Night sky cooling is explored as an alternative to the conventional cooling technologies using fossil fuels. The night sky cooling method is based on the long wave radiation of unglazed collectors to the sky at night....Night sky cooling is explored as an alternative to the conventional cooling technologies using fossil fuels. The night sky cooling method is based on the long wave radiation of unglazed collectors to the sky at night. An evaluation of the night sky cooling system is present for a residential building in three cities of Australia, namely Alice Springs, Darwin and Melbourne. The system comprises an unglazed flat plate solar collector integrated with borehole storage. It uses night sky radiation to reduce the temperature of the ground near to the boreholes. The system was simulated with TRNSYS, a transient simulation program. The simulation results for adequately sized systems show that night sky radiation is able to reduce the coolth storage borehole temperature and the proposed system is able to meet the cooling load of the residential building simulated in three locations. Borchole lengths of 270, 318 and 106 m are required for coolth storage with 90, 260 and 14 m2 collector area for heat rejection in Alice Springs, Darwin and Melbourne, respectively. At the 20th simulation year, the proposed system is able to achieve a system cooling coefficient of performance of 2.2 in Alice Springs, and 2.8 in Darwin and Melbourne.展开更多
The thermal-environment characteristics of the existing forced-convection cooling system were compared with those of the convective cooling system, which combined the radiant-floor cooling system using floor-heating p...The thermal-environment characteristics of the existing forced-convection cooling system were compared with those of the convective cooling system, which combined the radiant-floor cooling system using floor-heating panel typically applied to apartments in South Korea with the forced-convection cooling system using improved fan coil unit. The subjective warm/cool-feeling responses to the combined radiant-floor and convective cooling system in the questionnaire survey conducted among the test subjects were analyzed to establish the basic data for the combined cooling system. The results show that in the thermal-equilibrium condition, the vertical air temperature difference in the model living room is larger in the forced-convection-cooling condition. Most of the subjects feel a proper warm/cool feeling on their entire body, but they feel colder on the foot and lower body in the combined-cooling condition.展开更多
The hybrid system with radiant cooling and dedicated outdoor air not only possesses high energy efficiency, but also creates a healthy and comfortable indoor environment. Indoor air quality will be improved by the ded...The hybrid system with radiant cooling and dedicated outdoor air not only possesses high energy efficiency, but also creates a healthy and comfortable indoor environment. Indoor air quality will be improved by the dedicated outdoor air system(DOAS) and indoor thermal comfort can be enhanced by the radiant cooling system(RCS). The optimal air-supply mode of the hybrid system and the corresponding design approach were investigated. A full-scale experimental chamber with various air outlets and the ceiling radiant cooling panels(CRCP) was designed and established. The performances of different air-supply modes along with CRCPs were analyzed by multi-index evaluations. Preliminary investigations were also conducted on the humidity stratification and the control effect of different airflow modes to prevent condensation on CRCP. The overhead supply air is recommended as the best combination mode for the hybrid system after comprehensive comparison of the experiment results. The optimal proportion of CRCP accounting for the total cooling capacities in accord with specific cooling loads is found, which may provide valuable reference for the design and operation of the hybrid system.展开更多
文摘Night sky cooling is explored as an alternative to the conventional cooling technologies using fossil fuels. The night sky cooling method is based on the long wave radiation of unglazed collectors to the sky at night. An evaluation of the night sky cooling system is present for a residential building in three cities of Australia, namely Alice Springs, Darwin and Melbourne. The system comprises an unglazed flat plate solar collector integrated with borehole storage. It uses night sky radiation to reduce the temperature of the ground near to the boreholes. The system was simulated with TRNSYS, a transient simulation program. The simulation results for adequately sized systems show that night sky radiation is able to reduce the coolth storage borehole temperature and the proposed system is able to meet the cooling load of the residential building simulated in three locations. Borchole lengths of 270, 318 and 106 m are required for coolth storage with 90, 260 and 14 m2 collector area for heat rejection in Alice Springs, Darwin and Melbourne, respectively. At the 20th simulation year, the proposed system is able to achieve a system cooling coefficient of performance of 2.2 in Alice Springs, and 2.8 in Darwin and Melbourne.
基金Project(NRF-2013RIA2A1A01014020)supported by the National Research Foundation of Korea
文摘The thermal-environment characteristics of the existing forced-convection cooling system were compared with those of the convective cooling system, which combined the radiant-floor cooling system using floor-heating panel typically applied to apartments in South Korea with the forced-convection cooling system using improved fan coil unit. The subjective warm/cool-feeling responses to the combined radiant-floor and convective cooling system in the questionnaire survey conducted among the test subjects were analyzed to establish the basic data for the combined cooling system. The results show that in the thermal-equilibrium condition, the vertical air temperature difference in the model living room is larger in the forced-convection-cooling condition. Most of the subjects feel a proper warm/cool feeling on their entire body, but they feel colder on the foot and lower body in the combined-cooling condition.
基金Project(51178298)supported by the National Natural Science Foundation of China
文摘The hybrid system with radiant cooling and dedicated outdoor air not only possesses high energy efficiency, but also creates a healthy and comfortable indoor environment. Indoor air quality will be improved by the dedicated outdoor air system(DOAS) and indoor thermal comfort can be enhanced by the radiant cooling system(RCS). The optimal air-supply mode of the hybrid system and the corresponding design approach were investigated. A full-scale experimental chamber with various air outlets and the ceiling radiant cooling panels(CRCP) was designed and established. The performances of different air-supply modes along with CRCPs were analyzed by multi-index evaluations. Preliminary investigations were also conducted on the humidity stratification and the control effect of different airflow modes to prevent condensation on CRCP. The overhead supply air is recommended as the best combination mode for the hybrid system after comprehensive comparison of the experiment results. The optimal proportion of CRCP accounting for the total cooling capacities in accord with specific cooling loads is found, which may provide valuable reference for the design and operation of the hybrid system.