The accurate identification of the oil-paper insulation state of a transformer is crucial for most maintenance strategies.This paper presents a multi-feature comprehensive evaluation model based on combination weighti...The accurate identification of the oil-paper insulation state of a transformer is crucial for most maintenance strategies.This paper presents a multi-feature comprehensive evaluation model based on combination weighting and an improved technique for order of preference by similarity to ideal solution(TOPSIS)method to perform an objective and scientific evaluation of the transformer oil-paper insulation state.Firstly,multiple aging features are extracted from the recovery voltage polarization spectrum and the extended Debye equivalent circuit owing to the limitations of using a single feature for evaluation.A standard evaluation index system is then established by using the collected time-domain dielectric spectrum data.Secondly,this study implements the per-unit value concept to integrate the dimension of the index matrix and calculates the objective weight by using the random forest algorithm.Furthermore,it combines the weighting model to overcome the drawbacks of the single weighting method by using the indicators and considering the subjective experience of experts and the random forest algorithm.Lastly,the enhanced TOPSIS approach is used to determine the insulation quality of an oil-paper transformer.A verification example demonstrates that the evaluation model developed in this study can efficiently and accurately diagnose the insulation status of transformers.Essentially,this study presents a novel approach for the assessment of transformer oil-paper insulation.展开更多
Amidst the swift advancement of new power systems and electric vehicles,inverter-fed machines have progressively materialized as a pivotal apparatus for efficient energy conversion.Stator winding turn insulation failu...Amidst the swift advancement of new power systems and electric vehicles,inverter-fed machines have progressively materialized as a pivotal apparatus for efficient energy conversion.Stator winding turn insulation failure is the root cause of inverter-fed machine breakdown.The online monitoring of turn insulation health can detect potential safety risks promptly,but faces the challenge of weak characteristics of turn insulation degradation.This study proposes an innovative method to evaluate the turn insulation state of inverter-fed machines by utilizing the fractional Fourier transform with a Mel filter(FrFT-Mel).First,the sensitivity of the high-frequency(HF)switching oscillation current to variations in turn insulation was analyzed within the fractional domain.Subsequently,an improved Mel filter is introduced,and its structure and parameters are specifically designed based on the features intrinsic to the common-mode impedance resonance point of the electrical machine.Finally,an evaluation index was proposed for the turn insulation state of inverter-fed machines.Experimental results on a 3kW permanent magnet synchronous machine(PMSM)demonstrate that the proposed FrFT-Mel method significantly enhances the sensitivity of turn insulation state perception by approximately five times,compared to the traditional Fourier transform method.展开更多
The paper provides a general overview of chemical processes leading to the degradation of oil-paper insulation in oil-immersed electrical current transformers. Previous knowledge available in literature is complemente...The paper provides a general overview of chemical processes leading to the degradation of oil-paper insulation in oil-immersed electrical current transformers. Previous knowledge available in literature is complemented by new results placing a specific emphasis on the physicochemical factors which affect the copper release in the insulation oil and the oil oxidation kinetics. It is demonstrated that various ageing processes interact with each other, with one or another process dominating under specific conditions. Comprehensive but disjoint studies focusing on separate sub-processes may produce rather misleading results, and occasionally, lie behind rather irrelevant quality demands imposed on the insulating liquids.展开更多
The valve side windings of converter transformers bear AC, DC, impulse, and reversal-polarity voltages during operation, which could result in serious insulation problems of the equipment. By performing experiments wi...The valve side windings of converter transformers bear AC, DC, impulse, and reversal-polarity voltages during operation, which could result in serious insulation problems of the equipment. By performing experiments with surface discharge model of oil-paper insula- tion at 80 ℃ under combined AC-DC voltage for 200 h, we studied the spectrums and statistical parameters of partial discharges at different discharge stages. Furthermore, some fingerprint parameters were calculated in order to estimate the development situation of par- tial discharge, while the characteristic gases dissolved in the transformer oil were measured by gas chromatography. The surface discharges in the experiments were observed using a high speed camera, and a full discharge process could be marked off into four stages as follows. ①The elementary stage. When a partial discharge occurs near electrodes, electrical charges are injected into the region near electrodes and causing bubble generation. ②Due to their high resistivity and low dielectric constant, the bubbles would bare the major part of the voltage applied to samples. Therefore, discharge happens inside the small bubbles, and it emits a lot of light. ③Micromolecules of gas are produced in discharge, and further ionization in the transformer oil takes place simultaneously when high-energy electrons collide with oil molecules. ④The carrier charge moves forward to electrodes driven by the applied electric field, till they neutralize with the charge from electrodes, and hence discharge channels are formed subsequently.展开更多
The chaotic characteristics of time series of five partial discharge (PD) patterns in oil-paper insulation are studied. The results verify obvious chaotic characteristic of the time series of discharge signals and t...The chaotic characteristics of time series of five partial discharge (PD) patterns in oil-paper insulation are studied. The results verify obvious chaotic characteristic of the time series of discharge signals and the fact that PD is a chaotic process. These time series have distinctive features, and the chaotic attractors obtained from time series differed greatly from each other by shapes in the phase space, so they could be used to qualitatively identify the PD patterns. The phase space parameters are selected, then the chaotic characteristic quantities can be extracted. These quantities could quantificationally characterize the PD patterns. The effects on pattern recognition of PRPD and CAPD are compared by using the neural network of radial basis function. The results show that both of the two recognition methods work well and have their respective advantages. Then, both the statistical operators under PRPD mode and the chaotic characteristic quantities under CAPD mode are selected comprehensively as the input vectors of neural network, and the PD pattern recognition accuracy is thereby greatly improved.展开更多
In order to study the linkage effects between degree of polymerization and frequency domain dielectric spectroscopy characteristics of oil-paper insulation, the frequency domain dielectric response test platform of oi...In order to study the linkage effects between degree of polymerization and frequency domain dielectric spectroscopy characteristics of oil-paper insulation, the frequency domain dielectric response test platform of oil-paper insulation is set up. Complex permittivity of oil-paper insulation respectively composed by new or aged oil and insulation paper with different DP are tested, and complex permittivity of oil-paper insulation respectively composed by insulation respectively composed by new oil and insulation paper with different DP and low or high moisture content are tested. The test results are analyzed, and the analysis results show that the degree of polymerization of insulation paper has an influence on complex permittivity of oil-paper insulation though influencing the distribution of moisture and acids between oil and paper.展开更多
This paper deals with experimental investigations of the electrical and physical properties of oil impregnated insulation paper for power transformers at different temperatures. The ac breakdown voltage, tensile stren...This paper deals with experimental investigations of the electrical and physical properties of oil impregnated insulation paper for power transformers at different temperatures. The ac breakdown voltage, tensile strength and water content of insulation papers impregnated in mineral oil for different time periods were investigated. The effect of insulation paper thickness on the electrical and mechanical properties has also been studied. The results showed that the breakdown voltage and the tensile strength decreased with increasing the time of immersion of insulation paper in oil at room temperature, at 5℃ and at -12℃. Also, the thermal aging effect on the characteristic of insulation paper has been studied. It was found that high temperatures affect the breakdown voltage and the tensile strength to a great extent.展开更多
In view of long-term transformer insulation resistance and dielectric loss measurement, measurement and according to the national standard formula conversion values are not completely consistent, in this paper, a vari...In view of long-term transformer insulation resistance and dielectric loss measurement, measurement and according to the national standard formula conversion values are not completely consistent, in this paper, a variety of transformers are studied, and the applicable scope of the conversion formula is discussed emphatically, combined with the test results are analyzed of transformer insulation resistance value to temperature and oiliness and dielectric loss tangent to temperature and oiliness, and puts forward suggestions on how to improve the insulation performance of transformer.展开更多
Low-cost thermal insulation porous ceramics with uniform pore diameter and low bulk density were prepared with soda-ash dregs and felsic tailings.We investigated the effect of temperature,foaming agent,fluxing agent,A...Low-cost thermal insulation porous ceramics with uniform pore diameter and low bulk density were prepared with soda-ash dregs and felsic tailings.We investigated the effect of temperature,foaming agent,fluxing agent,Al_(2)O_(3)and CaO content on the pore structure and crystal phase of porous ceramics.The effect of Ca^(2+)in soda-ash dregs on the preparation of quartz-feldspar based porous ceramics was studied.The results showed that the contribution of Ca^(2+)to the preparation of porous ceramics in this system was mainly to accelerate the Si-O bond fracture and reduce the sintering temperature at the initial stage of sintering,which destroyed the needle-like feldspar in the high temperature melt and reduced the melt viscosity,thus reduced the foaming resistance and promoted the porous products with uniform pore size distribution.The Ca^(2+)content on the high side can participate in the formation of crystals in sintering.The generated needle-like diopside and augite,which have small length-diameter ratio,will negligibly change in the viscosity of melt at high temperatures,and their inhibition effect on pores is not as good as that of feldspar with large length-diameter ratio,resulting in the merger and collapse of pores.But the increase of diopside and augite can improve the compressive strength of porous products to some extent.Porous ceramic products containing needle-like feldspar phase can be prepared by using two kinds of solid waste,which can improve the compressive strength of the products and reduce the raw material cost and energy consumption while comprehensively utilizing the double solid waste.The optimal product has a bulk density of 0.45 g/cm^(3),a compressive strength of 3.17 MPa,and a thermal conductivity of 0.11 W/(m·K).展开更多
The present work aims to develop a new vegetable insulating fluid for power transformers based on Jatropha curcas oil. Besides its technical benefits, Jatropha curcas oil has a socio-economic role by promoting income ...The present work aims to develop a new vegetable insulating fluid for power transformers based on Jatropha curcas oil. Besides its technical benefits, Jatropha curcas oil has a socio-economic role by promoting income to rural families, contributing to the countryside development and avoiding rural exodus. Thus, the entire transformer oil production (extraction, processing, characterization and accelerated aging) was covered and a new process was developed. For oil extraction, the most suitable process was the solvent extraction (5 mL of hexane per gram of crushed non-peeled seeds during 30 minutes) with an oil yield of 32%. In raw oil processing stage, the degumming, with 0.4 g of phosphoric acid per 100 g of oil, at 70°C, was used to remove phosphatides. Then, free fatty acids were 96% neutralized with a sodium hydroxide solution (0.5% w/w) at room temperature. For the oil clarification, the combination of 5% w/woil of activated carbon and 1% w/woil of MgO resulted in a bright, odorless and clear oil with an acid number of 0.04 mgKOH·g﹣1. The oil drying in a vacuum rotary evaporator, at 70°C, for 2 hours reduced the water content to 177 ppm. The processed oil was characterized following ASTM D6871 methods. This oil presented higher dielectric breakdown voltage (55 kV) than commercial transformer fluids (BIOTEMP?, EnvirotempFR3?, and Bivolt?), which increases transformer safety, capacity and lifetime. In addition, the processed oil has a lower viscosity than BIOTEMP? fluid, which can enhance the heat dissipation efficiency in the transformer. Moreover, the processed oil flash and fire points of 310°C and >340°C, respectively, confirm the great security of vegetable insulating fluids. The analyzed properties of the processed oil fulfill all the ASTM D6871, ABNT NBR 15422 and IEC 62770 specifications. Therefore, Jatropha curcas oil is a potential substitute formineral insulating fluids.展开更多
To improve the accuracy and efficiency of the aging life prediction and assessment of transformer oil-paper insulation,and to make up for the deficiencies of traditional characterizers,such as 2-furfural,carbon monoxi...To improve the accuracy and efficiency of the aging life prediction and assessment of transformer oil-paper insulation,and to make up for the deficiencies of traditional characterizers,such as 2-furfural,carbon monoxide,and carbon dioxide,a method for the simultaneous determination of methanol,ethanol,n−propanol,and η-butanol in oil with a single injection is established by headspace-gas chromatography-mass spectrometry.The measured results show that the determination limits of the four alcohol characterizers can be controlled to 10μg/kg level.Based on this method,the change patterns of the above four alcohols with thermal aging time and degree of polymerization are obtained through thermal aging experimental research.Ethanol,η-propanol,and η-butanol in oil indicate nearly linear correlations with thermal aging time and degree of polymerization,similar to that of methanol.By analyzing 52 sets of measured data of 500 kV EHV transformers in operation,η-butanol is found to have excellent performance,and a new method to evaluate the aging state of oil-paper insulation employing η-butanol and methanol is proposed along with the aging attention value model.The measured data of 500 kV EHV transformers in operation indicate that the combination of η-butanol and methanol as the preferred characterizers can effectively compensate for the shortcoming of traditional characterizers in the early stages of aging,and the feasibility of the method is verified.Two possible pathways for the generation of η-butanol by cellulose cleavage during the aging of oil-paper are proposed from the chemical structure of cellulose.展开更多
Output voltage is an important performance characteristic of planar insulating core transformer (PICT).In PICT magnetic cores are insulated from their neighboring magnetic cores by solid insulating materials.Solid ins...Output voltage is an important performance characteristic of planar insulating core transformer (PICT).In PICT magnetic cores are insulated from their neighboring magnetic cores by solid insulating materials.Solid insulating materials can increase leakage flux.This results in a low generated voltage in secondary coils,especially on the upper stages.Connecting flux compensation capacitors to secondary coils can compensate the flux loss.Design equations to calculate the flux compensation capacitors value and relevant simulation by CST and Protel software were presented.Simulation results of an actual PICT showed that output voltage increased by 19% after being connected to flux compensation capacitors and the voltage on every stage was equally distributed.Results of simulation were consistent with the following experimental test,which revealed that flux compensation capacitors were effective.展开更多
The design of the insulated core transformer(ICT)needs to consider the flux leakage effects.An equivalent linear circuit model is proposed based on the principle of duality.It is composed by two types of leakage induc...The design of the insulated core transformer(ICT)needs to consider the flux leakage effects.An equivalent linear circuit model is proposed based on the principle of duality.It is composed by two types of leakage inductances:conventional leakage between windings and special leakage introduced mainly by the insulation gaps.The values of leakage inductances depend on the dimensions of the core,gaps,or windings and the property of magnetic materials.The circuit allows for quantitatively evaluating influences of ICT internal parameters on its output properties.The winding self- and mutual inductance matrix is mathematically converted to derive the inductance formula.As an example,the leakage parameters of a sixstage two-dimensional(2D) ICT are calculated and analyzed.展开更多
Looking at the problem of electrical discharge development in mineral oil, it is easy to see that most studies in this area focused on the setups of bare high voltage electrodes having a point-plane electrode arrangem...Looking at the problem of electrical discharge development in mineral oil, it is easy to see that most studies in this area focused on the setups of bare high voltage electrodes having a point-plane electrode arrangement. The setups with insulated electrodes are the mar- gin of these studies but it seems to be important to find the dependences between the paper insulation on high voltage electrode and parameters of the discharges initiated in the vicinity of this electrode. Hence, in this paper the results of researches intended to reveal the role of insulation wrapping on a HV electrode in the mechanism of electrical discharges in transformer oil under lightning impulse of both polar- ities are presented. This role is determined by analysis of the parameters characterizing the discharges (onset voltage, propagation velocity, time to initiation, rise-time of light impulses) and also by observation of their spatio-temporal development and oscillograms of the light emitted by their channels. The research was performed for two model electrode configurations: an electrode with paper insulation and a bare electrode which had the same outer dimensions as the insulated one. The most essential conclusion from performed experiment is related to times to initiation. These times, equal in the case of insulated electrodes and model bare electrode, indicate that the source of "weak points" of the paper-oil insulation system is the oil, not the surface of insulation wrapping or the metal.展开更多
A novel high-frequency and high power density planar insulated core transformer(PICT) applied to high voltage DC generator is introduced. PICT's operating principle and fundamental configuration are described,and ...A novel high-frequency and high power density planar insulated core transformer(PICT) applied to high voltage DC generator is introduced. PICT's operating principle and fundamental configuration are described,and preliminary experimental results in self-designed PICT apparatus are presented. Emphatically, magnetic leakage flux(MFL) giving rise to the output voltage drop is analyzed in detail both theoretically and by finite element method(FEM). Showing good consistency with experimental result, FEM simulation is considered to be practicable in physical design of PICT. To cancel out leakage inductance and improve the voltage uniformity,compensation capacitor is adopted and experimental verification is also presented. All shows satisfactory results.展开更多
It is well known that the hot spot temperature represents the most critical parameter identifying the power rating of a transformer. This paper investigates the effect of the degradation of core magnetic properties on...It is well known that the hot spot temperature represents the most critical parameter identifying the power rating of a transformer. This paper investigates the effect of the degradation of core magnetic properties on temperature variation of aged oil-cooled transformers. Within this work, 2D accurate assessment of time average flux density distribution in an oil insulated-cooled 25 MVA transformer has been computed using finite-element analysis taking into account ageing and stress-induced non-uniform core permeability values. Knowing the core material specific loss and winding details, local core and winding losses are converted into heat. Based upon the ambient temperature outside the transformer tank and thermal heat transfer related factors, the detailed thermal modeling and analysis have then been carried out to determine temperature distribution everywhere. Analytical details and simulation results demonstrating effects of core magnetic properties degradation on hot spot temperatures of the transformer’s components are given in the paper.展开更多
基金supported by the Natural Science Foundation of the Fujian Province(2021J01109).
文摘The accurate identification of the oil-paper insulation state of a transformer is crucial for most maintenance strategies.This paper presents a multi-feature comprehensive evaluation model based on combination weighting and an improved technique for order of preference by similarity to ideal solution(TOPSIS)method to perform an objective and scientific evaluation of the transformer oil-paper insulation state.Firstly,multiple aging features are extracted from the recovery voltage polarization spectrum and the extended Debye equivalent circuit owing to the limitations of using a single feature for evaluation.A standard evaluation index system is then established by using the collected time-domain dielectric spectrum data.Secondly,this study implements the per-unit value concept to integrate the dimension of the index matrix and calculates the objective weight by using the random forest algorithm.Furthermore,it combines the weighting model to overcome the drawbacks of the single weighting method by using the indicators and considering the subjective experience of experts and the random forest algorithm.Lastly,the enhanced TOPSIS approach is used to determine the insulation quality of an oil-paper transformer.A verification example demonstrates that the evaluation model developed in this study can efficiently and accurately diagnose the insulation status of transformers.Essentially,this study presents a novel approach for the assessment of transformer oil-paper insulation.
基金supported in part by the National Natural Science Foundation of China under Grant 51907116in part sponsored by Natural Science Foundation of Shanghai 22ZR1425400sponsored by Shanghai Rising-Star Program 23QA1404000.
文摘Amidst the swift advancement of new power systems and electric vehicles,inverter-fed machines have progressively materialized as a pivotal apparatus for efficient energy conversion.Stator winding turn insulation failure is the root cause of inverter-fed machine breakdown.The online monitoring of turn insulation health can detect potential safety risks promptly,but faces the challenge of weak characteristics of turn insulation degradation.This study proposes an innovative method to evaluate the turn insulation state of inverter-fed machines by utilizing the fractional Fourier transform with a Mel filter(FrFT-Mel).First,the sensitivity of the high-frequency(HF)switching oscillation current to variations in turn insulation was analyzed within the fractional domain.Subsequently,an improved Mel filter is introduced,and its structure and parameters are specifically designed based on the features intrinsic to the common-mode impedance resonance point of the electrical machine.Finally,an evaluation index was proposed for the turn insulation state of inverter-fed machines.Experimental results on a 3kW permanent magnet synchronous machine(PMSM)demonstrate that the proposed FrFT-Mel method significantly enhances the sensitivity of turn insulation state perception by approximately five times,compared to the traditional Fourier transform method.
文摘The paper provides a general overview of chemical processes leading to the degradation of oil-paper insulation in oil-immersed electrical current transformers. Previous knowledge available in literature is complemented by new results placing a specific emphasis on the physicochemical factors which affect the copper release in the insulation oil and the oil oxidation kinetics. It is demonstrated that various ageing processes interact with each other, with one or another process dominating under specific conditions. Comprehensive but disjoint studies focusing on separate sub-processes may produce rather misleading results, and occasionally, lie behind rather irrelevant quality demands imposed on the insulating liquids.
基金supported by National High-tech Research and Development Program of China(863 Program)(2009AA04Z416) National Science Foundation of China(51021005) Scientific Innovation of Colleges and Universities(Project v-200704)
基金Project supported by National Basic Research Program of China(973 Program) (2011CB 209400)Program of State Key Laboratory of Power Systems for ±1 100 kV UHVDC Technology(SKLD10M09)
文摘The valve side windings of converter transformers bear AC, DC, impulse, and reversal-polarity voltages during operation, which could result in serious insulation problems of the equipment. By performing experiments with surface discharge model of oil-paper insula- tion at 80 ℃ under combined AC-DC voltage for 200 h, we studied the spectrums and statistical parameters of partial discharges at different discharge stages. Furthermore, some fingerprint parameters were calculated in order to estimate the development situation of par- tial discharge, while the characteristic gases dissolved in the transformer oil were measured by gas chromatography. The surface discharges in the experiments were observed using a high speed camera, and a full discharge process could be marked off into four stages as follows. ①The elementary stage. When a partial discharge occurs near electrodes, electrical charges are injected into the region near electrodes and causing bubble generation. ②Due to their high resistivity and low dielectric constant, the bubbles would bare the major part of the voltage applied to samples. Therefore, discharge happens inside the small bubbles, and it emits a lot of light. ③Micromolecules of gas are produced in discharge, and further ionization in the transformer oil takes place simultaneously when high-energy electrons collide with oil molecules. ④The carrier charge moves forward to electrodes driven by the applied electric field, till they neutralize with the charge from electrodes, and hence discharge channels are formed subsequently.
基金supported by National Natural Science Foundation of China(No.50877064)
文摘The chaotic characteristics of time series of five partial discharge (PD) patterns in oil-paper insulation are studied. The results verify obvious chaotic characteristic of the time series of discharge signals and the fact that PD is a chaotic process. These time series have distinctive features, and the chaotic attractors obtained from time series differed greatly from each other by shapes in the phase space, so they could be used to qualitatively identify the PD patterns. The phase space parameters are selected, then the chaotic characteristic quantities can be extracted. These quantities could quantificationally characterize the PD patterns. The effects on pattern recognition of PRPD and CAPD are compared by using the neural network of radial basis function. The results show that both of the two recognition methods work well and have their respective advantages. Then, both the statistical operators under PRPD mode and the chaotic characteristic quantities under CAPD mode are selected comprehensively as the input vectors of neural network, and the PD pattern recognition accuracy is thereby greatly improved.
基金supported by National High-tech Research and Development Program of China(863 Program)(2009AA04Z416) National Science Foundation of China(51021005) Scientific Innovation of Colleges and Universities(200704)
文摘In order to study the linkage effects between degree of polymerization and frequency domain dielectric spectroscopy characteristics of oil-paper insulation, the frequency domain dielectric response test platform of oil-paper insulation is set up. Complex permittivity of oil-paper insulation respectively composed by new or aged oil and insulation paper with different DP are tested, and complex permittivity of oil-paper insulation respectively composed by insulation respectively composed by new oil and insulation paper with different DP and low or high moisture content are tested. The test results are analyzed, and the analysis results show that the degree of polymerization of insulation paper has an influence on complex permittivity of oil-paper insulation though influencing the distribution of moisture and acids between oil and paper.
文摘This paper deals with experimental investigations of the electrical and physical properties of oil impregnated insulation paper for power transformers at different temperatures. The ac breakdown voltage, tensile strength and water content of insulation papers impregnated in mineral oil for different time periods were investigated. The effect of insulation paper thickness on the electrical and mechanical properties has also been studied. The results showed that the breakdown voltage and the tensile strength decreased with increasing the time of immersion of insulation paper in oil at room temperature, at 5℃ and at -12℃. Also, the thermal aging effect on the characteristic of insulation paper has been studied. It was found that high temperatures affect the breakdown voltage and the tensile strength to a great extent.
文摘In view of long-term transformer insulation resistance and dielectric loss measurement, measurement and according to the national standard formula conversion values are not completely consistent, in this paper, a variety of transformers are studied, and the applicable scope of the conversion formula is discussed emphatically, combined with the test results are analyzed of transformer insulation resistance value to temperature and oiliness and dielectric loss tangent to temperature and oiliness, and puts forward suggestions on how to improve the insulation performance of transformer.
基金Supported by the National Natural Science Foundation of China(No.51674161)Major Basic Research Projects of Shandong Province Natural Science Foundation(No.ZR2017ZC0735)+1 种基金Open Topic of Key Laboratory of Gold Mineralization Processes and Resource Utilization Subordinated to the Ministry of Land and Resources and Key Laboratory of Metallogenic Geological Process and Resources Utilization in Shandong Province(No.Kfkt201812)Research on Precious Metal Mineral Achievement Integration and Tailings Comprehensive Utilization in Shandong Province(Shandong Geological Exploration Document:[2018]No.10)。
文摘Low-cost thermal insulation porous ceramics with uniform pore diameter and low bulk density were prepared with soda-ash dregs and felsic tailings.We investigated the effect of temperature,foaming agent,fluxing agent,Al_(2)O_(3)and CaO content on the pore structure and crystal phase of porous ceramics.The effect of Ca^(2+)in soda-ash dregs on the preparation of quartz-feldspar based porous ceramics was studied.The results showed that the contribution of Ca^(2+)to the preparation of porous ceramics in this system was mainly to accelerate the Si-O bond fracture and reduce the sintering temperature at the initial stage of sintering,which destroyed the needle-like feldspar in the high temperature melt and reduced the melt viscosity,thus reduced the foaming resistance and promoted the porous products with uniform pore size distribution.The Ca^(2+)content on the high side can participate in the formation of crystals in sintering.The generated needle-like diopside and augite,which have small length-diameter ratio,will negligibly change in the viscosity of melt at high temperatures,and their inhibition effect on pores is not as good as that of feldspar with large length-diameter ratio,resulting in the merger and collapse of pores.But the increase of diopside and augite can improve the compressive strength of porous products to some extent.Porous ceramic products containing needle-like feldspar phase can be prepared by using two kinds of solid waste,which can improve the compressive strength of the products and reduce the raw material cost and energy consumption while comprehensively utilizing the double solid waste.The optimal product has a bulk density of 0.45 g/cm^(3),a compressive strength of 3.17 MPa,and a thermal conductivity of 0.11 W/(m·K).
文摘The present work aims to develop a new vegetable insulating fluid for power transformers based on Jatropha curcas oil. Besides its technical benefits, Jatropha curcas oil has a socio-economic role by promoting income to rural families, contributing to the countryside development and avoiding rural exodus. Thus, the entire transformer oil production (extraction, processing, characterization and accelerated aging) was covered and a new process was developed. For oil extraction, the most suitable process was the solvent extraction (5 mL of hexane per gram of crushed non-peeled seeds during 30 minutes) with an oil yield of 32%. In raw oil processing stage, the degumming, with 0.4 g of phosphoric acid per 100 g of oil, at 70°C, was used to remove phosphatides. Then, free fatty acids were 96% neutralized with a sodium hydroxide solution (0.5% w/w) at room temperature. For the oil clarification, the combination of 5% w/woil of activated carbon and 1% w/woil of MgO resulted in a bright, odorless and clear oil with an acid number of 0.04 mgKOH·g﹣1. The oil drying in a vacuum rotary evaporator, at 70°C, for 2 hours reduced the water content to 177 ppm. The processed oil was characterized following ASTM D6871 methods. This oil presented higher dielectric breakdown voltage (55 kV) than commercial transformer fluids (BIOTEMP?, EnvirotempFR3?, and Bivolt?), which increases transformer safety, capacity and lifetime. In addition, the processed oil has a lower viscosity than BIOTEMP? fluid, which can enhance the heat dissipation efficiency in the transformer. Moreover, the processed oil flash and fire points of 310°C and >340°C, respectively, confirm the great security of vegetable insulating fluids. The analyzed properties of the processed oil fulfill all the ASTM D6871, ABNT NBR 15422 and IEC 62770 specifications. Therefore, Jatropha curcas oil is a potential substitute formineral insulating fluids.
基金supported by Innovation Foundation of China Electric Power Research Institute(GY83-18-006).
文摘To improve the accuracy and efficiency of the aging life prediction and assessment of transformer oil-paper insulation,and to make up for the deficiencies of traditional characterizers,such as 2-furfural,carbon monoxide,and carbon dioxide,a method for the simultaneous determination of methanol,ethanol,n−propanol,and η-butanol in oil with a single injection is established by headspace-gas chromatography-mass spectrometry.The measured results show that the determination limits of the four alcohol characterizers can be controlled to 10μg/kg level.Based on this method,the change patterns of the above four alcohols with thermal aging time and degree of polymerization are obtained through thermal aging experimental research.Ethanol,η-propanol,and η-butanol in oil indicate nearly linear correlations with thermal aging time and degree of polymerization,similar to that of methanol.By analyzing 52 sets of measured data of 500 kV EHV transformers in operation,η-butanol is found to have excellent performance,and a new method to evaluate the aging state of oil-paper insulation employing η-butanol and methanol is proposed along with the aging attention value model.The measured data of 500 kV EHV transformers in operation indicate that the combination of η-butanol and methanol as the preferred characterizers can effectively compensate for the shortcoming of traditional characterizers in the early stages of aging,and the feasibility of the method is verified.Two possible pathways for the generation of η-butanol by cellulose cleavage during the aging of oil-paper are proposed from the chemical structure of cellulose.
文摘Output voltage is an important performance characteristic of planar insulating core transformer (PICT).In PICT magnetic cores are insulated from their neighboring magnetic cores by solid insulating materials.Solid insulating materials can increase leakage flux.This results in a low generated voltage in secondary coils,especially on the upper stages.Connecting flux compensation capacitors to secondary coils can compensate the flux loss.Design equations to calculate the flux compensation capacitors value and relevant simulation by CST and Protel software were presented.Simulation results of an actual PICT showed that output voltage increased by 19% after being connected to flux compensation capacitors and the voltage on every stage was equally distributed.Results of simulation were consistent with the following experimental test,which revealed that flux compensation capacitors were effective.
基金supported by National Natural Science Foundation of China(No.11305068)the‘‘2011 project’’organized by Hubei Collaboration Innovation Center of Non-power Nuclear Technology
文摘The design of the insulated core transformer(ICT)needs to consider the flux leakage effects.An equivalent linear circuit model is proposed based on the principle of duality.It is composed by two types of leakage inductances:conventional leakage between windings and special leakage introduced mainly by the insulation gaps.The values of leakage inductances depend on the dimensions of the core,gaps,or windings and the property of magnetic materials.The circuit allows for quantitatively evaluating influences of ICT internal parameters on its output properties.The winding self- and mutual inductance matrix is mathematically converted to derive the inductance formula.As an example,the leakage parameters of a sixstage two-dimensional(2D) ICT are calculated and analyzed.
文摘Looking at the problem of electrical discharge development in mineral oil, it is easy to see that most studies in this area focused on the setups of bare high voltage electrodes having a point-plane electrode arrangement. The setups with insulated electrodes are the mar- gin of these studies but it seems to be important to find the dependences between the paper insulation on high voltage electrode and parameters of the discharges initiated in the vicinity of this electrode. Hence, in this paper the results of researches intended to reveal the role of insulation wrapping on a HV electrode in the mechanism of electrical discharges in transformer oil under lightning impulse of both polar- ities are presented. This role is determined by analysis of the parameters characterizing the discharges (onset voltage, propagation velocity, time to initiation, rise-time of light impulses) and also by observation of their spatio-temporal development and oscillograms of the light emitted by their channels. The research was performed for two model electrode configurations: an electrode with paper insulation and a bare electrode which had the same outer dimensions as the insulated one. The most essential conclusion from performed experiment is related to times to initiation. These times, equal in the case of insulated electrodes and model bare electrode, indicate that the source of "weak points" of the paper-oil insulation system is the oil, not the surface of insulation wrapping or the metal.
基金Supported by the Science and Technology Commission of Shanghai Municipality under Grant No.12ZR1436500the Knowledge Innovation Programm of the Chinese Academy of Sciences
文摘A novel high-frequency and high power density planar insulated core transformer(PICT) applied to high voltage DC generator is introduced. PICT's operating principle and fundamental configuration are described,and preliminary experimental results in self-designed PICT apparatus are presented. Emphatically, magnetic leakage flux(MFL) giving rise to the output voltage drop is analyzed in detail both theoretically and by finite element method(FEM). Showing good consistency with experimental result, FEM simulation is considered to be practicable in physical design of PICT. To cancel out leakage inductance and improve the voltage uniformity,compensation capacitor is adopted and experimental verification is also presented. All shows satisfactory results.
文摘It is well known that the hot spot temperature represents the most critical parameter identifying the power rating of a transformer. This paper investigates the effect of the degradation of core magnetic properties on temperature variation of aged oil-cooled transformers. Within this work, 2D accurate assessment of time average flux density distribution in an oil insulated-cooled 25 MVA transformer has been computed using finite-element analysis taking into account ageing and stress-induced non-uniform core permeability values. Knowing the core material specific loss and winding details, local core and winding losses are converted into heat. Based upon the ambient temperature outside the transformer tank and thermal heat transfer related factors, the detailed thermal modeling and analysis have then been carried out to determine temperature distribution everywhere. Analytical details and simulation results demonstrating effects of core magnetic properties degradation on hot spot temperatures of the transformer’s components are given in the paper.