A big step forward to improve power system monitoring and performance, continued load growth without a corresponding increase in transmission resources has resulted in reduced operational margins for many power system...A big step forward to improve power system monitoring and performance, continued load growth without a corresponding increase in transmission resources has resulted in reduced operational margins for many power systems worldwide and has led to operation of power systems closer to their stability limits and to power exchange in new patterns. These issues, as well as the on-going worldwide trend towards deregulation of the entire industry on the one hand and the increased need for accurate and better network monitoring on the other hand, force power utilities exposed to this pressure to demand new solutions for wide area monitoring, protection and control. Wide-area monitoring, protection, and control require communicating the specific-node information to a remote station but all information should be time synchronized so that to neutralize the time difference between information. It gives a complete simultaneous snap shot of the power system. The conventional system is not able to satisfy the time-synchronized requirement of power system. Phasor Measurement Unit (PMU) is enabler of time-synchronized measurement, it communicate the synchronized local information to remote station.展开更多
短路分断是断路器的核心功能,提高断路器的短路分断能力是市场的持续需求。针对有效提升塑壳断路器(Moulded Case Circuit Breaker,MCCB)短路分断能力的方法开展了研究。利用栅片电压测量分析法可以检测灭弧栅片在短路分断时切割电弧的...短路分断是断路器的核心功能,提高断路器的短路分断能力是市场的持续需求。针对有效提升塑壳断路器(Moulded Case Circuit Breaker,MCCB)短路分断能力的方法开展了研究。利用栅片电压测量分析法可以检测灭弧栅片在短路分断时切割电弧的情况,评估各灭弧栅片切割电弧的性能以及电弧在灭弧室内的动态特性,为电弧优化提供参考数据。利用有限元仿真的方法进行电磁力计算,有利于快速验证优化设计方案而免去实际的试验验证,节约产品的研发成本,缩短产品的研发周期。蒸汽喷射控制(Vapour Jet Control,VJC)产气材料的运用也能够进一步提高产品的短路分断能力。综合运用以上设计方法,能够在不会大幅增加研发成本的基础上,快速提升MCCB的短路分断能力,工程应用价值较好。展开更多
为解决船舶中压直流(medium voltage direct current,MVDC)电力系统直流电流开断困难,以及发生短路时故障电流上升率高且峰值大的问题,提出一种基于耦合电抗器的阻容限流型固态直流断路器拓扑。以晶闸管(silicon controlled rectifier,S...为解决船舶中压直流(medium voltage direct current,MVDC)电力系统直流电流开断困难,以及发生短路时故障电流上升率高且峰值大的问题,提出一种基于耦合电抗器的阻容限流型固态直流断路器拓扑。以晶闸管(silicon controlled rectifier,SCR)作为主开断器件,通过耦合电抗器来辅助晶闸管开断,并在直流系统发生故障时,通过换流过程将阻容限流元件接入,有效限制故障电流上升率和峰值,减少故障开断所需时间。基于所提拓扑设计了6 kV/4.2 kA的直流断路器模型,在PSCAD/EMTDC中进行仿真,并与现有拓扑进行对比分析。仿真结果表明:所设计断路器可针对直流系统不同的运行状态,按照不同的控制策略顺利完成对直流电流的开断,并且在开断速度、限流能力和金属氧化物避雷器(metal oxide arrester,MOA)耗能方面均具有一定优势。展开更多
能量路由器的核心元件为双有源桥(dual active bridge,DAB)直流变压器,针对其短路故障时电流上升速率快,峰值大,导致DAB内部电力电子器件闭锁的问题,该文提出一种具有限流型结构的直流变压器,限流装置结构为从DAB高压侧H桥连接单相整流...能量路由器的核心元件为双有源桥(dual active bridge,DAB)直流变压器,针对其短路故障时电流上升速率快,峰值大,导致DAB内部电力电子器件闭锁的问题,该文提出一种具有限流型结构的直流变压器,限流装置结构为从DAB高压侧H桥连接单相整流桥,再与输出端口的限流电感相连。当直流系统发生短路故障时,限流型直流变压器采用混合控制算法进行整流,为限流电感提供钳位电压,限制故障电流的峰值,并与断路器配合实现无弧开断,该方法避免DAB中电力电子器件发生闭锁,快速实现故障限流和隔离。在仿真系统中搭建了基于10kV/750V直流变压器的限流型直流变压器的模型,仿真结果表明限流型直流变压器与断路器配合实现故障限流和隔离的有效性和可行性。展开更多
The two main challenges of medium voltage direct current(MVDC)distribution network are the flexible control of power flow(PF)and fault protection.In this paper,the power flow controller(PFC)is introduced to regulate t...The two main challenges of medium voltage direct current(MVDC)distribution network are the flexible control of power flow(PF)and fault protection.In this paper,the power flow controller(PFC)is introduced to regulate the PF and inhibit the fault current during the DC fault.The coordination strategy of series-parallel PFC(SP-PFC)and hybrid DC circuit breaker(DCCB)is proposed.By regulating the polarity and magnitude of SP-PFC output voltage during the fault,the rising speed of fault current can be suppressed so as to reduce the breaking current of hybrid DCCB.The access mode of SP-PFC to the MVDC distribution network and its topology are analyzed,and the coordination strategy between SP-PFC and hybrid DCCB is investigated.Moreover,the emergency control and bypass control strategies of SP-PFC are developed.On this basis,the mathematical model of SP-PFC in different fault stages is derived.With the equivalent model of SP-PFC,the fault current of the MVDC distribution network can be calculated accurately.A simulation model of the MVDC distribution network containing SP-PFC is established in MATLAB/Simulink.The fault current calculation result is compared with the simulation result,and the effectiveness of the proposed coordination strategy is verified.展开更多
A ZW-126/D2000-40 type single-break vacuum circuit breaker(VCB)with controlled switching technology is designed and produced in this paper.The results of type tests based on IEC and GB standards are presented.A 126 kV...A ZW-126/D2000-40 type single-break vacuum circuit breaker(VCB)with controlled switching technology is designed and produced in this paper.The results of type tests based on IEC and GB standards are presented.A 126 kV singlebreak vacuum interrupter(VI)with 3/4 coil axial magnetic field(AMF)contacts is used in the VCB,which can interrupt short currents of 40 kA.The external insulation of the VI is provided by SF_(6) at 0.1 MPa.In order to match the 126 kV single-break VI and controlled switching device,a long-stroke electro-magnetic force actuator(EMFA)with 16 kN closing holding force and 3.5 m/s average opening speed is designed.Moreover,a position tracking controlled switching device based on closed-loop control using the technology of a fuzzy control algorithm and pulse width modulation is applied to the controlled switching device.This device is applied to control the coil current of EMFA and the electromagnetic force,so as to control the EMFA to follow the ideal position curve.The type tests of 126 kV VCB are all passed according to the IEC62271-100 and GB1984-2014,including dielectric tests,basic short-circuit tests,shortline fault tests,out-of-phase tests,etc.The strong capacitive current breaking capacity and mechanical strength of the VCB are proved by the capacitive current switching test of class C2,electrical endurance test of class E2 and mechanical endurance test of class M2.The electromagnetic compatibility(EMC)tests are passed according to the IEC61000-4.The controlled switching test of capacitive current was successful according to IEC62271-302 and GB/T30846-2014,and the controlled switching accuracy is less than±0.5 ms.The test results show that the VCB has excellent performance,which has broad application prospects in special occasions at a 126 kV voltage level,such as a switching capacitor and no-load transformer,etc.展开更多
文摘A big step forward to improve power system monitoring and performance, continued load growth without a corresponding increase in transmission resources has resulted in reduced operational margins for many power systems worldwide and has led to operation of power systems closer to their stability limits and to power exchange in new patterns. These issues, as well as the on-going worldwide trend towards deregulation of the entire industry on the one hand and the increased need for accurate and better network monitoring on the other hand, force power utilities exposed to this pressure to demand new solutions for wide area monitoring, protection and control. Wide-area monitoring, protection, and control require communicating the specific-node information to a remote station but all information should be time synchronized so that to neutralize the time difference between information. It gives a complete simultaneous snap shot of the power system. The conventional system is not able to satisfy the time-synchronized requirement of power system. Phasor Measurement Unit (PMU) is enabler of time-synchronized measurement, it communicate the synchronized local information to remote station.
文摘为解决船舶中压直流(medium voltage direct current,MVDC)电力系统直流电流开断困难,以及发生短路时故障电流上升率高且峰值大的问题,提出一种基于耦合电抗器的阻容限流型固态直流断路器拓扑。以晶闸管(silicon controlled rectifier,SCR)作为主开断器件,通过耦合电抗器来辅助晶闸管开断,并在直流系统发生故障时,通过换流过程将阻容限流元件接入,有效限制故障电流上升率和峰值,减少故障开断所需时间。基于所提拓扑设计了6 kV/4.2 kA的直流断路器模型,在PSCAD/EMTDC中进行仿真,并与现有拓扑进行对比分析。仿真结果表明:所设计断路器可针对直流系统不同的运行状态,按照不同的控制策略顺利完成对直流电流的开断,并且在开断速度、限流能力和金属氧化物避雷器(metal oxide arrester,MOA)耗能方面均具有一定优势。
文摘能量路由器的核心元件为双有源桥(dual active bridge,DAB)直流变压器,针对其短路故障时电流上升速率快,峰值大,导致DAB内部电力电子器件闭锁的问题,该文提出一种具有限流型结构的直流变压器,限流装置结构为从DAB高压侧H桥连接单相整流桥,再与输出端口的限流电感相连。当直流系统发生短路故障时,限流型直流变压器采用混合控制算法进行整流,为限流电感提供钳位电压,限制故障电流的峰值,并与断路器配合实现无弧开断,该方法避免DAB中电力电子器件发生闭锁,快速实现故障限流和隔离。在仿真系统中搭建了基于10kV/750V直流变压器的限流型直流变压器的模型,仿真结果表明限流型直流变压器与断路器配合实现故障限流和隔离的有效性和可行性。
基金supported by the National Key Research and Development Program of China(No.2018YFB0904600)the National Natural Science Foundation of China(No.52077017)。
文摘The two main challenges of medium voltage direct current(MVDC)distribution network are the flexible control of power flow(PF)and fault protection.In this paper,the power flow controller(PFC)is introduced to regulate the PF and inhibit the fault current during the DC fault.The coordination strategy of series-parallel PFC(SP-PFC)and hybrid DC circuit breaker(DCCB)is proposed.By regulating the polarity and magnitude of SP-PFC output voltage during the fault,the rising speed of fault current can be suppressed so as to reduce the breaking current of hybrid DCCB.The access mode of SP-PFC to the MVDC distribution network and its topology are analyzed,and the coordination strategy between SP-PFC and hybrid DCCB is investigated.Moreover,the emergency control and bypass control strategies of SP-PFC are developed.On this basis,the mathematical model of SP-PFC in different fault stages is derived.With the equivalent model of SP-PFC,the fault current of the MVDC distribution network can be calculated accurately.A simulation model of the MVDC distribution network containing SP-PFC is established in MATLAB/Simulink.The fault current calculation result is compared with the simulation result,and the effectiveness of the proposed coordination strategy is verified.
基金This work is supported by the National Natural Science Foundation of China(No.51877026 and No.51337001)the Science&Technology Project of SGCC(No.5229CG15003Q).
文摘A ZW-126/D2000-40 type single-break vacuum circuit breaker(VCB)with controlled switching technology is designed and produced in this paper.The results of type tests based on IEC and GB standards are presented.A 126 kV singlebreak vacuum interrupter(VI)with 3/4 coil axial magnetic field(AMF)contacts is used in the VCB,which can interrupt short currents of 40 kA.The external insulation of the VI is provided by SF_(6) at 0.1 MPa.In order to match the 126 kV single-break VI and controlled switching device,a long-stroke electro-magnetic force actuator(EMFA)with 16 kN closing holding force and 3.5 m/s average opening speed is designed.Moreover,a position tracking controlled switching device based on closed-loop control using the technology of a fuzzy control algorithm and pulse width modulation is applied to the controlled switching device.This device is applied to control the coil current of EMFA and the electromagnetic force,so as to control the EMFA to follow the ideal position curve.The type tests of 126 kV VCB are all passed according to the IEC62271-100 and GB1984-2014,including dielectric tests,basic short-circuit tests,shortline fault tests,out-of-phase tests,etc.The strong capacitive current breaking capacity and mechanical strength of the VCB are proved by the capacitive current switching test of class C2,electrical endurance test of class E2 and mechanical endurance test of class M2.The electromagnetic compatibility(EMC)tests are passed according to the IEC61000-4.The controlled switching test of capacitive current was successful according to IEC62271-302 and GB/T30846-2014,and the controlled switching accuracy is less than±0.5 ms.The test results show that the VCB has excellent performance,which has broad application prospects in special occasions at a 126 kV voltage level,such as a switching capacitor and no-load transformer,etc.