The assessment of the measurement error status of online Capacitor Voltage Transformers (CVT) within the power grid is of profound significance to the equitable trade of electric energy and the secure operation of the...The assessment of the measurement error status of online Capacitor Voltage Transformers (CVT) within the power grid is of profound significance to the equitable trade of electric energy and the secure operation of the power grid. This paper advances an online CVT error state evaluation method, anchored in the in-phase relationship and outlier detection. Initially, this method leverages the in-phase relationship to obviate the influence of primary side fluctuations in the grid on assessment accuracy. Subsequently, Principal Component Analysis (PCA) is employed to meticulously disentangle the error change information inherent in the CVT from the measured values and to compute statistics that delineate the error state. Finally, the Local Outlier Factor (LOF) is deployed to discern outliers in the statistics, with thresholds serving to appraise the CVT error state. Experimental results incontrovertibly demonstrate the efficacy of this method, showcasing its prowess in effecting online tracking of CVT error changes and conducting error state assessments. The discernible enhancements in reliability, accuracy, and sensitivity are manifest, with the assessment accuracy reaching an exemplary 0.01%.展开更多
Output voltage is an important performance characteristic of planar insulating core transformer (PICT).In PICT magnetic cores are insulated from their neighboring magnetic cores by solid insulating materials.Solid ins...Output voltage is an important performance characteristic of planar insulating core transformer (PICT).In PICT magnetic cores are insulated from their neighboring magnetic cores by solid insulating materials.Solid insulating materials can increase leakage flux.This results in a low generated voltage in secondary coils,especially on the upper stages.Connecting flux compensation capacitors to secondary coils can compensate the flux loss.Design equations to calculate the flux compensation capacitors value and relevant simulation by CST and Protel software were presented.Simulation results of an actual PICT showed that output voltage increased by 19% after being connected to flux compensation capacitors and the voltage on every stage was equally distributed.Results of simulation were consistent with the following experimental test,which revealed that flux compensation capacitors were effective.展开更多
This article presents an extensive examination and modeling of Capacitor Coupled Substations (CCS), noting some of their inherent constraints. The underlying implementation of a CCS is to supply electricity directly f...This article presents an extensive examination and modeling of Capacitor Coupled Substations (CCS), noting some of their inherent constraints. The underlying implementation of a CCS is to supply electricity directly from high-voltage (HV) transmission lines to low-voltage (LV) consumers through coupling capacitors and is said to be cost-effective as compared to conventional distribution networks. However, the functionality of such substations is susceptible to various transient phenomena, including ferroresonance and overvoltage occurrences. To address these challenges, the study uses simulations to evaluate the effectiveness of conventional resistor-inductor-capacitor (RLC) filter in mitigating hazardous overvoltage resulting from transients. The proposed methodology entails using standard RLC filter to suppress transients and its associated overvoltage risks. Through a series of MATLAB/Simulink simulations, the research emphasizes the practical effectiveness of this technique. The study examines the impact of transients under varied operational scenarios, including no-load switching conditions, temporary short-circuits, and load on/off events. The primary aim of the article is to assess the viability of using an established technology to manage system instabilities upon the energization of a CCS under no-load circumstances or in case of a short-circuit fault occurring on the primary side of the CCS distribution transformer. The findings underscore the effectiveness of conventional RLC filters in suppressing transients induced by the CCS no-load switching.展开更多
The main purpose of the electrical power system is to transport and distribute energy generated by the central power plants in a safe and reliable manner to the customer premises. Most of the electrical equipment is e...The main purpose of the electrical power system is to transport and distribute energy generated by the central power plants in a safe and reliable manner to the customer premises. Most of the electrical equipment is exposed within the open which suggests they can be vulnerable to lightning strikes, road dwindling, windstorms, and a few engineering activities with the potential of causing different degrees of damage to the electrical equipment. One of the ways to guard the equipment is to deploy switching devices. However, the operations of most of these switching devices produce oscillatory transient in the electrical transmission and distribution systems which result in voltage, current, and frequency fluctuations in the load. This paper investigates the effect of switching devices on power quality and proposes a positive sequence voltage power transient suppression technique that can spontaneously improve the distorted voltage at the instant of capacitor switching using the capacitor line model as a case study. MATLAB/Simulink software was utilized for the analysis on an electrical network model with bus voltages of 69 kV/12.47 kV and 480 V. The results showed that, during switching operations, the positive sequence voltage power detector block produces ripple-free accurate results.展开更多
为解决现有电容式电压互感器(capacitor voltage transformer,CVT)无法对电力系统暂态电压扰动信号精准监测问题,本文通过在原有CVT低压端串联大电容C_(3),设计了一种基于CVT,适用于500kV系统的暂态电压扰动监测装置。通过建立模型,对...为解决现有电容式电压互感器(capacitor voltage transformer,CVT)无法对电力系统暂态电压扰动信号精准监测问题,本文通过在原有CVT低压端串联大电容C_(3),设计了一种基于CVT,适用于500kV系统的暂态电压扰动监测装置。通过建立模型,对装置的低压及二次回路对频响影响进行仿真。借助实验平台对该装置性能进行了评估,结果表明装置暂态特性、线性度、频率响应性能、波形跟随特性均满足技术指标要求,目前该装置在现场工作良好。展开更多
This paper presents a novel method that is applied to realize the Linear Transformation(LT)Switched-Capacitor Filter(SCF).It adopts the Voltage Control Voltage Source(VCVS)equalized transfor-mation to revise the origi...This paper presents a novel method that is applied to realize the Linear Transformation(LT)Switched-Capacitor Filter(SCF).It adopts the Voltage Control Voltage Source(VCVS)equalized transfor-mation to revise the original LC ladder filter and induce it into 16 basic sections and then extend the princi-ple of the LT in order to fit active and 3 port networks and give out switched-capacitor circuits corre-sponding to the 16 basic sections,which can realize all four kinds of filters——LP,HP,BP,BS filters.De-signed examples are given here.An Nth order filter only requires N amplifiers and the circuit is insensitive toparasitic capacitances.The experimental results of a 3rd order elliptic LP and a 6th order elliptic BP are giv-en and agree with the theory.展开更多
通过等效电路分析了电容式电压互感器(capacitor voltage transformer,CVT)二次电压变化与其电容量变化的关系,结合SCADA系统中存储的线路和母线电压数据,开展了某电网100余座变电站CVT缺陷排查工作,有效避免了多起CVT缺陷扩大影响电力...通过等效电路分析了电容式电压互感器(capacitor voltage transformer,CVT)二次电压变化与其电容量变化的关系,结合SCADA系统中存储的线路和母线电压数据,开展了某电网100余座变电站CVT缺陷排查工作,有效避免了多起CVT缺陷扩大影响电力系统稳定运行的事故发生,通过典型缺陷解体案例的分析进一步验证了该方法的有效性,该方法的成功实践一定程度上为CVT缺陷的提前发现和及时处理提供了有效经验。展开更多
With the increase of the operating voltage and enlargement of the size of the capacitor voltage transformer(CVT),the additional measurement error caused by stray capacitance coupling and leakage current along the poll...With the increase of the operating voltage and enlargement of the size of the capacitor voltage transformer(CVT),the additional measurement error caused by stray capacitance coupling and leakage current along the polluted surface of the CVT becomes noticeable.The equipotential shielding CVT(EPSCVT)was proposed and designed by the authors to mitigate these effects.An improved conceptual design option of the EPS-CVT is presented in this paper with special references to this study to improve the shielding effect without the increase of shielding capacitance.A proposed method of non-uniform capacitance configuration can improve the shielding effect significantly without an increase of the external shielding capacitance.Based on this achievement,the potential difference and the capacitive current exchange between the internal measuring system and external shielding systems are significantly reduced.In the evaluation of the shielding effect for the influence of stray capacitance,compared with a conventional CVT with equal capacitance,EPS-CVT can reduce the measurement error by two orders of magnitude.In addition,the measurement error caused by the leakage current can also be greatly reduced,especially for the reduction of the phase angle error.Based on the improved design method,a design scheme for an engineering application is proposed which can achieve effective shielding while ensuring as good a technical performance as the existing CVT.展开更多
文摘The assessment of the measurement error status of online Capacitor Voltage Transformers (CVT) within the power grid is of profound significance to the equitable trade of electric energy and the secure operation of the power grid. This paper advances an online CVT error state evaluation method, anchored in the in-phase relationship and outlier detection. Initially, this method leverages the in-phase relationship to obviate the influence of primary side fluctuations in the grid on assessment accuracy. Subsequently, Principal Component Analysis (PCA) is employed to meticulously disentangle the error change information inherent in the CVT from the measured values and to compute statistics that delineate the error state. Finally, the Local Outlier Factor (LOF) is deployed to discern outliers in the statistics, with thresholds serving to appraise the CVT error state. Experimental results incontrovertibly demonstrate the efficacy of this method, showcasing its prowess in effecting online tracking of CVT error changes and conducting error state assessments. The discernible enhancements in reliability, accuracy, and sensitivity are manifest, with the assessment accuracy reaching an exemplary 0.01%.
文摘Output voltage is an important performance characteristic of planar insulating core transformer (PICT).In PICT magnetic cores are insulated from their neighboring magnetic cores by solid insulating materials.Solid insulating materials can increase leakage flux.This results in a low generated voltage in secondary coils,especially on the upper stages.Connecting flux compensation capacitors to secondary coils can compensate the flux loss.Design equations to calculate the flux compensation capacitors value and relevant simulation by CST and Protel software were presented.Simulation results of an actual PICT showed that output voltage increased by 19% after being connected to flux compensation capacitors and the voltage on every stage was equally distributed.Results of simulation were consistent with the following experimental test,which revealed that flux compensation capacitors were effective.
文摘This article presents an extensive examination and modeling of Capacitor Coupled Substations (CCS), noting some of their inherent constraints. The underlying implementation of a CCS is to supply electricity directly from high-voltage (HV) transmission lines to low-voltage (LV) consumers through coupling capacitors and is said to be cost-effective as compared to conventional distribution networks. However, the functionality of such substations is susceptible to various transient phenomena, including ferroresonance and overvoltage occurrences. To address these challenges, the study uses simulations to evaluate the effectiveness of conventional resistor-inductor-capacitor (RLC) filter in mitigating hazardous overvoltage resulting from transients. The proposed methodology entails using standard RLC filter to suppress transients and its associated overvoltage risks. Through a series of MATLAB/Simulink simulations, the research emphasizes the practical effectiveness of this technique. The study examines the impact of transients under varied operational scenarios, including no-load switching conditions, temporary short-circuits, and load on/off events. The primary aim of the article is to assess the viability of using an established technology to manage system instabilities upon the energization of a CCS under no-load circumstances or in case of a short-circuit fault occurring on the primary side of the CCS distribution transformer. The findings underscore the effectiveness of conventional RLC filters in suppressing transients induced by the CCS no-load switching.
文摘The main purpose of the electrical power system is to transport and distribute energy generated by the central power plants in a safe and reliable manner to the customer premises. Most of the electrical equipment is exposed within the open which suggests they can be vulnerable to lightning strikes, road dwindling, windstorms, and a few engineering activities with the potential of causing different degrees of damage to the electrical equipment. One of the ways to guard the equipment is to deploy switching devices. However, the operations of most of these switching devices produce oscillatory transient in the electrical transmission and distribution systems which result in voltage, current, and frequency fluctuations in the load. This paper investigates the effect of switching devices on power quality and proposes a positive sequence voltage power transient suppression technique that can spontaneously improve the distorted voltage at the instant of capacitor switching using the capacitor line model as a case study. MATLAB/Simulink software was utilized for the analysis on an electrical network model with bus voltages of 69 kV/12.47 kV and 480 V. The results showed that, during switching operations, the positive sequence voltage power detector block produces ripple-free accurate results.
文摘为解决现有电容式电压互感器(capacitor voltage transformer,CVT)无法对电力系统暂态电压扰动信号精准监测问题,本文通过在原有CVT低压端串联大电容C_(3),设计了一种基于CVT,适用于500kV系统的暂态电压扰动监测装置。通过建立模型,对装置的低压及二次回路对频响影响进行仿真。借助实验平台对该装置性能进行了评估,结果表明装置暂态特性、线性度、频率响应性能、波形跟随特性均满足技术指标要求,目前该装置在现场工作良好。
文摘This paper presents a novel method that is applied to realize the Linear Transformation(LT)Switched-Capacitor Filter(SCF).It adopts the Voltage Control Voltage Source(VCVS)equalized transfor-mation to revise the original LC ladder filter and induce it into 16 basic sections and then extend the princi-ple of the LT in order to fit active and 3 port networks and give out switched-capacitor circuits corre-sponding to the 16 basic sections,which can realize all four kinds of filters——LP,HP,BP,BS filters.De-signed examples are given here.An Nth order filter only requires N amplifiers and the circuit is insensitive toparasitic capacitances.The experimental results of a 3rd order elliptic LP and a 6th order elliptic BP are giv-en and agree with the theory.
文摘通过等效电路分析了电容式电压互感器(capacitor voltage transformer,CVT)二次电压变化与其电容量变化的关系,结合SCADA系统中存储的线路和母线电压数据,开展了某电网100余座变电站CVT缺陷排查工作,有效避免了多起CVT缺陷扩大影响电力系统稳定运行的事故发生,通过典型缺陷解体案例的分析进一步验证了该方法的有效性,该方法的成功实践一定程度上为CVT缺陷的提前发现和及时处理提供了有效经验。
文摘With the increase of the operating voltage and enlargement of the size of the capacitor voltage transformer(CVT),the additional measurement error caused by stray capacitance coupling and leakage current along the polluted surface of the CVT becomes noticeable.The equipotential shielding CVT(EPSCVT)was proposed and designed by the authors to mitigate these effects.An improved conceptual design option of the EPS-CVT is presented in this paper with special references to this study to improve the shielding effect without the increase of shielding capacitance.A proposed method of non-uniform capacitance configuration can improve the shielding effect significantly without an increase of the external shielding capacitance.Based on this achievement,the potential difference and the capacitive current exchange between the internal measuring system and external shielding systems are significantly reduced.In the evaluation of the shielding effect for the influence of stray capacitance,compared with a conventional CVT with equal capacitance,EPS-CVT can reduce the measurement error by two orders of magnitude.In addition,the measurement error caused by the leakage current can also be greatly reduced,especially for the reduction of the phase angle error.Based on the improved design method,a design scheme for an engineering application is proposed which can achieve effective shielding while ensuring as good a technical performance as the existing CVT.