and line differential protection function have been investigated and presented. Finally, conclusions based on the study are presented in the paper.