To thoroughly study the extinguishing effect of a high-pressure water mist fire extinguishing system when a transformer fire occurs,a 3D experimental model of a transformer is established in this work by employing Fir...To thoroughly study the extinguishing effect of a high-pressure water mist fire extinguishing system when a transformer fire occurs,a 3D experimental model of a transformer is established in this work by employing Fire Dynamics Simulator(FDS)software.More specifically,by setting different parameters,the process of the highpressure water mist fire extinguishing system with the presence of both diverse ambient temperatures and water mist sprinkler laying conditions is simulated.In addition,the fire extinguishing effect of the employed high-pressure water mist system with the implementation of different strategies is systematically analyzed.The extracted results show that a fire source farther away fromthe centerline leads to a lower local temperature distribution.In addition,as the ambient temperature increases,the temperature above the fire source decreases,while the temperature and the concentrationof theupperflue gas layer bothdecrease.Interestingly,after thehigh-pressurewatermist sprinkler begins to operate,both the temperature distribution above the fire source and the concentration of the flue gas decrease,which indicates that the high-pressure water mist system plays the role of cooling and dust removal.By comparing various sprinkler laying methods,it is found that the lower sprinkler height has a better effect on the temperature above the fire source,the temperature of the upper flue gas layer,and the concentration of the flue gas.Moreover,when the sprinkler is spread over thewhole transformer,the cooling effect on both the temperature above the fire source and the temperature of the upper flue gas layer is good,whereas the change in the concentration of the flue gas above the fire source is not obvious compared to the case where the sprinkler is not fully spread.展开更多
BACKGROUND This case of gestational gingival tumor is huge and extremely rare in clinical practice.As the growth location of this gingival tumor is in the upper anterior tooth area,it seriously affects the pregnant wo...BACKGROUND This case of gestational gingival tumor is huge and extremely rare in clinical practice.As the growth location of this gingival tumor is in the upper anterior tooth area,it seriously affects the pregnant woman's speech and food,causing great pain to the patient.The use of Nd:YGA water mist laser to remove the gingival tumor resulted in minimal intraoperative bleeding,minimal adverse reactions,and good postoperative healing,which is worthy of clinical promotion and application.CASE SUMMARY The patient,a pregnant woman,reported a large lump in her mouth on the first day of postpartum treatment.Based on medical history and clinical examination,the diagnosis was diagnosed as gestational gingival tumor.Postoperative pathological biopsy also confirmed this diagnosis.The use of Nd:YAG water mist laser to remove the tumor resulted in minimal intraoperative bleeding,clear surgical field of view,short surgical time,and good postoperative healing.CONCLUSION In comparison to traditional surgery,Nd:YAG water mist laser surgery is minimally invasive,minimizes cell damage,reduces bleeding,ensures a clear field of vision,and virtually eliminates postoperative edema,carbonization,and the risk of cross infection.It has unique advantages in oral soft tissue surgery for pregnant patients.Therefore,the clinical application of Nd:YAG water mist laser for the treatment of gestational gingival tumors is an ideal choice.展开更多
Combined effects of obstacles and fine water mist on a methane-air explosion of a semi-closed pipe were investigated experimentally.In this study,the diameter of the water mist,the location,and the number of obstacles...Combined effects of obstacles and fine water mist on a methane-air explosion of a semi-closed pipe were investigated experimentally.In this study,the diameter of the water mist,the location,and the number of obstacles was considered.The results demonstrated that 5 μm water mist present a significant suppression affected while 45 μm shows a slight promotion effected on a gas explosion of the condition without obstacles.In the presence of an obstacle,however,the inhibitory effect of 5 μm water veils of mist dropped significantly during flame propagation,and the effect of 45 μm water veils of mist changed from the enhancement of inhibition,and its inhibitory effect was significant.The inhibitory effect of 45 μm water veils of mist on gas explosion weakened firstly and then enhanced with the increasing distance between obstacle location from the ignition location as well as in several obstacles.展开更多
The main objective of the present study was introduced water mist suppressiontechnology to prevent and control gas burning which occurred during drilling at Wu20160working-face in No.10 coal mine of Pingdingshan Ltd.....The main objective of the present study was introduced water mist suppressiontechnology to prevent and control gas burning which occurred during drilling at Wu20160working-face in No.10 coal mine of Pingdingshan Ltd..Based on the self-developed ex-periment platform,a series of fire suppression tests to evaluate the performance of a watermist system were conducted.The detailed measurements of the spray characteristics,i.e.,the Sauter Mean Diameter(SMD),the velocity and spray angle which are the main pa-rameters considered in the Study,were obtained by using LS-2000 Sizer.The amount ofwater consumed and the water flux density distribution over the cross section downstreamthe nozzle exit were measured by cup collector method.The operating pressure of thewater mist nozzle is set to 0.5 MPa,the droplet SMD of 104 pm,the water flux density dis-tribution from 0.71 to 8.47 L/(m^2.min),the average velocity of 2.14 m/s.The experimentalresults show that the averaged time required for extinguishment is 3.14 s,and the corre-sponding amount of water used during fire test is about 0.11 kg.The gas fire suppressionsystem reduces the temperature in combustion chamber of the experimental apparatusbelow the ignition point of the gas,which can effectively avoid the occurrence of the gasfire in coal mine.展开更多
In order to apply ultra-fine water mist technology on spontaneous coal combustion in the goaf of a coal mine, we built a small scale compartment with ultra-fine water mist for restraining coal combustion in a confined...In order to apply ultra-fine water mist technology on spontaneous coal combustion in the goaf of a coal mine, we built a small scale compartment with ultra-fine water mist for restraining coal combustion in a confined space and then investigated the restraining efficiency and related factors. The study obtained the following results: a descending rate of heat release, an increase in 02, the production of CO2 decreased gradually, while the production of CO increased dramatically and quickly and then decreased; ultimately it tended to become stable after the discharge of an ultra-fine water mist. The technology showed that the ultra-fine water mist can effectively reduce the heat release rate of coal and the rate to generate components. We found that the restraining effect relied on the mist flux, the discharge time and other factors. A sufficient amount of mist has a better effect compared to an insufficient amount of mist. To combat coal combustion, the greater the discharge time, the better coal flames are extinguished.展开更多
Water mist technology provides efficient firefighting performance while there is still room for improvement. So varieties of additives have been studied in recent years both at home and abroad. The self-made additives...Water mist technology provides efficient firefighting performance while there is still room for improvement. So varieties of additives have been studied in recent years both at home and abroad. The self-made additives are used to compare the firefighting performance of diesel and heptane fire in open space. By adjusting the concentration of substance in the additives and conducting the experiment under the pressure of 0.3 MPa,0.5 MPa and 0.7 MPa,extinguish time and temperature are measured in the experiment. Through the experiments using different fuels,it can be found when the fuel is heptane that has a lower ignition point and a higher evaporation rate, the water mist additive can still significantly improve the firefighting performance. According to the data based on different concentrations of fluorinated surfactants,we find that fluorinated surfactants are the main substance to improve the performances by changing physical property of water mist. Optimal proportion of the additives for firefighting performance is found by experiment results.展开更多
Electric discharge in and in contact with water can accompany ultraviolet(UV)radiation and electron impact, which can generate a large number of active species such as hydroxyl radicals(OH), oxygen radical(O), o...Electric discharge in and in contact with water can accompany ultraviolet(UV)radiation and electron impact, which can generate a large number of active species such as hydroxyl radicals(OH), oxygen radical(O), ozone(O_3) and hydrogen peroxide(H_2O_2). In this paper, a nonthermal plasma processing system was established by means of dielectric barrier discharge(DBD)arrays in water mist spray. The relationship between droplet size and water content was examined,and the effects of the concentrations of oxides in both treated water and gas were investigated under different water content and discharge time. The relative intensity of UV spectra from DBD in water mist was a function of water content. The concentrations of both O_3 and nitrogen dioxide(NO_2) in DBD room decreased with increasing water content. Moreover, the concentrations of H_2O_2, O_3 and nitrogen oxides(NOx) in treated water decreased with increasing water content,and all the ones enhanced after discharge. The experimental results were further analyzed by chemical reaction equations and commented by physical principles as much as possible. At last,the water containing phenol was tested in this system for the concentration from 100 mg/L to9.8 mg/L in a period of 35 min.展开更多
In order to study the extinguishing performance of high-pressure-water-mist-based systems on the fires originating from power transformers the PyroSim software is used.Different particle velocities and flow rates are ...In order to study the extinguishing performance of high-pressure-water-mist-based systems on the fires originating from power transformers the PyroSim software is used.Different particle velocities and flow rates are considered.The evolution laws of temperature around transformer,flue gas concentration and upper layer temperature of flue gas are analyzed under different boundary conditions.It is shown that the higher the particle velocity is,the lower the smoke concentration is,the better the cooling effect on the upper layer temperature of flue gas layer is,the larger the flow rate is and the better the cooling effect is.展开更多
In order to solve the problem of using new nozzle is proposed in fire rescue robot. middle or low water pressure to form fine water mist, a Existing water mist nozzles are basically used for high pressure and in large...In order to solve the problem of using new nozzle is proposed in fire rescue robot. middle or low water pressure to form fine water mist, a Existing water mist nozzles are basically used for high pressure and in large size, complex structure and poor low pressure atomization effect in comparison with requirement of snake-like fire rescue robots. On the basis of comprehensive typical spray noz- zles, a direct spiral double helix converging nozzle (DSDHCN) is proposed, which has the advanta- ges of small volume, light weight, simple structure, and convenient installation. To make the spray nozzle have good performance, and meet the requirements of more efficient fire extinguishing, a nu- merical study is carried out to analyze the internal and external full flow field of nozzle. A gas-liquid two-phase flow is applied to simulate the external full flow field of nozzle with VOF model in fluent software. The simulation results show the real situation of water flow out of the atomization nozzle and the water jet trajectory. Some simulations about middle or low water pressure direct spiral double he- lix converging optimized nozzle have been done in 30bar pressure. The simulation results show that the optimized nozzle structure not only makes the spray droplets have a good cone angle, but also have a sufficient axial velocity,which proves the structure rationality of the proposed optimized nozzle.展开更多
The principles of fine water mist explosion-extinguishing system was introduced. The defects of current systems were analyzed. The concept of a new water column cur-tain and the explosion-extinguishing mechanism were ...The principles of fine water mist explosion-extinguishing system was introduced. The defects of current systems were analyzed. The concept of a new water column cur-tain and the explosion-extinguishing mechanism were given. Using water column curtain to suppress methane explosion in experiment pipes was conducted. The photos were written with schlieren photograph system. The results of experiment show that the effect is perfect.展开更多
基金supported by Science and Technology Projects Funded by State Grid Corporation of China (5200202024105A0000).
文摘To thoroughly study the extinguishing effect of a high-pressure water mist fire extinguishing system when a transformer fire occurs,a 3D experimental model of a transformer is established in this work by employing Fire Dynamics Simulator(FDS)software.More specifically,by setting different parameters,the process of the highpressure water mist fire extinguishing system with the presence of both diverse ambient temperatures and water mist sprinkler laying conditions is simulated.In addition,the fire extinguishing effect of the employed high-pressure water mist system with the implementation of different strategies is systematically analyzed.The extracted results show that a fire source farther away fromthe centerline leads to a lower local temperature distribution.In addition,as the ambient temperature increases,the temperature above the fire source decreases,while the temperature and the concentrationof theupperflue gas layer bothdecrease.Interestingly,after thehigh-pressurewatermist sprinkler begins to operate,both the temperature distribution above the fire source and the concentration of the flue gas decrease,which indicates that the high-pressure water mist system plays the role of cooling and dust removal.By comparing various sprinkler laying methods,it is found that the lower sprinkler height has a better effect on the temperature above the fire source,the temperature of the upper flue gas layer,and the concentration of the flue gas.Moreover,when the sprinkler is spread over thewhole transformer,the cooling effect on both the temperature above the fire source and the temperature of the upper flue gas layer is good,whereas the change in the concentration of the flue gas above the fire source is not obvious compared to the case where the sprinkler is not fully spread.
文摘BACKGROUND This case of gestational gingival tumor is huge and extremely rare in clinical practice.As the growth location of this gingival tumor is in the upper anterior tooth area,it seriously affects the pregnant woman's speech and food,causing great pain to the patient.The use of Nd:YGA water mist laser to remove the gingival tumor resulted in minimal intraoperative bleeding,minimal adverse reactions,and good postoperative healing,which is worthy of clinical promotion and application.CASE SUMMARY The patient,a pregnant woman,reported a large lump in her mouth on the first day of postpartum treatment.Based on medical history and clinical examination,the diagnosis was diagnosed as gestational gingival tumor.Postoperative pathological biopsy also confirmed this diagnosis.The use of Nd:YAG water mist laser to remove the tumor resulted in minimal intraoperative bleeding,clear surgical field of view,short surgical time,and good postoperative healing.CONCLUSION In comparison to traditional surgery,Nd:YAG water mist laser surgery is minimally invasive,minimizes cell damage,reduces bleeding,ensures a clear field of vision,and virtually eliminates postoperative edema,carbonization,and the risk of cross infection.It has unique advantages in oral soft tissue surgery for pregnant patients.Therefore,the clinical application of Nd:YAG water mist laser for the treatment of gestational gingival tumors is an ideal choice.
基金financial supports of the National Key Research and Development Program of China(2018YFC0808103)the National Natural Science Foundation of China (51774115, 51604095)。
文摘Combined effects of obstacles and fine water mist on a methane-air explosion of a semi-closed pipe were investigated experimentally.In this study,the diameter of the water mist,the location,and the number of obstacles was considered.The results demonstrated that 5 μm water mist present a significant suppression affected while 45 μm shows a slight promotion effected on a gas explosion of the condition without obstacles.In the presence of an obstacle,however,the inhibitory effect of 5 μm water veils of mist dropped significantly during flame propagation,and the effect of 45 μm water veils of mist changed from the enhancement of inhibition,and its inhibitory effect was significant.The inhibitory effect of 45 μm water veils of mist on gas explosion weakened firstly and then enhanced with the increasing distance between obstacle location from the ignition location as well as in several obstacles.
基金Supported by the Natural Science Foundation of China(50274061,50476033)The Outstanding Talents Innovative Foundation of Henan Province of China(421000800)the Natural Science Foundation of HPU(646102)
文摘The main objective of the present study was introduced water mist suppressiontechnology to prevent and control gas burning which occurred during drilling at Wu20160working-face in No.10 coal mine of Pingdingshan Ltd..Based on the self-developed ex-periment platform,a series of fire suppression tests to evaluate the performance of a watermist system were conducted.The detailed measurements of the spray characteristics,i.e.,the Sauter Mean Diameter(SMD),the velocity and spray angle which are the main pa-rameters considered in the Study,were obtained by using LS-2000 Sizer.The amount ofwater consumed and the water flux density distribution over the cross section downstreamthe nozzle exit were measured by cup collector method.The operating pressure of thewater mist nozzle is set to 0.5 MPa,the droplet SMD of 104 pm,the water flux density dis-tribution from 0.71 to 8.47 L/(m^2.min),the average velocity of 2.14 m/s.The experimentalresults show that the averaged time required for extinguishment is 3.14 s,and the corre-sponding amount of water used during fire test is about 0.11 kg.The gas fire suppressionsystem reduces the temperature in combustion chamber of the experimental apparatusbelow the ignition point of the gas,which can effectively avoid the occurrence of the gasfire in coal mine.
基金Project 50274061 supported by the National Natural Science Foundation of Chinaprovided by the NSFC (50274061)+3 种基金the Program for Changjiang Scholars and Innovative Research Team in University (IRT0618)the Henan Province Basic and Lead-ing-edge Technology Research Program (082300 463205 and 072300420180)the Program for New Century Excellent Talents in University of Henan Province (2005HANCET-05) the Henan Poly-technic University Innovation Funds of Graduate Student Scientific Dissertation (M-20) is gratefully acknowledged
文摘In order to apply ultra-fine water mist technology on spontaneous coal combustion in the goaf of a coal mine, we built a small scale compartment with ultra-fine water mist for restraining coal combustion in a confined space and then investigated the restraining efficiency and related factors. The study obtained the following results: a descending rate of heat release, an increase in 02, the production of CO2 decreased gradually, while the production of CO increased dramatically and quickly and then decreased; ultimately it tended to become stable after the discharge of an ultra-fine water mist. The technology showed that the ultra-fine water mist can effectively reduce the heat release rate of coal and the rate to generate components. We found that the restraining effect relied on the mist flux, the discharge time and other factors. A sufficient amount of mist has a better effect compared to an insufficient amount of mist. To combat coal combustion, the greater the discharge time, the better coal flames are extinguished.
基金Opening Fund of State Key Laboratory of Fire Science,University of Science and Technology of China(No.HZ2011-KF04)
文摘Water mist technology provides efficient firefighting performance while there is still room for improvement. So varieties of additives have been studied in recent years both at home and abroad. The self-made additives are used to compare the firefighting performance of diesel and heptane fire in open space. By adjusting the concentration of substance in the additives and conducting the experiment under the pressure of 0.3 MPa,0.5 MPa and 0.7 MPa,extinguish time and temperature are measured in the experiment. Through the experiments using different fuels,it can be found when the fuel is heptane that has a lower ignition point and a higher evaporation rate, the water mist additive can still significantly improve the firefighting performance. According to the data based on different concentrations of fluorinated surfactants,we find that fluorinated surfactants are the main substance to improve the performances by changing physical property of water mist. Optimal proportion of the additives for firefighting performance is found by experiment results.
基金supported by National Natural Science Foundation of China(Nos.11274092,51107033,11404092,11274091)the Nantong Science and Technology Project,China(No.BK2014024)+1 种基金the Open Project of Jiangsu Province Key Laboratory of Environmental Engineering,China(No.KF2014001)the Fundamental Research Funds for the Central Universities,China(No.2014B11414)
文摘Electric discharge in and in contact with water can accompany ultraviolet(UV)radiation and electron impact, which can generate a large number of active species such as hydroxyl radicals(OH), oxygen radical(O), ozone(O_3) and hydrogen peroxide(H_2O_2). In this paper, a nonthermal plasma processing system was established by means of dielectric barrier discharge(DBD)arrays in water mist spray. The relationship between droplet size and water content was examined,and the effects of the concentrations of oxides in both treated water and gas were investigated under different water content and discharge time. The relative intensity of UV spectra from DBD in water mist was a function of water content. The concentrations of both O_3 and nitrogen dioxide(NO_2) in DBD room decreased with increasing water content. Moreover, the concentrations of H_2O_2, O_3 and nitrogen oxides(NOx) in treated water decreased with increasing water content,and all the ones enhanced after discharge. The experimental results were further analyzed by chemical reaction equations and commented by physical principles as much as possible. At last,the water containing phenol was tested in this system for the concentration from 100 mg/L to9.8 mg/L in a period of 35 min.
基金This work was supported by Science and Technology Project Funded by State Grid Henan Electric Power Company(521702200004)Henan Province Key R&D and Promotion Special(Technology Research)Project(212102210016)Opening Fund of State Key Laboratory of Fire Science(SKLFS)under Grant No.HZ2021-KF11.
文摘In order to study the extinguishing performance of high-pressure-water-mist-based systems on the fires originating from power transformers the PyroSim software is used.Different particle velocities and flow rates are considered.The evolution laws of temperature around transformer,flue gas concentration and upper layer temperature of flue gas are analyzed under different boundary conditions.It is shown that the higher the particle velocity is,the lower the smoke concentration is,the better the cooling effect on the upper layer temperature of flue gas layer is,the larger the flow rate is and the better the cooling effect is.
基金Supported by the National Natural Science Foundation of China(No.61105086)Self-Planned Task(SKLRS-2010-MS-12)of State Key Laboratory of Robotics and System(HIT)Hubei Province Natural Science Foundation(No.2010CDB03405)
文摘In order to solve the problem of using new nozzle is proposed in fire rescue robot. middle or low water pressure to form fine water mist, a Existing water mist nozzles are basically used for high pressure and in large size, complex structure and poor low pressure atomization effect in comparison with requirement of snake-like fire rescue robots. On the basis of comprehensive typical spray noz- zles, a direct spiral double helix converging nozzle (DSDHCN) is proposed, which has the advanta- ges of small volume, light weight, simple structure, and convenient installation. To make the spray nozzle have good performance, and meet the requirements of more efficient fire extinguishing, a nu- merical study is carried out to analyze the internal and external full flow field of nozzle. A gas-liquid two-phase flow is applied to simulate the external full flow field of nozzle with VOF model in fluent software. The simulation results show the real situation of water flow out of the atomization nozzle and the water jet trajectory. Some simulations about middle or low water pressure direct spiral double he- lix converging optimized nozzle have been done in 30bar pressure. The simulation results show that the optimized nozzle structure not only makes the spray droplets have a good cone angle, but also have a sufficient axial velocity,which proves the structure rationality of the proposed optimized nozzle.
基金Supported by National Nature Science Foundation of China(59925411)
文摘The principles of fine water mist explosion-extinguishing system was introduced. The defects of current systems were analyzed. The concept of a new water column cur-tain and the explosion-extinguishing mechanism were given. Using water column curtain to suppress methane explosion in experiment pipes was conducted. The photos were written with schlieren photograph system. The results of experiment show that the effect is perfect.