The power of the toroidal field (TF) coil in HL-2A is supplied with two 80 MVA motor generators (MGs) together through a diode rectifier. The TF system is designed to obtain the parameters as follows: the highest...The power of the toroidal field (TF) coil in HL-2A is supplied with two 80 MVA motor generators (MGs) together through a diode rectifier. The TF system is designed to obtain the parameters as follows: the highest toroidal filed of 2.8 T, the biggest coil current of 45 kA, the fiat top time of 3-5 s. So the released energy of each MG set for one pulse discharge mast be more than 500 MJ.展开更多
文摘The power of the toroidal field (TF) coil in HL-2A is supplied with two 80 MVA motor generators (MGs) together through a diode rectifier. The TF system is designed to obtain the parameters as follows: the highest toroidal filed of 2.8 T, the biggest coil current of 45 kA, the fiat top time of 3-5 s. So the released energy of each MG set for one pulse discharge mast be more than 500 MJ.