A defect of chromatogram in a 35kV oil-immersed three-phase one-piece electric reactor in a 500kV substation。The initial analysis suggests that the defect is caused by the loose connection of the iron core magnet shi...A defect of chromatogram in a 35kV oil-immersed three-phase one-piece electric reactor in a 500kV substation。The initial analysis suggests that the defect is caused by the loose connection of the iron core magnet shield (magnet shield layer of iron core or earthling top). Examination of winding DC resistance, DGA and other relevant examinations were carried out to investigate the defect reasons., which is demonstrated by the dismantlement. In-depth study is taken and corresponding prevention measures are put forward in the paper.展开更多
The SF6 decomposed products are very alike,so the peaks of the SF6 decomposed products are overlapped.It make us hard to quantitatively calculate.This paper introduced a method to separate the overlapped chromatogram ...The SF6 decomposed products are very alike,so the peaks of the SF6 decomposed products are overlapped.It make us hard to quantitatively calculate.This paper introduced a method to separate the overlapped chromatogram peaks with iterative curve-fitting and Gauss function,and deduced the formula of the iterative curve-fitting;provided a method to calculate the initial value of the peaks intensity and width by iterative formula,and confirm the final peaks intensity and width to separate the overlapped signals.By the analysis of the real chromatogram data,it proved the validity of this method on the main components used in distinguishing the GIS internal defects.This method overcomes the influence of SF6 peak to the other thin concentration peaks,so it can be used in the study of the quantitative analysis of the decomposed products on different failures and different voltages.展开更多
文摘A defect of chromatogram in a 35kV oil-immersed three-phase one-piece electric reactor in a 500kV substation。The initial analysis suggests that the defect is caused by the loose connection of the iron core magnet shield (magnet shield layer of iron core or earthling top). Examination of winding DC resistance, DGA and other relevant examinations were carried out to investigate the defect reasons., which is demonstrated by the dismantlement. In-depth study is taken and corresponding prevention measures are put forward in the paper.
基金Project Supported by National Natural Science Foundation of China ( 50777070), Science and Technique Project of Chongqing (CSTC, 2007AC2041 ).
文摘The SF6 decomposed products are very alike,so the peaks of the SF6 decomposed products are overlapped.It make us hard to quantitatively calculate.This paper introduced a method to separate the overlapped chromatogram peaks with iterative curve-fitting and Gauss function,and deduced the formula of the iterative curve-fitting;provided a method to calculate the initial value of the peaks intensity and width by iterative formula,and confirm the final peaks intensity and width to separate the overlapped signals.By the analysis of the real chromatogram data,it proved the validity of this method on the main components used in distinguishing the GIS internal defects.This method overcomes the influence of SF6 peak to the other thin concentration peaks,so it can be used in the study of the quantitative analysis of the decomposed products on different failures and different voltages.