The paper presents a simple model for outdoor air contaminant transmission into occupied rooms. In the model, several factors such as filtration, ventilation, deposition, re-emission, outdoor concentration and indoor ...The paper presents a simple model for outdoor air contaminant transmission into occupied rooms. In the model, several factors such as filtration, ventilation, deposition, re-emission, outdoor concentration and indoor sources are included. The model results show that the air exchange rate plays an important role in the transmission of outdoor contaminants into the indoor environment. The model shows that increasing the value of the filtration efficiency decreases the mass concentration of indoor particles. In addition, if outdoor aerosol particles have a periodic behaviour, indoor aerosol particles also behave periodically but smoother. Indoor sources are found to be able to increase indoor concentrations greatly and continuously.展开更多
A new air exchange rate (AER) monitoring method using continuous CO2 sensors was developed and validated through both laboratory experiments and field studies. Controlled laboratory simulation tests were conducted i...A new air exchange rate (AER) monitoring method using continuous CO2 sensors was developed and validated through both laboratory experiments and field studies. Controlled laboratory simulation tests were conducted in a 1-m3 environmental chamber at different AERs (0.1-10.0 hr-1). AERs were determined using the decay method based on box model assumptions. Field tests were conducted in classrooms, dormitories, meeting rooms and apartments during 2-5 weekdays using CO2 sensors coupled with data loggers. Indoor temperature, relative humidity (RH), and CO2 concentrations were continuously monitored while outdoor parameters combined with on-site climate conditions were recorded. Statistical results indicated that good laboratory performance was achieved: duplicate precision was within 10%, and the measured AERs were 90%-120% of the real AERs. Average AERs were 1.22, 1.37, 1.10, 1.91 and 0.73 hr-l in dormitories, air-conditioned classrooms, classrooms with an air circulation cooling system, reading rooms, and meeting rooms, respectively. In an elderly particulate matter exposure study, all the homes had AER values ranging from 0.29 to 3.46 hr-1 in fall, and 0.12 to 1.39 hr-1 in winter with a median AER of 1.15.展开更多
This study assessed six commercially available in-duct air cleaning devices which are designed to be mounted in the central ventilation system of offices or commercial buildings.The selected devices use different air ...This study assessed six commercially available in-duct air cleaning devices which are designed to be mounted in the central ventilation system of offices or commercial buildings.The selected devices use different air cleaning technologies:mechanical filtration,electrostatic precipitation,gas filtration,ionization/cold plasma,photocatalytic oxidation(PCO)and catalysis under UV light.They were tested against particles,a mixture of volatile organic compounds containing acetone,acetaldehyde,toluene,heptane and formaldehyde,and two bio-contaminants:Aspergillus brasiliensis(fungus)and Staphylococcus epidermidis(bacteria).Two different test rigs were used.The single pass efficiency of each device was determined for three airflow rates,corresponding to face velocities ranging from 0.9 to 2.7 m/s,and two sets of temperature and humidity that are representative of indoor air conditions in wintertime and summertime.The concentration of the chal-lenge volatile organic compounds was also varied in the 30 to 100μg/m^(3)range as a way to characterize their influence on efficiency at realistic concentration levels for non-industrial buildings.Measurements of ozone and formaldehyde concentration downstream of the air cleaners were carried out to determine the emission rate of by-products into the air stream.Finally,the energy issue was addressed by measuring the electric power drawn and pressure loss of the devices.The results showed that two devices,namely a radiant catalytic ionizer and a plasma ionizer,had a very low single pass efficiency against all the challenge pollutants.The association of the plasma ionizer and the electrostatic precipitator did not produce a synergetic effect between the two technologies either,contrary to what their manufacturer claims.Finally,three of the six devices tested were effective in terms of pollutant removal,but only two had an acceptable energy effectiveness in view of their use in low or zero energy buildings.Their energy effectiveness ranged from a few thousand m^(3)/kWh for VOCs at the highest airflow rate(3600 m^(3)/h),to more than 60000 m^(3)/kWh for particles and bio-contaminants at 1200 or 1600 m^(3)/h.These results are at least one order of magnitude higher than the majority of stand-alone air cleaners.Moreover,they suggest that optimal IAQ and energy conditions can be achieved if variable air volume control methods are used to maintain indoor temperature and humidity.展开更多
基金Funded by Beijing Higher Education Young Elite Teacher Project(No.YETP0371)National Key Technologies R&D Program of China(No.2012BAJ02B02)
文摘The paper presents a simple model for outdoor air contaminant transmission into occupied rooms. In the model, several factors such as filtration, ventilation, deposition, re-emission, outdoor concentration and indoor sources are included. The model results show that the air exchange rate plays an important role in the transmission of outdoor contaminants into the indoor environment. The model shows that increasing the value of the filtration efficiency decreases the mass concentration of indoor particles. In addition, if outdoor aerosol particles have a periodic behaviour, indoor aerosol particles also behave periodically but smoother. Indoor sources are found to be able to increase indoor concentrations greatly and continuously.
基金supported by the Scientific Research Projects for State Environmental Protection and Commonweal (No. 200709048)the National Natural Science Foundation of China (No. 20977054/B070704)+1 种基金the Innovation Fund of Nankai UniversityJoint Research Grant to Both Nankai University and Tianjin University sponsored by the Ministry of Education,China
文摘A new air exchange rate (AER) monitoring method using continuous CO2 sensors was developed and validated through both laboratory experiments and field studies. Controlled laboratory simulation tests were conducted in a 1-m3 environmental chamber at different AERs (0.1-10.0 hr-1). AERs were determined using the decay method based on box model assumptions. Field tests were conducted in classrooms, dormitories, meeting rooms and apartments during 2-5 weekdays using CO2 sensors coupled with data loggers. Indoor temperature, relative humidity (RH), and CO2 concentrations were continuously monitored while outdoor parameters combined with on-site climate conditions were recorded. Statistical results indicated that good laboratory performance was achieved: duplicate precision was within 10%, and the measured AERs were 90%-120% of the real AERs. Average AERs were 1.22, 1.37, 1.10, 1.91 and 0.73 hr-l in dormitories, air-conditioned classrooms, classrooms with an air circulation cooling system, reading rooms, and meeting rooms, respectively. In an elderly particulate matter exposure study, all the homes had AER values ranging from 0.29 to 3.46 hr-1 in fall, and 0.12 to 1.39 hr-1 in winter with a median AER of 1.15.
文摘This study assessed six commercially available in-duct air cleaning devices which are designed to be mounted in the central ventilation system of offices or commercial buildings.The selected devices use different air cleaning technologies:mechanical filtration,electrostatic precipitation,gas filtration,ionization/cold plasma,photocatalytic oxidation(PCO)and catalysis under UV light.They were tested against particles,a mixture of volatile organic compounds containing acetone,acetaldehyde,toluene,heptane and formaldehyde,and two bio-contaminants:Aspergillus brasiliensis(fungus)and Staphylococcus epidermidis(bacteria).Two different test rigs were used.The single pass efficiency of each device was determined for three airflow rates,corresponding to face velocities ranging from 0.9 to 2.7 m/s,and two sets of temperature and humidity that are representative of indoor air conditions in wintertime and summertime.The concentration of the chal-lenge volatile organic compounds was also varied in the 30 to 100μg/m^(3)range as a way to characterize their influence on efficiency at realistic concentration levels for non-industrial buildings.Measurements of ozone and formaldehyde concentration downstream of the air cleaners were carried out to determine the emission rate of by-products into the air stream.Finally,the energy issue was addressed by measuring the electric power drawn and pressure loss of the devices.The results showed that two devices,namely a radiant catalytic ionizer and a plasma ionizer,had a very low single pass efficiency against all the challenge pollutants.The association of the plasma ionizer and the electrostatic precipitator did not produce a synergetic effect between the two technologies either,contrary to what their manufacturer claims.Finally,three of the six devices tested were effective in terms of pollutant removal,but only two had an acceptable energy effectiveness in view of their use in low or zero energy buildings.Their energy effectiveness ranged from a few thousand m^(3)/kWh for VOCs at the highest airflow rate(3600 m^(3)/h),to more than 60000 m^(3)/kWh for particles and bio-contaminants at 1200 or 1600 m^(3)/h.These results are at least one order of magnitude higher than the majority of stand-alone air cleaners.Moreover,they suggest that optimal IAQ and energy conditions can be achieved if variable air volume control methods are used to maintain indoor temperature and humidity.