This paper presents a three-phase integrated power electronic transformer(PET)topology with the capability of DC fault clearance based on the investigation of PET topology.The proposed PET has three ports of high-volt...This paper presents a three-phase integrated power electronic transformer(PET)topology with the capability of DC fault clearance based on the investigation of PET topology.The proposed PET has three ports of high-voltage AC,high-voltage DC and low-voltage DC,which can achieve the flexible access of distributed energy resources・The power unit of the PET adopts a three-phase integrated topology,and the single-phase fluctuating power in the DC-link capacitor is reduced by a 4-port DC/DC converter,thereby reducing the capacitance of the DC-link capacitor;Meanwhile,the power unit uses the clamp double sub-module(CDSM)to allow for self-clearing of the short-circuit fault on the high-voltage DC side.Finally,this paper verifies the proposed PET through an EMT simulation and experimental prototype.展开更多
基金supported by National Key Research and Development Program of China(2016YFB0400505)Science and Technology Project of State Grid Corporation(SGRIGLBDTKJ[2017]676).
文摘This paper presents a three-phase integrated power electronic transformer(PET)topology with the capability of DC fault clearance based on the investigation of PET topology.The proposed PET has three ports of high-voltage AC,high-voltage DC and low-voltage DC,which can achieve the flexible access of distributed energy resources・The power unit of the PET adopts a three-phase integrated topology,and the single-phase fluctuating power in the DC-link capacitor is reduced by a 4-port DC/DC converter,thereby reducing the capacitance of the DC-link capacitor;Meanwhile,the power unit uses the clamp double sub-module(CDSM)to allow for self-clearing of the short-circuit fault on the high-voltage DC side.Finally,this paper verifies the proposed PET through an EMT simulation and experimental prototype.