Ultrahigh voltage(UHV)and extra-high voltage(EHV)have been widely used in power system,so the requirement for technology of operation management,as well as the accident analysis and disposal are more pressing.Based on...Ultrahigh voltage(UHV)and extra-high voltage(EHV)have been widely used in power system,so the requirement for technology of operation management,as well as the accident analysis and disposal are more pressing.Based on the theory of Newton-Laphson power flow method,this simulation system imitates the primary device and secondary circuit,together with the normal,the abnormal and accidents in operation.Through simulation in various situations,it validates that this design is capable of simulating the complicated faults in UHV and EHV accurately and in real time.In addition,it can analyse and dispose them efficiently.展开更多
The characteristics of conducted disturbances via current transformer(CT)caused by switch operations in 1000 kV UHV substations are studied in this paper.Since the broadband circuit models might have limitations on th...The characteristics of conducted disturbances via current transformer(CT)caused by switch operations in 1000 kV UHV substations are studied in this paper.Since the broadband circuit models might have limitations on the stability and accuracy for CT conducted disturbance simulation,a frequencydomain simulation method without circuit synthesis is proposed based on VFTC spectrum and CT transfer characteristics.To improve VFTC simulation accuracy,both the bushing radiation loss and frequency-dependent earth impedance are taken into consideration.Transfer characteristics of three types of windings for the 1000 kV GIS CT are ingeniously measured from a combination of fast and slow impulse tests.Through conducted disturbances simulations in UHV Wuhu substation,bushing radiation loss is found to have a suppression effect on the highfrequency response but the effect of frequency-dependent earth impedance can be ignored.As a result,the maximum amplitude of 84.5 A for the conducted disturbance is obtained,thus a fast damped oscillatory wave immunity test with no lower than Level 4 from IEC standard is suggested to test the anti-interference performance of the secondary equipment in UHV substation.展开更多
基金China Postdoctoral Science Foundation(No.20080441149)Shandong Province Postdoctoral Innovation Program Foundation(No.200803036)SDUST Research Fund(No.2010KYTD101)
文摘Ultrahigh voltage(UHV)and extra-high voltage(EHV)have been widely used in power system,so the requirement for technology of operation management,as well as the accident analysis and disposal are more pressing.Based on the theory of Newton-Laphson power flow method,this simulation system imitates the primary device and secondary circuit,together with the normal,the abnormal and accidents in operation.Through simulation in various situations,it validates that this design is capable of simulating the complicated faults in UHV and EHV accurately and in real time.In addition,it can analyse and dispose them efficiently.
基金supported by the National Natural Science Foundation of China(51977199).
文摘The characteristics of conducted disturbances via current transformer(CT)caused by switch operations in 1000 kV UHV substations are studied in this paper.Since the broadband circuit models might have limitations on the stability and accuracy for CT conducted disturbance simulation,a frequencydomain simulation method without circuit synthesis is proposed based on VFTC spectrum and CT transfer characteristics.To improve VFTC simulation accuracy,both the bushing radiation loss and frequency-dependent earth impedance are taken into consideration.Transfer characteristics of three types of windings for the 1000 kV GIS CT are ingeniously measured from a combination of fast and slow impulse tests.Through conducted disturbances simulations in UHV Wuhu substation,bushing radiation loss is found to have a suppression effect on the highfrequency response but the effect of frequency-dependent earth impedance can be ignored.As a result,the maximum amplitude of 84.5 A for the conducted disturbance is obtained,thus a fast damped oscillatory wave immunity test with no lower than Level 4 from IEC standard is suggested to test the anti-interference performance of the secondary equipment in UHV substation.