This paper proposed a simple approach to determine noise frequency of boiler drum level in order to improve control performance. Based on analysis of uncertainty of drum level, the redundant oscillation component of s...This paper proposed a simple approach to determine noise frequency of boiler drum level in order to improve control performance. Based on analysis of uncertainty of drum level, the redundant oscillation component of signal, noise is ascribed to the surface wave of drum water. According to the characteristic of surface wave, a new method was proposed to determine noise’s frequency band. By gradually removing the lowest frequency component of signal, the variance of remained component is calculated and observed. An apparent turning point was found and the corresponding critical frequcncy was determined. With this result a low-pass filter was designed to separate noise component. Finally validation is conducted by comparing the proposed method and conventional ones. Results show the accuracy and simpleness of the proposed method.展开更多
文摘This paper proposed a simple approach to determine noise frequency of boiler drum level in order to improve control performance. Based on analysis of uncertainty of drum level, the redundant oscillation component of signal, noise is ascribed to the surface wave of drum water. According to the characteristic of surface wave, a new method was proposed to determine noise’s frequency band. By gradually removing the lowest frequency component of signal, the variance of remained component is calculated and observed. An apparent turning point was found and the corresponding critical frequcncy was determined. With this result a low-pass filter was designed to separate noise component. Finally validation is conducted by comparing the proposed method and conventional ones. Results show the accuracy and simpleness of the proposed method.