在基于实时数字仿真器(Real-time digital simulator,RTDS)所建立的特高压直流输电系统实时仿真平台中,常规锁相环技术无法实现换流阀触发脉冲的精确控制,不利于实际直流工程的故障重现。基于系统正序分量的瞬时锁相环控制原理,提出了...在基于实时数字仿真器(Real-time digital simulator,RTDS)所建立的特高压直流输电系统实时仿真平台中,常规锁相环技术无法实现换流阀触发脉冲的精确控制,不利于实际直流工程的故障重现。基于系统正序分量的瞬时锁相环控制原理,提出了一种高精度锁相环的建模方法,实现了电网系统频率的高精确跟踪测量。在RTDS仿真平台上搭建完整的云广特高压直流工程的控制系统仿真模型,并结合实际工程的运行工况设计仿真试验算例。试验结果表明,仿真波形与实际工程的录波取得了高度一致性,该仿真建模方法是有效可行的。展开更多
An input-output signal selection based on Phillips-Heffron model of a parallel high voltage alternative current/high voltage direct current(HVAC/HVDC) power system is presented to study power system stability. It is w...An input-output signal selection based on Phillips-Heffron model of a parallel high voltage alternative current/high voltage direct current(HVAC/HVDC) power system is presented to study power system stability. It is well known that appropriate coupling of inputs-outputs signals in the multivariable HVDC-HVAC system can improve the performance of designed supplemetary controller. In this work, different analysis techniques are used to measure controllability and observability of electromechanical oscillation mode. Also inputs–outputs interactions are considered and suggestions are drawn to select the best signal pair through the system inputs-outputs. In addition, a supplementary online adaptive controller for nonlinear HVDC to damp low frequency oscillations in a weakly connected system is proposed. The results obtained using MATLAB software show that the best output-input for damping controller design is rotor speed deviation as out put and phase angle of rectifier as in put. Also response of system equipped with adaptive damping controller based on HVDC system has appropriate performance when it is faced with faults and disturbance.展开更多
This paper introduces the working principle of HVDC control and protection system. And the paper summarizes the flexible HVDC technology features and application fields and describes the composition and software intel...This paper introduces the working principle of HVDC control and protection system. And the paper summarizes the flexible HVDC technology features and application fields and describes the composition and software intelligent flexible HVDC control and protection system configuration. Finally, the simulation results are also given, experimental results show: HVDC flexible intelligent control and protection has a good control effect in the steady state and transient process, suitable for practical engineering application.展开更多
VFT (variable frequency transformer) has been recently used as art alternative to HVDC (high voltage direct current) to control power flow between asynchronous networks. VFT consumes less reactive power than a bac...VFT (variable frequency transformer) has been recently used as art alternative to HVDC (high voltage direct current) to control power flow between asynchronous networks. VFT consumes less reactive power than a back-to-back HVDC system, provides faster initial transient recovery, and has better natural damping capability. VFT is simply a DFIM (doubly-fed induction machine) where the machine torque controls the power flow from stator to rotor and vice versa. The main disadvantage of this VFT is the slip rings and brushes required for the rotor circuit, especially in bulk power transmission. The BDFM (brushless doubly-fed machine) with nested cage rotor machine is proved to be a comparable alternative to conventional DFIM in many applications with the advantage that all windings being in the stator frame with fixed output terminals. In this paper, the BDFM is used as a BVFT (brushless variable frequency transformer). A prototype machine is designed and simulated to verify the system validity.展开更多
Voltage source converter high-voltage direct current (VSC-HVDC) is a new power transmission technology pref- erable in small or medium power transmission. In this paper we discuss a new control system based on space...Voltage source converter high-voltage direct current (VSC-HVDC) is a new power transmission technology pref- erable in small or medium power transmission. In this paper we discuss a new control system based on space vector modulation (SVM) without any voltage line sensors. Using direct power control (DPC) SVM and a new double synchronous reference frame phase-locked loop (DSRF-PLL) approach, the control system is resistant to the majority of line voltage disturbances. Also, the system response has accelerated by using a feed forward power decoupled loop. The operation of this control strategy was verified in a SIMULINK/MATLAB simulation environment. To validate this control system, a 5 kV.A prototype system was constructed. Compared to the original controllers, the current total harmonic distortion (THD), the active and reactive deviations and the DC voltage overshoot were lowered by 2.5%, 6.2% and 8%, respectively. The rectifier power factor in the worst condition was 0.93 and the DC voltage settling time was 0.2 s.展开更多
文摘在基于实时数字仿真器(Real-time digital simulator,RTDS)所建立的特高压直流输电系统实时仿真平台中,常规锁相环技术无法实现换流阀触发脉冲的精确控制,不利于实际直流工程的故障重现。基于系统正序分量的瞬时锁相环控制原理,提出了一种高精度锁相环的建模方法,实现了电网系统频率的高精确跟踪测量。在RTDS仿真平台上搭建完整的云广特高压直流工程的控制系统仿真模型,并结合实际工程的运行工况设计仿真试验算例。试验结果表明,仿真波形与实际工程的录波取得了高度一致性,该仿真建模方法是有效可行的。
文摘An input-output signal selection based on Phillips-Heffron model of a parallel high voltage alternative current/high voltage direct current(HVAC/HVDC) power system is presented to study power system stability. It is well known that appropriate coupling of inputs-outputs signals in the multivariable HVDC-HVAC system can improve the performance of designed supplemetary controller. In this work, different analysis techniques are used to measure controllability and observability of electromechanical oscillation mode. Also inputs–outputs interactions are considered and suggestions are drawn to select the best signal pair through the system inputs-outputs. In addition, a supplementary online adaptive controller for nonlinear HVDC to damp low frequency oscillations in a weakly connected system is proposed. The results obtained using MATLAB software show that the best output-input for damping controller design is rotor speed deviation as out put and phase angle of rectifier as in put. Also response of system equipped with adaptive damping controller based on HVDC system has appropriate performance when it is faced with faults and disturbance.
文摘This paper introduces the working principle of HVDC control and protection system. And the paper summarizes the flexible HVDC technology features and application fields and describes the composition and software intelligent flexible HVDC control and protection system configuration. Finally, the simulation results are also given, experimental results show: HVDC flexible intelligent control and protection has a good control effect in the steady state and transient process, suitable for practical engineering application.
文摘VFT (variable frequency transformer) has been recently used as art alternative to HVDC (high voltage direct current) to control power flow between asynchronous networks. VFT consumes less reactive power than a back-to-back HVDC system, provides faster initial transient recovery, and has better natural damping capability. VFT is simply a DFIM (doubly-fed induction machine) where the machine torque controls the power flow from stator to rotor and vice versa. The main disadvantage of this VFT is the slip rings and brushes required for the rotor circuit, especially in bulk power transmission. The BDFM (brushless doubly-fed machine) with nested cage rotor machine is proved to be a comparable alternative to conventional DFIM in many applications with the advantage that all windings being in the stator frame with fixed output terminals. In this paper, the BDFM is used as a BVFT (brushless variable frequency transformer). A prototype machine is designed and simulated to verify the system validity.
文摘Voltage source converter high-voltage direct current (VSC-HVDC) is a new power transmission technology pref- erable in small or medium power transmission. In this paper we discuss a new control system based on space vector modulation (SVM) without any voltage line sensors. Using direct power control (DPC) SVM and a new double synchronous reference frame phase-locked loop (DSRF-PLL) approach, the control system is resistant to the majority of line voltage disturbances. Also, the system response has accelerated by using a feed forward power decoupled loop. The operation of this control strategy was verified in a SIMULINK/MATLAB simulation environment. To validate this control system, a 5 kV.A prototype system was constructed. Compared to the original controllers, the current total harmonic distortion (THD), the active and reactive deviations and the DC voltage overshoot were lowered by 2.5%, 6.2% and 8%, respectively. The rectifier power factor in the worst condition was 0.93 and the DC voltage settling time was 0.2 s.