期刊文献+
共找到142篇文章
< 1 2 8 >
每页显示 20 50 100
Simulation of Arc Rotation and Its Effects on Pressure of Expansion Volume in an Auto-Expansion SF_6 Circuit Breaker 被引量:1
1
作者 张俊民 迟程缤 +2 位作者 关永刚 刘卫东 吴军辉 《Plasma Science and Technology》 SCIE EI CAS CSCD 2016年第3期287-291,共5页
A 3D Magnetohydrodynamics (MHD) arc model in conjunction with an arc move- ment model is applied to simulate the arc rotation as well as to solve its effect on the pressure in an auto-expansion circuit breaker. The ... A 3D Magnetohydrodynamics (MHD) arc model in conjunction with an arc move- ment model is applied to simulate the arc rotation as well as to solve its effect on the pressure in an auto-expansion circuit breaker. The rotation of the arc driven by an external electromagnetic force is simulated in the case with 200 kA of the short circuit current and 16 ms of arc duration. The arc rotating process and the speed of arc rotation have been obtained in the simulation. A comparison of the pressure in the expansion volume with and without an external magnetic field has been carried out based on the calculation results of two cases. The results of the simulation reveal that the arc rotation, which causes more energy exchange between the arc and its sur- rounding gas, can evidently bring about the pressurization in the expansion volume, which would contribute to more effective arc quenching at current zero and further reducing operation power. 展开更多
关键词 SF6 circuit breaker 3D arc model external magnetic field arc rotation
下载PDF
Simulation of the Process of Arc Energy-Effect in High Voltage Auto-Expansion SF_6 Circuit Breaker
2
作者 荣命哲 杨茜 范春朵 《Plasma Science and Technology》 SCIE EI CAS CSCD 2005年第6期3166-3169,共4页
A new magnetic hydro-dynamics (MHD) model of arc in H.V. auto-expansion SF6 circuit breaker that takes into consideration nozzle ablation due to both radiation and thermal conduction is presented in this paper. The ... A new magnetic hydro-dynamics (MHD) model of arc in H.V. auto-expansion SF6 circuit breaker that takes into consideration nozzle ablation due to both radiation and thermal conduction is presented in this paper. The effect of PTFE (polytetrafluorethylene) vapor is considered in the mass, momentum and energy conservation equations of the constructed model. Then, the gas flow fields with and without conduction considered are simulated. By comparing the aforementioned two results, it is indicated that the arc's maximal temperature with conduction considered is 90 percent of that without considering conduction. 展开更多
关键词 auto-expansion SF6 circuit breaker ARC SIMULATION conduction RADIATION
下载PDF
Integrated Experimental and Simulation Investigation of Breakdown Voltage Characteristics Across Electrode Configurations in SF_(6) Circuit Breakers
3
作者 Bo Guan Qi Yu +4 位作者 Qingpeng Yuan Shiwen Chen Lailin Chen Su Guo Peilong Zhu 《Journal of Electronic Research and Application》 2024年第4期133-142,共10页
This study investigates the breakdown voltage characteristics in sulfur hexafluoride(SF6)circuit breakers,employing a novel approach that integrates both experimental investigations and finite element simulations.Util... This study investigates the breakdown voltage characteristics in sulfur hexafluoride(SF6)circuit breakers,employing a novel approach that integrates both experimental investigations and finite element simulations.Utilizing a sphere-sphere electrode configuration,we meticulously measured the relationship between breakdown voltage and electrode gap distances ranging from 1 cm to 4.5 cm.Subsequent simulations,conducted using COMSOL Multiphysics,mirrored the experimental setup to validate the model’s accuracy through a comparison of the breakdown voltage-electrode gap distance curves.The simulation results not only aligned closely with the experimental data but also allowed the extraction of detailed electric field strength,electric potential contours,and electric current flow curves at the breakdown voltage for gap distances extending from 1 to 4.5 cm.Extending the analysis,the study explored the electric field and potential distribution at a constant voltage of 72.5 kV for gap distances between 1 to 10 cm,identifying the maximum electric field strength.A comprehensive comparison of five different electrode configurations(sphere-sphere,sphere-rod,sphere-plane,rod-plane,rod-rod)at 72.5 kV and a gap distance of 1.84 cm underscored the significant influence of electrode geometry on the breakdown process.Moreover,the research contrasts the breakdown voltage in SF6 with that in air,emphasizing SF6’s superior insulating properties.This investigation not only elucidates the intricate dynamics of electrical breakdown in SF6 circuit breakers but also contributes valuable insights into the optimal electrode configurations and the potential for alternative insulating gases,steering future advancements in high-voltage circuit breaker technology. 展开更多
关键词 SF6 circuit breaker Breakdown voltage Electrode configurations COMSOL simulation Electrical insulation
下载PDF
Analysis of Arc Characteristics and Flow Field in Arc Chamber of High-Voltage SF_6 Auto-Expansion Circuit Breaker 被引量:2
4
作者 张俊民 陈长 《Plasma Science and Technology》 SCIE EI CAS CSCD 2008年第5期594-599,共6页
A new magnetic hydro-dynamics model for nozzle arc emphasizing the interaction of arc with PTFE (polytetrafluorethylene) vapour is established based on the conservation equations. The interruption of auto-expansion ... A new magnetic hydro-dynamics model for nozzle arc emphasizing the interaction of arc with PTFE (polytetrafluorethylene) vapour is established based on the conservation equations. The interruption of auto-expansion circuit breaker is simulated numerically by finite element method and the influence of PTFE vapour on the arc is analysed with this model. The results reveal that the flow field inside the arc chamber is determined by the arc current, the arcing time, the nozzle arc and the clogging of its thermal boundary. The establishment of quenching pressure relies on both SF6 gas and PTFE vapour that absorbed arc energy in the nozzle. The PTFE vapour leads to an increase in the pressure of nozzle arc obviously, and a decrease in the temperature of arc. But it enhances the temperature of arc at zero current and slows down the decreasing rate of arc temperature as the current decreases. 展开更多
关键词 PTFE vapour arc characteristics SF6 auto-expansion circuit breaker numerical analysis nozzle ablation
下载PDF
Calculation of Steady SF_6 Gas Flow through a 420 kV Circuit Breaker Nozzle and Electric Field Distribution
5
作者 Dejan Beslija Sead Delic +2 位作者 Kyong-Hoe Kim Mirsad Kapetanovic Almir Ahmethodzic 《Journal of Energy and Power Engineering》 2014年第11期1964-1973,共10页
关键词 气体质量流量 断路器 电场 喷嘴 计算流体动力学 电流零点 计算结果 计算机仿真
下载PDF
Study on the Mathematical Model of Dielectric Recovery Characteristics in High Voltage SF6 Circuit Breaker 被引量:13
6
作者 林莘 王飞鸣 +2 位作者 徐建源 夏亚龙 刘卫东 《Plasma Science and Technology》 SCIE EI CAS CSCD 2016年第3期223-229,共7页
According to the stream theory, this paper proposes a mathematical model of the dielectric recovery characteristic based on the two-temperature ionization equilibrium equation. Taking the dynamic variation of charged ... According to the stream theory, this paper proposes a mathematical model of the dielectric recovery characteristic based on the two-temperature ionization equilibrium equation. Taking the dynamic variation of charged particle's ionization and attachment into account, this model can be used in collaboration with the Coulomb collision model, which gives the relationship of the heavy particle temperature and electron temperature to calculate the electron density and temperature under different pressure and electric field conditions, so as to deliver the breakdown electric field strength under different pressure conditions. Meanwhile an experiment loop of the circuit breaker has been built to measure the breakdown voltage. It is shown that calculated results are in conformity with experiment results on the whole while results based on the stream criterion are larger than experiment results. This indicates that the mathematical model proposed here is more accurate for calculating the dielectric recovery characteristic, it is derived from the stream model with some improvement and refinement and has great significance for increasing the simulation accuracy of circuit breaker's interruption characteristic. 展开更多
关键词 SF6 high voltage circuit breaker dielectric recovery characteristic the break-down voltage experiment of dynamic breakdown Saha ionization equilibrium
下载PDF
The Voltage Distribution Characteristics of a Hybrid Circuit Breaker During High Current Interruption 被引量:7
7
作者 程显 段雄英 +3 位作者 廖敏夫 黄智慧 罗彦 邹积岩 《Plasma Science and Technology》 SCIE EI CAS CSCD 2013年第8期800-806,共7页
Hybrid circuit breaker (HCB) technology based on a vacuum interrupter and a SF6 interrupter in series has become a new research direction because of the low-carbon requirements for high voltage switches. The vacuum ... Hybrid circuit breaker (HCB) technology based on a vacuum interrupter and a SF6 interrupter in series has become a new research direction because of the low-carbon requirements for high voltage switches. The vacuum interrupter has an excellent ability to deal with the steep rising part of the transient recovery voltage (TRV), while the SF6 interrupter can withstand the peak part of the voltage easily. An HCB can take advantage of the interrupters in the current interruption process. In this study, an HCB model based on the vacuum ion diffusion equations, ion density equation, and modified Cassie-Mayr arc equation is explored. A simulation platform is constructed by using a set of software called the alternative transient program (ATP). An HCB prototype is also designed, and the short circuit current is interrupted by the HCB under different action sequences of contacts. The voltage distribution of the HCB is analyzed through simulations and tests. The results demonstrate that if the vacuum interrupter withstands the initial TRV and interrupts the post-arc current first, then the recovery speed of the dielectric strength of the SF6 interrupter will be fast. The voltage distribution between two interrupters is determined by their post-arc resistance, which happens after current-zero, and subsequently, it is determined by the capacitive impedance after the post-arc current decays to zero. 展开更多
关键词 hybrid circuit breaker vacuum arc SF6 arc transient recovery voltage di- electric recovery breaking capacity
下载PDF
Coupling model of AC filter branch in SF6 circuit breaker during the break process
8
作者 彭在兴 刘凯 +4 位作者 南岩玮 王颂 杨飞 孙昊 喇元 《Plasma Science and Technology》 SCIE EI CAS CSCD 2020年第12期70-77,共8页
In this paper, a coupling model of the AC filter branch circuit with the arc plasma in the circuit breaker was built to investigate the arcing process considering the harmonic current. The comparisons among the curren... In this paper, a coupling model of the AC filter branch circuit with the arc plasma in the circuit breaker was built to investigate the arcing process considering the harmonic current. The comparisons among the current at power frequency(50 Hz), power frequency combining the 11 th harmonic and power frequency combining the 24 th harmonic show that the high-order harmonic current would lead to higher decreasing rate of current before current-zero period. In addition, the influence of arc on the amplitude of high-order harmonic current is not negligible. Thus, the coupling of arc with AC filter branch circuit is quite necessary in the numerical modeling of the circuit breaker in the AC filter branch at the high voltage direct current converter station. 展开更多
关键词 AC filter branch arc characteristics SF6 circuit breaker
下载PDF
SF_6断路器断口附近三维电场的边界元分析 被引量:4
9
作者 曹云东 刘志远 +1 位作者 王尔智 林莘 《高电压技术》 EI CAS CSCD 北大核心 1999年第1期75-77,共3页
运用边界元法对罐式SF6 断路器的三维电场进行了数值计算,在计算中对比较复杂的场域应用了分域处理技术,考虑了并联电容器组对电场分布的影响。
关键词 六氟化硫断路器 三维电场 边界元法 数值计算
下载PDF
SF_6断路器无载开断过程中气流特性的计算机模拟 被引量:4
10
作者 佟立柱 王其平 王尔智 《电工技术学报》 EI CSCD 北大核心 1996年第3期16-20,共5页
本文提出了一种用于进行跨音速问题分析的计算方法,即改进的FLIC(fluid-in-cell)法,并对SF6断路器触头开断过程中灭弧室内气流的流动特性进行了数值计算,给出了在触头开断过程中气流特性的分布情况,解决了S... 本文提出了一种用于进行跨音速问题分析的计算方法,即改进的FLIC(fluid-in-cell)法,并对SF6断路器触头开断过程中灭弧室内气流的流动特性进行了数值计算,给出了在触头开断过程中气流特性的分布情况,解决了SF6断路器灭弧室内具有大畸变的复杂流场的计算问题。 展开更多
关键词 六氟化硫断路器 开断过程 气流特性 计算机模拟
下载PDF
SF_6断路器灭弧室内电场的数值分析 被引量:8
11
作者 海涛 王其平 《高压电器》 CAS CSCD 北大核心 1993年第3期19-24,共6页
采用8节点等参元法,对SF_6断路器灭弧室内断口间的电场进行了详细的计算。在此基础上分别对喷口,最大开距,主触头结构,主、弧触头间结构的配合等参数的改变对断口间电场的影响,进行了讨论。整个计算软件具有通用性强,使用方便,易于处理... 采用8节点等参元法,对SF_6断路器灭弧室内断口间的电场进行了详细的计算。在此基础上分别对喷口,最大开距,主触头结构,主、弧触头间结构的配合等参数的改变对断口间电场的影响,进行了讨论。整个计算软件具有通用性强,使用方便,易于处理复杂边界,前处理简单,后处理形象、直观等优点。 展开更多
关键词 软件 数值计算 SF6断路器
下载PDF
自能式SF_6断路器在不同气压下的开断过程 被引量:2
12
作者 韩书谟 徐国政 +2 位作者 唐冬之 徐建源 林莘 《高压电器》 EI CAS CSCD 北大核心 1999年第6期12-16,共5页
对自能式SF_6断路器在不同气压下的开断过程进行了分析,得到了不同气压下操动机构的运动特性、膨胀室的状态参数、灭弧室内的气流场和电弧的动态特性.部分计算结果与试验值进行了比较,二者基本吻合.
关键词 六氟化硫断路器 灭弧室 开断过程 断路器
下载PDF
SF_6断路器操动机构的运行可靠性和选型探讨 被引量:31
13
作者 崔景春 袁大陆 杜彦明 《高压电器》 CAS CSCD 北大核心 2001年第2期1-4,共4页
本文统计了我国电力系统 1989~ 1997年间 110~5 0 0kVSF6断路器操动机构的故障 ,分析了影响操动机构运行可靠性的因素 ,介绍了SF6断路器开断原理和操动机构的演变和特点 ,提出了提高操动机构可靠性的途径及选用时应注意的问题。
关键词 六氟化硫断路器 操动机构 运行可靠性 选型
下载PDF
关于GIS和SF_6断路器的现场检测方法 被引量:23
14
作者 张丽娜 陈永义 梁桂州 《高压电器》 CAS CSCD 北大核心 2001年第3期47-48,共2页
本文介绍了GIS和SF6断路器的现场检测方法 ,包括机械振动法、检测管检测法和动态电阻检测法 ,分析了每一种检测方法的原理、适用设备。根据试验中发现的问题和经验 ,提出了抗干扰措施。
关键词 全封闭组合电器 GIS 六氟化硫断路器 现场检测
下载PDF
超高压SF_6断路器的智能操作 被引量:38
15
作者 马志瀛 陈晓宁 +1 位作者 徐黎明 苏方春 《中国电机工程学报》 EI CSCD 北大核心 1999年第7期11-13,71,共4页
提出了超高压断路器“智能操作”(即“动触头从一个位置到另一个位置的自适应控制的转换”)的新概念。这是断路器性能智能化的一个重要方面和可行途径。介绍了该智能操作断路器的工作原理。
关键词 六氟化硫断路器 智能操作 超高压 断路器
下载PDF
环境温度及湿度对SF_6断路器中微量水分的影响及控制措施 被引量:18
16
作者 陈新岗 陈渝光 +1 位作者 黄建国 钟连超 《高压电器》 CAS CSCD 北大核心 2004年第1期63-64,67,共3页
分析了环境温度及湿度对LW8-40.5型SF6断路器中微量水分的影响及造成该影响的主要原因,进而提出了控制和减小环境温度和湿度对SF6断路器中微量水分影响的措施。
关键词 六氟化硫断路器 微量水分 环境温度 环境湿度 LW8-40.5型 控制措施 电弧 绝缘性能
下载PDF
SF_6断路器电弧电流过零后介质强度恢复特性数值计算 被引量:2
17
作者 佟立柱 王尔智 王其平 《电机与控制学报》 EI CSCD 1997年第1期54-57,共4页
从实际 SF_6断路器灭弧室的基本结构出发,采用 FLIC 法计算了断路器在短路开断过程中灭弧室内热气流的流动特性。在计算中成功地加入了电弧模型,较好地模拟了电弧对气流的作用,对不同燃弧时间对气流特性的影响进行了计算分析,并应用流... 从实际 SF_6断路器灭弧室的基本结构出发,采用 FLIC 法计算了断路器在短路开断过程中灭弧室内热气流的流动特性。在计算中成功地加入了电弧模型,较好地模拟了电弧对气流的作用,对不同燃弧时间对气流特性的影响进行了计算分析,并应用流注理论获得了不同燃弧时间下的介质强度恢复特性。 展开更多
关键词 SF6断路器 灭弧室 电弧 数值计算
下载PDF
SF_(6)断路器触头劣化过程合闸预击穿特性研究
18
作者 马飞越 黎炜 +4 位作者 孙尚鹏 相中华 吴强 王尧平 王羽 《高压电器》 CAS CSCD 北大核心 2024年第4期113-122,共10页
电容器组投切断路器触头烧蚀劣化后会改变合闸预击穿时间,这不仅会影响选相合闸效果,同时也说明预击穿电弧持续时间可作为衡量触头烧蚀状态的指标之一。建立了126 kV SF_(6)断路器灭弧室内合闸预击穿过程电—流体耦合仿真模型,研究了触... 电容器组投切断路器触头烧蚀劣化后会改变合闸预击穿时间,这不仅会影响选相合闸效果,同时也说明预击穿电弧持续时间可作为衡量触头烧蚀状态的指标之一。建立了126 kV SF_(6)断路器灭弧室内合闸预击穿过程电—流体耦合仿真模型,研究了触头劣化过程中合闸预击穿特性,并提出了预击穿时间带电检测方法。结果表明:合闸过程中场强最大点总是出现在静弧触头表面;灭弧室内SF_(6)气体密度几乎保持不变;110 kV电压等级相电压下,触头预击穿电弧持续时间随烧蚀程度变化的试验值与仿真值吻合良好。从电场畸变角度解释了随着触头的表面烧蚀劣化程度增大对应预击穿时间的变化规律,结果可为断路器选相合闸策略和触头状态评估提供理论指导。 展开更多
关键词 SF_(6)断路器 预击穿特性 多物理场耦合仿真 选相合闸 触头状态评估
下载PDF
SF_6断路器灭弧室内二维气流场的数值分析 被引量:3
19
作者 海涛 王其平 《电工技术学报》 EI CSCD 北大核心 1995年第3期54-58,共5页
本文采用结合差分法与有限元法优点的Taylor-Galerkin有限元法对实际SF6断路器灭弧室内的气流场进行了计算。计算结果表明,采用这种方法可以对灭弧室内复杂的气流场进行定量的计算分析。文中对不同结构、不同开距下... 本文采用结合差分法与有限元法优点的Taylor-Galerkin有限元法对实际SF6断路器灭弧室内的气流场进行了计算。计算结果表明,采用这种方法可以对灭弧室内复杂的气流场进行定量的计算分析。文中对不同结构、不同开距下气流场的流动特性进行了计算对比。 展开更多
关键词 断路器 六氟化硫断路器 灭弧室 二维气流场 计算
下载PDF
并联电容器组对高压SF_6断路器内部电场分布的影响 被引量:7
20
作者 刘晓明 王尔智 +1 位作者 曹云东 徐东阳 《电网技术》 EI CSCD 北大核心 2000年第8期53-56,共4页
采用模拟电荷法对高压 SF6断路器断口附近复杂三维场域进行了电场计算 ,得到了不同截面等电位线的分布情况及电场分布图。计算结果表明 ,在整个场域中 ,屏蔽罩和并联电容器组起到了很好的均匀电场的作用 ;
关键词 SF6断路器 并联电容器 电场分布 高压
下载PDF
上一页 1 2 8 下一页 到第