By combining the time-history response analysis and the eigenvalue buckling analysis, this paper developed a computational procedure to study the elastic dynamic stability of a transmission tower by APDL language in A...By combining the time-history response analysis and the eigenvalue buckling analysis, this paper developed a computational procedure to study the elastic dynamic stability of a transmission tower by APDL language in ANSYS. The influences of different input directions of seismic excitations and damping ratio on the elastic dynamic stability of tower were discussed. The following conclusions were obtained: ( 1 ) Longitudinal direction of the transmission lines is the worst input direction of seismic excitation for the transmission tower. (2) Dead load has no significant effect on the critical load and the occurrence time of buckling. (3) Vertical input of seismic excitations has no great effect on the dynamic stability of the transmission tower. (4) Damping effect has an influence on the dynamic stability of the transmission tower; however, the inherent characteristics of dynamic buckling is not changed.展开更多
基金The National Natural Science Foundation of China (No.50878093)
文摘By combining the time-history response analysis and the eigenvalue buckling analysis, this paper developed a computational procedure to study the elastic dynamic stability of a transmission tower by APDL language in ANSYS. The influences of different input directions of seismic excitations and damping ratio on the elastic dynamic stability of tower were discussed. The following conclusions were obtained: ( 1 ) Longitudinal direction of the transmission lines is the worst input direction of seismic excitation for the transmission tower. (2) Dead load has no significant effect on the critical load and the occurrence time of buckling. (3) Vertical input of seismic excitations has no great effect on the dynamic stability of the transmission tower. (4) Damping effect has an influence on the dynamic stability of the transmission tower; however, the inherent characteristics of dynamic buckling is not changed.