Ground-coupled heat pumps(GCHP)are commonly used in residential heating system.To mitigate the boreholes temperature dropping with operating time,a new exhaust-air recharging system is developed.The new recharging sys...Ground-coupled heat pumps(GCHP)are commonly used in residential heating system.To mitigate the boreholes temperature dropping with operating time,a new exhaust-air recharging system is developed.The new recharging system can be used in three operational modes.In this paper,a ground-coupled heat recovery ventilation(HRV)model is discussed.A thermal model is set up to find the optimal brine flow rate and heat transfer allocation ratio between exhaust and supply coils for maximum heat recovery efficiency.Contrary to the conventional liquid-loop HRV systems,the brine temperature entering the exhaust coil never goes blow zero(0℃),and hence defrosting is needless in the ground-coupled HRV system.This can make the ground-coupled HRV system over 20% more efficient than a conventional HRV system at low outdoor temperatures.展开更多
Considering four different climate zones in China, an investigation on the choice of heat recovery ventilator for the buildings with little moisture emissions is carried out. The annual composition of energy consumpti...Considering four different climate zones in China, an investigation on the choice of heat recovery ventilator for the buildings with little moisture emissions is carried out. The annual composition of energy consumption of air intake for per unitary air ventilation flow rate is evaluated by employing the testing data of climatic parameters in eight selected cities. The analysis shows that the total heat recovery is suitable in a controlled ventilation system with air humidity controlled during heating period of all the climates. For the building without air humidity controlled in winter, the sensible heat recovery ventilators can be used in severe cold and cold regions, and total heat recovery systems are more suitable for energy saving in hot summer and cold winter and hot summer and warm winter regions.展开更多
文摘Ground-coupled heat pumps(GCHP)are commonly used in residential heating system.To mitigate the boreholes temperature dropping with operating time,a new exhaust-air recharging system is developed.The new recharging system can be used in three operational modes.In this paper,a ground-coupled heat recovery ventilation(HRV)model is discussed.A thermal model is set up to find the optimal brine flow rate and heat transfer allocation ratio between exhaust and supply coils for maximum heat recovery efficiency.Contrary to the conventional liquid-loop HRV systems,the brine temperature entering the exhaust coil never goes blow zero(0℃),and hence defrosting is needless in the ground-coupled HRV system.This can make the ground-coupled HRV system over 20% more efficient than a conventional HRV system at low outdoor temperatures.
基金National Natural Science Foundation of China(Grant No50578034)Shanghai Educational Development Foundationtitled"Shuguang Project"(Grant NO03SG30)
文摘Considering four different climate zones in China, an investigation on the choice of heat recovery ventilator for the buildings with little moisture emissions is carried out. The annual composition of energy consumption of air intake for per unitary air ventilation flow rate is evaluated by employing the testing data of climatic parameters in eight selected cities. The analysis shows that the total heat recovery is suitable in a controlled ventilation system with air humidity controlled during heating period of all the climates. For the building without air humidity controlled in winter, the sensible heat recovery ventilators can be used in severe cold and cold regions, and total heat recovery systems are more suitable for energy saving in hot summer and cold winter and hot summer and warm winter regions.