DC magnetic biasing problem,caused by the DC grounding electrode, threatened the safe operation of AC power grid. In this paper, the characteristics of the soil stratification near DC grounding electrode was researche...DC magnetic biasing problem,caused by the DC grounding electrode, threatened the safe operation of AC power grid. In this paper, the characteristics of the soil stratification near DC grounding electrode was researched. The AC-DC interconnected large-scale system model under the monopole operation mode was established. The earth surface potential and DC current distribution in various stations under the different surface thickness was calculated. Some useful conclusions are drawn from the analyzed results.展开更多
This paper presents and investigates planar and coaxial high frequency power transformers used for DC/DC converters in a three phase photo voltaic (PV) power systems. The winding structure including a Faraday shield...This paper presents and investigates planar and coaxial high frequency power transformers used for DC/DC converters in a three phase photo voltaic (PV) power systems. The winding structure including a Faraday shield between the primary and secondary windings is designed to minimize eddy current losses, skin and proximity effects, and to reduce the leakage inductance, and the inter winding coupling capacitance. Finite Element Method is employed to analyze the magnetic flux and eddy current distributions. The two different kinds of prototype high frequency transformers are designed and tested. The simulation and experiment results are demonstrated and compared with non-shielded transformers. The shielded transformers have achieved the expected results with a relatively small coupling capacitance, compared with the conventional high frequency transformer. This shield decreases the inter-winding coupling capacitance Cps. The topology of this shield has to be such that it acts as a Faraday screen while avoiding eddy current generation.展开更多
Symmetrical monopolar configuration is the prevailing scheme configuration for modular multilevel converter based high-voltage direct current(MMC-HVDC) links, in which severe DC overvoltage or overcurrent can be cause...Symmetrical monopolar configuration is the prevailing scheme configuration for modular multilevel converter based high-voltage direct current(MMC-HVDC) links, in which severe DC overvoltage or overcurrent can be caused by the DC faults. To deal with the possible asymmetry in the DC faults and the coupling effects of the DC lines, this paper analyzes the DC fault characteristics based on the phase-mode transformation. First, the DC grid is decomposed into the common-mode and the differential-mode networks. The equivalent models of the MMCs and DC lines in the two networks are derived, respectively. Then, based on the state matrices, a unified numerical calculation method for the fault voltages and currents at the DC side is proposed. Compared with the time-domain simulations performed on PSCAD/EMTDC, the accuracy of the proposed method is validated. Last, the system parameter analysis shows that the grounding parameters play an important role in reducing the severity of the pole-to-ground faults, whereas the coupling effects of the DC lines should be considered when calculating the DC fault currents associated with the pole-to-pole faults.展开更多
Practically,the load currents in three phases are asymmetric in the power system.It means that the impedances are different in all three phases.If the consumer’s transformer neutral cut off and/or was disconnected fr...Practically,the load currents in three phases are asymmetric in the power system.It means that the impedances are different in all three phases.If the consumer’s transformer neutral cut off and/or was disconnected from the neutral of power supply source,then there will be some trouble and failure occurred.The current in the neutral wire drops down to zero when the neutral wire is cut off and the phase currents of all three-phase equal to each other since there was no return wire.The currents are equal but the voltages at the phase consumers are different.Especially for residential single-phase consumers,the voltage at the consumers of the phase varies differently for three phase systems when the neutral wire was disconnected at consumer side and even the voltage at the consumers one or two of those three phases becomes over nominal voltage or reaches nearly line voltage.In this case,the electronic appliances in that phase will be fed by high voltage than the rated value and they can be broken down.In the power system of UB(Ulaanbaatar)city,there are some occasional such kind of failures every year.Obviously,many electronic appliances were broken down due to high voltage and the electricity utility companies respond for service charge of damaged parts.展开更多
随着基于电压源型换流器的柔性直流输电(voltage source converter based high voltage direct current,VSC-HVDC)技术的快速发展,十几年间世界范围内已建成数十个各种不同电压等级的VSC-HVDC工程。根据交流电网的发展历史,未来构建大...随着基于电压源型换流器的柔性直流输电(voltage source converter based high voltage direct current,VSC-HVDC)技术的快速发展,十几年间世界范围内已建成数十个各种不同电压等级的VSC-HVDC工程。根据交流电网的发展历史,未来构建大规模直流电网是必然趋势。然而直流电网必须采用DC/DC变换器来充当直流变压器的角色,因此高效率、低成本的高压大容量DC/DC变换器是直流电网技术中亟待攻克的关键基础性课题。该文针对不同电压等级直流输电线路互联的技术需求,对经典低压DC/DC拓扑进行改造,推演出一系列基于容性能量转移原理的高压大容量DC/DC变换器拓扑,并揭示此类拓扑的演化规律和换流原理。相比传统变换器方案,该拓扑可降低器件数量,提升拓扑转换效率以及减小变换器体积重量。最后,通过仿真和实验验证基于容性能量转移原理的DC/DC变换器的可行性。展开更多
直流电流互感器(direct-current current transformers,DCCT)是高压直流输电系统中的重要测量设备。为保证其准确可靠,DCCT投运前和停电维护时需现场校准。对于电子式DCCT现场抗干扰及数字化同步两大关键问题,该文提出电子式DCCT的校准...直流电流互感器(direct-current current transformers,DCCT)是高压直流输电系统中的重要测量设备。为保证其准确可靠,DCCT投运前和停电维护时需现场校准。对于电子式DCCT现场抗干扰及数字化同步两大关键问题,该文提出电子式DCCT的校准方法并设计一套校准系统,主要包括直流电流源、作为标准器的磁调制式直流电流比较仪(DC current comparator,DCC)和具有光纤数字同步的电子式DCCT校验仪。重点对标准器和校验仪进行了现场抗干扰分析,对于标准器现场使用时可能遇到的母线偏心和邻近通流导体干扰情况进行仿真分析,优化磁屏蔽结构,研制了DCC样机,经中国计量科学研究院校准,该DCC不确定度为5×10-6,在此基础上进行了母线偏心和邻近导体影响测试,验证了优化的屏蔽结构能够有效抵御现场干扰;为检验校准系统,采用0.2级DCCT进行了校准测试,结果表明校准系统不确定度优于5×10-4。展开更多
文摘DC magnetic biasing problem,caused by the DC grounding electrode, threatened the safe operation of AC power grid. In this paper, the characteristics of the soil stratification near DC grounding electrode was researched. The AC-DC interconnected large-scale system model under the monopole operation mode was established. The earth surface potential and DC current distribution in various stations under the different surface thickness was calculated. Some useful conclusions are drawn from the analyzed results.
文摘This paper presents and investigates planar and coaxial high frequency power transformers used for DC/DC converters in a three phase photo voltaic (PV) power systems. The winding structure including a Faraday shield between the primary and secondary windings is designed to minimize eddy current losses, skin and proximity effects, and to reduce the leakage inductance, and the inter winding coupling capacitance. Finite Element Method is employed to analyze the magnetic flux and eddy current distributions. The two different kinds of prototype high frequency transformers are designed and tested. The simulation and experiment results are demonstrated and compared with non-shielded transformers. The shielded transformers have achieved the expected results with a relatively small coupling capacitance, compared with the conventional high frequency transformer. This shield decreases the inter-winding coupling capacitance Cps. The topology of this shield has to be such that it acts as a Faraday screen while avoiding eddy current generation.
文摘Symmetrical monopolar configuration is the prevailing scheme configuration for modular multilevel converter based high-voltage direct current(MMC-HVDC) links, in which severe DC overvoltage or overcurrent can be caused by the DC faults. To deal with the possible asymmetry in the DC faults and the coupling effects of the DC lines, this paper analyzes the DC fault characteristics based on the phase-mode transformation. First, the DC grid is decomposed into the common-mode and the differential-mode networks. The equivalent models of the MMCs and DC lines in the two networks are derived, respectively. Then, based on the state matrices, a unified numerical calculation method for the fault voltages and currents at the DC side is proposed. Compared with the time-domain simulations performed on PSCAD/EMTDC, the accuracy of the proposed method is validated. Last, the system parameter analysis shows that the grounding parameters play an important role in reducing the severity of the pole-to-ground faults, whereas the coupling effects of the DC lines should be considered when calculating the DC fault currents associated with the pole-to-pole faults.
文摘Practically,the load currents in three phases are asymmetric in the power system.It means that the impedances are different in all three phases.If the consumer’s transformer neutral cut off and/or was disconnected from the neutral of power supply source,then there will be some trouble and failure occurred.The current in the neutral wire drops down to zero when the neutral wire is cut off and the phase currents of all three-phase equal to each other since there was no return wire.The currents are equal but the voltages at the phase consumers are different.Especially for residential single-phase consumers,the voltage at the consumers of the phase varies differently for three phase systems when the neutral wire was disconnected at consumer side and even the voltage at the consumers one or two of those three phases becomes over nominal voltage or reaches nearly line voltage.In this case,the electronic appliances in that phase will be fed by high voltage than the rated value and they can be broken down.In the power system of UB(Ulaanbaatar)city,there are some occasional such kind of failures every year.Obviously,many electronic appliances were broken down due to high voltage and the electricity utility companies respond for service charge of damaged parts.
文摘随着基于电压源型换流器的柔性直流输电(voltage source converter based high voltage direct current,VSC-HVDC)技术的快速发展,十几年间世界范围内已建成数十个各种不同电压等级的VSC-HVDC工程。根据交流电网的发展历史,未来构建大规模直流电网是必然趋势。然而直流电网必须采用DC/DC变换器来充当直流变压器的角色,因此高效率、低成本的高压大容量DC/DC变换器是直流电网技术中亟待攻克的关键基础性课题。该文针对不同电压等级直流输电线路互联的技术需求,对经典低压DC/DC拓扑进行改造,推演出一系列基于容性能量转移原理的高压大容量DC/DC变换器拓扑,并揭示此类拓扑的演化规律和换流原理。相比传统变换器方案,该拓扑可降低器件数量,提升拓扑转换效率以及减小变换器体积重量。最后,通过仿真和实验验证基于容性能量转移原理的DC/DC变换器的可行性。
文摘直流电流互感器(direct-current current transformers,DCCT)是高压直流输电系统中的重要测量设备。为保证其准确可靠,DCCT投运前和停电维护时需现场校准。对于电子式DCCT现场抗干扰及数字化同步两大关键问题,该文提出电子式DCCT的校准方法并设计一套校准系统,主要包括直流电流源、作为标准器的磁调制式直流电流比较仪(DC current comparator,DCC)和具有光纤数字同步的电子式DCCT校验仪。重点对标准器和校验仪进行了现场抗干扰分析,对于标准器现场使用时可能遇到的母线偏心和邻近通流导体干扰情况进行仿真分析,优化磁屏蔽结构,研制了DCC样机,经中国计量科学研究院校准,该DCC不确定度为5×10-6,在此基础上进行了母线偏心和邻近导体影响测试,验证了优化的屏蔽结构能够有效抵御现场干扰;为检验校准系统,采用0.2级DCCT进行了校准测试,结果表明校准系统不确定度优于5×10-4。