Insulating parts are easily subjected to pollution which may cause damage to the electric system. A typical disc insulator is chosen as the target to test its flashover voltage by using an artificial pollution system....Insulating parts are easily subjected to pollution which may cause damage to the electric system. A typical disc insulator is chosen as the target to test its flashover voltage by using an artificial pollution system. This test system aims at obtaining characteristic parameters of damage for chosen conducting sola to the selected insulator. Experimental results show that thickness and electric conductivity of pollutant layer over insulators are the main parameters in damage evaluation. The flashover voltage decreases with increase of thickness and/or conductivity. These results provide a better basis on further revealing the damaging nature of conducting sol materials.展开更多
As a main insulating device of power system, insulator can be damaged by chemical pollutant, which does threaten the electric system. An artificial pollution test system is utilized to study the damage mode for a susp...As a main insulating device of power system, insulator can be damaged by chemical pollutant, which does threaten the electric system. An artificial pollution test system is utilized to study the damage mode for a suspension insulator, and the effects of concentration and existing state on damage efficiency of chemical pollutant are studied. Testing results show that the damage mode is flashover damage, whose efficiency increases with the decrease of creepage distance. The concentration of conductive particle of chemical pollution can effectively elevate damage efficiency, though it has a critical value. Unlike natural pollution, chemical pollutant can make insulator flashover damage whether in wet or dry condition. The damage process and relative results reveal the damage rule of insulator by chemical pollutant. Those studies put forward a new means to damage electric insulated device, and provide important reference to the protection design of electric insulator.展开更多
基金Sponsored by State Key Laboratory of Explosion Science and Technology Research Foundation (ZDKT08-04)
文摘Insulating parts are easily subjected to pollution which may cause damage to the electric system. A typical disc insulator is chosen as the target to test its flashover voltage by using an artificial pollution system. This test system aims at obtaining characteristic parameters of damage for chosen conducting sola to the selected insulator. Experimental results show that thickness and electric conductivity of pollutant layer over insulators are the main parameters in damage evaluation. The flashover voltage decreases with increase of thickness and/or conductivity. These results provide a better basis on further revealing the damaging nature of conducting sol materials.
基金Supported by State Key Laboratory of Explosion Science and Technology Foundation(ZDKT08-04)
文摘As a main insulating device of power system, insulator can be damaged by chemical pollutant, which does threaten the electric system. An artificial pollution test system is utilized to study the damage mode for a suspension insulator, and the effects of concentration and existing state on damage efficiency of chemical pollutant are studied. Testing results show that the damage mode is flashover damage, whose efficiency increases with the decrease of creepage distance. The concentration of conductive particle of chemical pollution can effectively elevate damage efficiency, though it has a critical value. Unlike natural pollution, chemical pollutant can make insulator flashover damage whether in wet or dry condition. The damage process and relative results reveal the damage rule of insulator by chemical pollutant. Those studies put forward a new means to damage electric insulated device, and provide important reference to the protection design of electric insulator.