Based on energy conservation equation and Darcy's law, a model of beach well infiltration intake system applied in a seawater source heat pump system was established. The model consists of the seawater seepage and th...Based on energy conservation equation and Darcy's law, a model of beach well infiltration intake system applied in a seawater source heat pump system was established. The model consists of the seawater seepage and the heat transfer process. A porous medium model in a software named FLUENT was applied to simulate the seepage and the heat transfer process. This model was also validated by field experiment conducted on the seashore in Tianjin, China. The maximum relative error between simulation results and experimental results was 2.1% (less than 5%), which was acceptable in engineering applica- tion. The porosity and coefficient of thermal conductivity of the aquifer soil were determined to be 0.49 W/(m. K) and 1.46W/(m.K), respectively in the simulation. In addition, the influencing factors of pumping water of beach well were also analyzed. The pumping water was found to increase when the distance between the beach well and the impervious boundary becomes longer, when the distance between the beach well and the supplying water source shortens, when the diameter of the beach well enlarges, and the drawdown enlarges.展开更多
In the beach well intake system, heat is transferred from soil to fluid when seawater is filtered through the aquifer, providing higher temperature source water to the seawater source heat pump (SWHP) system in winter...In the beach well intake system, heat is transferred from soil to fluid when seawater is filtered through the aquifer, providing higher temperature source water to the seawater source heat pump (SWHP) system in winter. A 3-D coupled seepage and heat transfer model for studying beach well intake system is established by adopting the computer code FLUENT. Numerical results of this model are compared with the experimental results under the same conditions. Based on the experiment-verified coupled model, numerical simulation of the supply water tem-perature is studied over a heating season. Results show that the minimum temperature of supply water is 275.2 K when this intake system continuously provides seawater with flow rate of 35 m3/h to SWHP. Results also indicate that the supply water temperature is higher than seawater, and that the minimum temperature of supply water lags behind seawater, ensuring effective and reliable operation of SWHP.展开更多
基金This work was supported by the National Natural Science Foundation of China (Grant No. 51106110).
文摘Based on energy conservation equation and Darcy's law, a model of beach well infiltration intake system applied in a seawater source heat pump system was established. The model consists of the seawater seepage and the heat transfer process. A porous medium model in a software named FLUENT was applied to simulate the seepage and the heat transfer process. This model was also validated by field experiment conducted on the seashore in Tianjin, China. The maximum relative error between simulation results and experimental results was 2.1% (less than 5%), which was acceptable in engineering applica- tion. The porosity and coefficient of thermal conductivity of the aquifer soil were determined to be 0.49 W/(m. K) and 1.46W/(m.K), respectively in the simulation. In addition, the influencing factors of pumping water of beach well were also analyzed. The pumping water was found to increase when the distance between the beach well and the impervious boundary becomes longer, when the distance between the beach well and the supplying water source shortens, when the diameter of the beach well enlarges, and the drawdown enlarges.
基金Supported by Tianjin Construction Committee Technology Project (No2007-37)
文摘In the beach well intake system, heat is transferred from soil to fluid when seawater is filtered through the aquifer, providing higher temperature source water to the seawater source heat pump (SWHP) system in winter. A 3-D coupled seepage and heat transfer model for studying beach well intake system is established by adopting the computer code FLUENT. Numerical results of this model are compared with the experimental results under the same conditions. Based on the experiment-verified coupled model, numerical simulation of the supply water tem-perature is studied over a heating season. Results show that the minimum temperature of supply water is 275.2 K when this intake system continuously provides seawater with flow rate of 35 m3/h to SWHP. Results also indicate that the supply water temperature is higher than seawater, and that the minimum temperature of supply water lags behind seawater, ensuring effective and reliable operation of SWHP.