Characteristics of R22 and its new alternative refrigerant R200 flowing through adiabatic capillary tubes are investigated based on the homogeneous model. Extensive flow variables along tube length such as pressure, t...Characteristics of R22 and its new alternative refrigerant R200 flowing through adiabatic capillary tubes are investigated based on the homogeneous model. Extensive flow variables along tube length such as pressure, temperature, viscosity, velocity. Reynolds number, friction factor and vapor quality etc are compared between the two fluids under the same operating condition. Two cases are considered, namely, either the same tube length or the same mass flow rate as inlet condition. The results show that the mass flow rate in the capillary tube of R290 is 40% lower than that of R22 due to the differences of physical properties between the two fluids. Further. a parametric analysis is performed and it appears that effects of geometric and thermodynamic parameters on mass flow rate of R290 are weaker than that of R22. When the condensing temperature is increased from 40℃ to 50℃ C. the mass flow rate for R22 is increased by 16%. while the increasing rate for R290 is 13%.展开更多
A homogeneous theoretical model is developed to predict the performance of R22 and R290 in adiabatic capillary tubes. The model is based on conservation equations of mass, momentum and energy. Metastable both liquid a...A homogeneous theoretical model is developed to predict the performance of R22 and R290 in adiabatic capillary tubes. The model is based on conservation equations of mass, momentum and energy. Metastable both liquid and two-phase flow regions are considered in the model. In metastable two-phase region, superheated liquid is introduced into the metastable mixture viscosity and two methods are presented to evaluate it. The model is validated by comparing the predicted pressure and temperature profile and mass flow rate with several investigators′ experimental data of R22 and one of its alternatives R290 reported in literature. All of the predicted mass flow rates are within ±800 of measured values. Comparisons are also made between the present model and other investigators′ models or sizing correlation. The model can be used for design or simulation calculation of adiabatic capillary tubes.展开更多
基金Supported by the Fund of"985 Project"of Tianjin University (TD2001011).
文摘Characteristics of R22 and its new alternative refrigerant R200 flowing through adiabatic capillary tubes are investigated based on the homogeneous model. Extensive flow variables along tube length such as pressure, temperature, viscosity, velocity. Reynolds number, friction factor and vapor quality etc are compared between the two fluids under the same operating condition. Two cases are considered, namely, either the same tube length or the same mass flow rate as inlet condition. The results show that the mass flow rate in the capillary tube of R290 is 40% lower than that of R22 due to the differences of physical properties between the two fluids. Further. a parametric analysis is performed and it appears that effects of geometric and thermodynamic parameters on mass flow rate of R290 are weaker than that of R22. When the condensing temperature is increased from 40℃ to 50℃ C. the mass flow rate for R22 is increased by 16%. while the increasing rate for R290 is 13%.
文摘A homogeneous theoretical model is developed to predict the performance of R22 and R290 in adiabatic capillary tubes. The model is based on conservation equations of mass, momentum and energy. Metastable both liquid and two-phase flow regions are considered in the model. In metastable two-phase region, superheated liquid is introduced into the metastable mixture viscosity and two methods are presented to evaluate it. The model is validated by comparing the predicted pressure and temperature profile and mass flow rate with several investigators′ experimental data of R22 and one of its alternatives R290 reported in literature. All of the predicted mass flow rates are within ±800 of measured values. Comparisons are also made between the present model and other investigators′ models or sizing correlation. The model can be used for design or simulation calculation of adiabatic capillary tubes.