When fault occurs on cross-coupling autotransformer(AT)power supply traction network,the up-line and down-line feeder circuit breakers in the traction substation trip at the same time without selectivity,which leads t...When fault occurs on cross-coupling autotransformer(AT)power supply traction network,the up-line and down-line feeder circuit breakers in the traction substation trip at the same time without selectivity,which leads to an extended power failure.Based on equivalent circuit and Kirchhoff’s current law,the feeder current characteristic in the substation,AT station and sectioning post when T-R fault,F-R fault,and T-F fault occur are analyzed and their expressions are obtained.When the traction power supply system is equipped with wide-area protection measurement and control system,the feeder protection device in each station collects the feeder currents in other two stations through the wide-area protection channel and a wide-area current differential protection scheme based on the feeder current characteristic is proposed.When a short-circuit fault occurs in the power supply arm,all the feeder protection devices in each station receive the feeder currents with time stamp in other two stations.After data synchronous processing and logic judgment,the fault line of the power supply arm can be identified and isolated quickly.The simulation result based on MATLAB/Simulink shows that the power supply arm protection scheme based on wide-area current differential has good fault discrimination ability under different fault positions,transition resistances,and fault types.The verification of measured data shows that the novel protection scheme will not be affected by the special working conditions of the electrical multiple unit(EMU),and reliability,selectivity,and rapidity of relay protection are all improved.展开更多
There are two phases in the development of China's high-speed railway after the1990s:the research and experiment phase during the Eighth and the Tenth Five-Year Plan periods;the construction and operation phase du...There are two phases in the development of China's high-speed railway after the1990s:the research and experiment phase during the Eighth and the Tenth Five-Year Plan periods;the construction and operation phase during the Eleventh and the Thirteenth Five-Year Plan periods.This paper regards the Beijing-Shanghai High-Speed Railway as the corner stone in the development of high-speed railway subgrade system,and proposes suggestions and solutions to the problems which may reduce the service life of subgrade.These solutions and methods can be referred to in future railway projects.展开更多
With the rapid development of the construction of high-speed railway in china, higher levels of power quality and reliability of traction power supply systems are required.The combination of bilateral power supply tec...With the rapid development of the construction of high-speed railway in china, higher levels of power quality and reliability of traction power supply systems are required.The combination of bilateral power supply technology with AT traction power supply technology can better meet the needs of development of high-speed railways, which will require new protection approaches to be proposed. Thus, corresponding protection schemes will be of great significance for the application and promotion of bilateral power supply technology.展开更多
基金supported by the Natural Science Foundation of Sichuan Province(No.2022NSFSC0405).
文摘When fault occurs on cross-coupling autotransformer(AT)power supply traction network,the up-line and down-line feeder circuit breakers in the traction substation trip at the same time without selectivity,which leads to an extended power failure.Based on equivalent circuit and Kirchhoff’s current law,the feeder current characteristic in the substation,AT station and sectioning post when T-R fault,F-R fault,and T-F fault occur are analyzed and their expressions are obtained.When the traction power supply system is equipped with wide-area protection measurement and control system,the feeder protection device in each station collects the feeder currents in other two stations through the wide-area protection channel and a wide-area current differential protection scheme based on the feeder current characteristic is proposed.When a short-circuit fault occurs in the power supply arm,all the feeder protection devices in each station receive the feeder currents with time stamp in other two stations.After data synchronous processing and logic judgment,the fault line of the power supply arm can be identified and isolated quickly.The simulation result based on MATLAB/Simulink shows that the power supply arm protection scheme based on wide-area current differential has good fault discrimination ability under different fault positions,transition resistances,and fault types.The verification of measured data shows that the novel protection scheme will not be affected by the special working conditions of the electrical multiple unit(EMU),and reliability,selectivity,and rapidity of relay protection are all improved.
文摘There are two phases in the development of China's high-speed railway after the1990s:the research and experiment phase during the Eighth and the Tenth Five-Year Plan periods;the construction and operation phase during the Eleventh and the Thirteenth Five-Year Plan periods.This paper regards the Beijing-Shanghai High-Speed Railway as the corner stone in the development of high-speed railway subgrade system,and proposes suggestions and solutions to the problems which may reduce the service life of subgrade.These solutions and methods can be referred to in future railway projects.
文摘With the rapid development of the construction of high-speed railway in china, higher levels of power quality and reliability of traction power supply systems are required.The combination of bilateral power supply technology with AT traction power supply technology can better meet the needs of development of high-speed railways, which will require new protection approaches to be proposed. Thus, corresponding protection schemes will be of great significance for the application and promotion of bilateral power supply technology.