A cable circuit of a substation in the United Kingdom showed high level of PD activities during a survey using hand hold PD testing equipment. The authors were invited to carry out on-site PD testing experiment to fur...A cable circuit of a substation in the United Kingdom showed high level of PD activities during a survey using hand hold PD testing equipment. The authors were invited to carry out on-site PD testing experiment to further diagnose and locate the potential problem of the cable system. This paper presents the experience of the present authors carrying out the cable test. Following a brief introduction to the experiment equipments and physical connections, the paper analyses the data collected from the testing, including PD pulse shape analysis, frequency spectrum analysis and phase resolved PD pattern analysis. Associated with PD propagation direction identification, PD source diagnosis and localisation was made. Four different types of sensors, which were adapted during the testing, are shown to have different frequency bandwidths and performed differently. Aider comparing the parameters of the sensor and the PD signals detected by individual sensor, optimal PD monitoring bandwidth for cable system is suggested.展开更多
文摘A cable circuit of a substation in the United Kingdom showed high level of PD activities during a survey using hand hold PD testing equipment. The authors were invited to carry out on-site PD testing experiment to further diagnose and locate the potential problem of the cable system. This paper presents the experience of the present authors carrying out the cable test. Following a brief introduction to the experiment equipments and physical connections, the paper analyses the data collected from the testing, including PD pulse shape analysis, frequency spectrum analysis and phase resolved PD pattern analysis. Associated with PD propagation direction identification, PD source diagnosis and localisation was made. Four different types of sensors, which were adapted during the testing, are shown to have different frequency bandwidths and performed differently. Aider comparing the parameters of the sensor and the PD signals detected by individual sensor, optimal PD monitoring bandwidth for cable system is suggested.