随着550 kN直流悬式绝缘子在±800 kV特高压直流输电线路上的广泛应用,550 k N直流悬式绝缘子的运行性能直接影响特高压直流输电线路的安全稳定运行。根据湖南电网550 kN直流悬式绝缘子运行数据,结合湖南电网运行特点,对在运550 k ...随着550 kN直流悬式绝缘子在±800 kV特高压直流输电线路上的广泛应用,550 k N直流悬式绝缘子的运行性能直接影响特高压直流输电线路的安全稳定运行。根据湖南电网550 kN直流悬式绝缘子运行数据,结合湖南电网运行特点,对在运550 k N直流悬式瓷绝缘子低零值、铁帽锈蚀、玻璃绝缘子零值自爆等缺陷进行了统计分析。同时对一批在运550 k N悬式绝缘子进行冲击击穿试验、机电(机械)破坏负荷试验、温度循环试验和残余机械强度试验,试验结果表明,部分厂家瓷绝缘子机械性能和电气性能有所下降,并对其原因进行了分析。建议加大对550 kN悬式绝缘子抽检试验力度,定期跟踪性能变化情况。展开更多
The shortcomings of oil-immersed transformer solid insulation like low high-temperature resistance of the insulation paper and the uneven distribution of electric field caused by the large difference of dielectric con...The shortcomings of oil-immersed transformer solid insulation like low high-temperature resistance of the insulation paper and the uneven distribution of electric field caused by the large difference of dielectric constants between insulation paper and transformer oil,restricted the development of transformer with smaller size and larger capacity.In view of this situation and the transformer’s demand for the dielectric physicochemical and mechanical property of insulation material,polycarbonate,polyester film and polyphenylene sulfide with high high-temperature resistance were chosen for the comparison analysis in this paper We did the 300-day thermal aging experiment on four samples in transformer oil under different aging temperatures of90°C,110°C and 130°C,then analyzed the changes of their dielectric properties.The experiment results are as follows;the permittivity and dielectric dissipation factor of the three polymer materials are apparently smaller than those of the paper both before and after 300-day aging;the volume resistivity and partial discharge inception voltage of the three materials are higher than those of the paper both before and after aging;and the breakdown field strength of polycarbonate is higher than that of the paper both before and after aging,while that of polyester film and polyphenylene sulfide are slightly lower than that of the paper.展开更多
文摘随着550 kN直流悬式绝缘子在±800 kV特高压直流输电线路上的广泛应用,550 k N直流悬式绝缘子的运行性能直接影响特高压直流输电线路的安全稳定运行。根据湖南电网550 kN直流悬式绝缘子运行数据,结合湖南电网运行特点,对在运550 k N直流悬式瓷绝缘子低零值、铁帽锈蚀、玻璃绝缘子零值自爆等缺陷进行了统计分析。同时对一批在运550 k N悬式绝缘子进行冲击击穿试验、机电(机械)破坏负荷试验、温度循环试验和残余机械强度试验,试验结果表明,部分厂家瓷绝缘子机械性能和电气性能有所下降,并对其原因进行了分析。建议加大对550 kN悬式绝缘子抽检试验力度,定期跟踪性能变化情况。
基金supported by the National Natural Science Foundation of China(Grant No.50977025)
文摘The shortcomings of oil-immersed transformer solid insulation like low high-temperature resistance of the insulation paper and the uneven distribution of electric field caused by the large difference of dielectric constants between insulation paper and transformer oil,restricted the development of transformer with smaller size and larger capacity.In view of this situation and the transformer’s demand for the dielectric physicochemical and mechanical property of insulation material,polycarbonate,polyester film and polyphenylene sulfide with high high-temperature resistance were chosen for the comparison analysis in this paper We did the 300-day thermal aging experiment on four samples in transformer oil under different aging temperatures of90°C,110°C and 130°C,then analyzed the changes of their dielectric properties.The experiment results are as follows;the permittivity and dielectric dissipation factor of the three polymer materials are apparently smaller than those of the paper both before and after 300-day aging;the volume resistivity and partial discharge inception voltage of the three materials are higher than those of the paper both before and after aging;and the breakdown field strength of polycarbonate is higher than that of the paper both before and after aging,while that of polyester film and polyphenylene sulfide are slightly lower than that of the paper.