The new techniques were presented for preventing undesirable distance relay maloperation during voltage collapse and power swings in transmission grids. Initially, the work focused on the development of a fast detecti...The new techniques were presented for preventing undesirable distance relay maloperation during voltage collapse and power swings in transmission grids. Initially, the work focused on the development of a fast detection of voltage collapse and a three-phase fault at transmission lines by using under impedance fault detector (UIFD) and support vector machine (SVM). Likewise, an intelligent approach was developed to discriminate a fault, stable swing and unstable swing, for correct distance relay operation by using the S-transform and the probabilistic neural network (PNN). To illustrate the effectiveness of the proposed techniques, simulations were carried out on the IEEE 39-bus test system using the PSS/E and MATLAB software.展开更多
文摘The new techniques were presented for preventing undesirable distance relay maloperation during voltage collapse and power swings in transmission grids. Initially, the work focused on the development of a fast detection of voltage collapse and a three-phase fault at transmission lines by using under impedance fault detector (UIFD) and support vector machine (SVM). Likewise, an intelligent approach was developed to discriminate a fault, stable swing and unstable swing, for correct distance relay operation by using the S-transform and the probabilistic neural network (PNN). To illustrate the effectiveness of the proposed techniques, simulations were carried out on the IEEE 39-bus test system using the PSS/E and MATLAB software.