A novel method of measuring the positive-sequence capacitance of T-connection transmission lines is proposed. The mathematical model of the new method is explained in detail. In order to obtain enough independent equa...A novel method of measuring the positive-sequence capacitance of T-connection transmission lines is proposed. The mathematical model of the new method is explained in detail. In order to obtain enough independent equations, three independent operation modes of T-connection transmission lines during the line measurement are introduced. The digital simulation results and field measurement results are shown. The simulation and measurement results have validated that the new method can meet the needs of measuring the positive-sequence capacitance of T-connection transmission lines. This method has been implemented in the newly developed measurement instrument.展开更多
The results of T-Line Traveling Wave Fault Location is easily influenced by the wave arrival time and traveling wave propagation velocity;it proposes that the traveling wave uses wavelet transform to extract the modul...The results of T-Line Traveling Wave Fault Location is easily influenced by the wave arrival time and traveling wave propagation velocity;it proposes that the traveling wave uses wavelet transform to extract the modulus maxima of breakdown voltage, to confirm the time of the traveling wave reaching the three-terminal line. The speed of the traveling wave reaching three terminals is confirmed by the structural parameters of the transmission line. We apply the arrival time and propagation velocity to the T-type traveling wave fault location algorithm. Different transmission line distance select the corresponding algorithm, excluding the impact of fault branches and in some cases ranging accuracy, the failure dead zone will not appear. After MATLAB simulation analysis, the algorithm analysis is clear;the range accuracy is high, so that it can meet the requirements of fault location.展开更多
文摘A novel method of measuring the positive-sequence capacitance of T-connection transmission lines is proposed. The mathematical model of the new method is explained in detail. In order to obtain enough independent equations, three independent operation modes of T-connection transmission lines during the line measurement are introduced. The digital simulation results and field measurement results are shown. The simulation and measurement results have validated that the new method can meet the needs of measuring the positive-sequence capacitance of T-connection transmission lines. This method has been implemented in the newly developed measurement instrument.
文摘The results of T-Line Traveling Wave Fault Location is easily influenced by the wave arrival time and traveling wave propagation velocity;it proposes that the traveling wave uses wavelet transform to extract the modulus maxima of breakdown voltage, to confirm the time of the traveling wave reaching the three-terminal line. The speed of the traveling wave reaching three terminals is confirmed by the structural parameters of the transmission line. We apply the arrival time and propagation velocity to the T-type traveling wave fault location algorithm. Different transmission line distance select the corresponding algorithm, excluding the impact of fault branches and in some cases ranging accuracy, the failure dead zone will not appear. After MATLAB simulation analysis, the algorithm analysis is clear;the range accuracy is high, so that it can meet the requirements of fault location.