The thick insulation layer of 110 kV XLPE power cables will result in the gradient changing morphology with the radius due to crosslinking process and cooling of the XLPE insulation. In this paper, the morphology of c...The thick insulation layer of 110 kV XLPE power cables will result in the gradient changing morphology with the radius due to crosslinking process and cooling of the XLPE insulation. In this paper, the morphology of cross-linked polyethylene (XLPE) insulation of 110 kV cable and the uniforming effect of the heating process on it are researched by the differential scanning calorimetry (DSC) and X-ray diffraction (WAXD). The middle layer morphology structures of insulation produced by normal technology are of better uniform, while the crystallinity of the inner and outer layer of the insulation is lower than that of the middle one. The melting enthalpy AHm of materials displays the difference of the crystal morphologies sensitively. The difference of crystallizing morphology in different layers of the high-voltage power cable insulation can be improved by heating process. But the uniforming of morphology of the insulation by heating process requires sufficient ttanperature and time. The effect of the on-line stress-relaxation equipment used widely by cable works now should be doubted. The test results of WAXD reveal that thermal stress changes the interplanar distances in the crystal region. So the radical stress in the insulation is tensile mainly.展开更多
The recent developments in the photoinitiated cross-linking of polyethylene and the significant breakthrough of its industrial application are reviewed. The enhanced photo-initiation system, the dynamics of photoiniti...The recent developments in the photoinitiated cross-linking of polyethylene and the significant breakthrough of its industrial application are reviewed. The enhanced photo-initiation system, the dynamics of photoinitiated crosslinking, the optimum conditions, the crystal morphological structures and related properties, and the photo- and thermo-oxidation stability of photocrosslinked polyethylene (XLPE) materials have been elucidated systematically. A new technique for producing photocrosslinked XLPE-insulated wire and cable is described in detail. It can be expected that the future applications of photocrosslinking technique of polyolefins will be very promising.展开更多
To improve the water tree resistance of PE, linear low-density polyethylene (LLDPE) was compounded with sodium acrylate (NaAA) for in situ polymerization, in which NaAA was fbrmed through the neutralization of acr...To improve the water tree resistance of PE, linear low-density polyethylene (LLDPE) was compounded with sodium acrylate (NaAA) for in situ polymerization, in which NaAA was fbrmed through the neutralization of acrylic acid (AA) with sodium hydroxide (NaOH) before adding dicumyl peroxide (DCP) to initiate the in situ graft polymerization and homo polymerization. A series of LLDPE/NaAA compounds were investigated for their water absorption ratio (WAR) measurement, water treeing, mechanical and dielectric properties. The results strongly suggest that NaAA can improve the water tree resistance of LLDPE. In addition, the LLDPE/NaAA compounds possess satisfactory mechanical properties and dielectric properties. Characterization of LLDPE/NaAA compounds by using Fourier transform infrared spectrometry (FTIR) suggests that the neutralization and polymerization reaction could be achieved effectively. Using adequate DCP content is the key factor for controlling the polymerization of NaAA with precise conversion ratio.展开更多
The degradation of crosslinked polyethylene (XLPE) cable insulation during service, such as thermo-oxidation and water treeing may lead to a premature electrical breakdown of the XLPE insulation cables. Therefore, it ...The degradation of crosslinked polyethylene (XLPE) cable insulation during service, such as thermo-oxidation and water treeing may lead to a premature electrical breakdown of the XLPE insulation cables. Therefore, it is necessary to optimize the period of replacement to evenly distribute the replacement cost by ascertaining the deterioration degree. Estimation of the aging degree is at present the most important task for diagnosis of the residual lifetime of the power cable insulation. This paper presents a study on the changes in the dielectric properties of the thermally aged XLPE cables in the frequency range from 0.07~10 MHz. Based on electrical and physicochemical characterization, some new "dactylograms" for the thermally aged XLPE cable insulation have been proposed.展开更多
热塑性聚乙烯基电缆绝缘材料具有优于交联聚乙烯(cross-linked polyethylene,XLPE)的电气和机械性能,有望成为新一代绿色环保的电缆绝缘材料。在电缆结构设计中,保守的安全绝缘厚度使得电缆的生产成本增加,降低绝缘层的击穿电场强度;并...热塑性聚乙烯基电缆绝缘材料具有优于交联聚乙烯(cross-linked polyethylene,XLPE)的电气和机械性能,有望成为新一代绿色环保的电缆绝缘材料。在电缆结构设计中,保守的安全绝缘厚度使得电缆的生产成本增加,降低绝缘层的击穿电场强度;并且在电缆实际运行过程中,绝缘材料往往工作在70~90℃高温环境下;因此针对新型绝缘材料,温度及厚度对其击穿电场强度的影响研究具有工程实际意义。以线性低密度聚乙烯(linear low density polyethylene,LLDPE)/高密度聚乙烯(high density polyethylene,HDPE)共混绝缘材料为研究对象,进行不同温度下(30、70、90、105℃)及不同厚度下的工频击穿实验,研究温度和厚度对其交流击穿的影响。测试结果表明:相较于XLPE绝缘材料,70L-30H(即LLDPE与HDPE在配比为7∶3的情况下熔融共混得到的绝缘材料)具有较高的工频击穿电场强度,在低于工况温度环境下,其击穿电场强度的温度稳定性较高;然而70L-30H的工频击穿电场强度受厚度影响程度略高,但在相同厚度下其击穿电场强度仍明显高于XLPE。上述研究可为热塑性聚乙烯基电缆绝缘材料研发提供参考。展开更多
文摘The thick insulation layer of 110 kV XLPE power cables will result in the gradient changing morphology with the radius due to crosslinking process and cooling of the XLPE insulation. In this paper, the morphology of cross-linked polyethylene (XLPE) insulation of 110 kV cable and the uniforming effect of the heating process on it are researched by the differential scanning calorimetry (DSC) and X-ray diffraction (WAXD). The middle layer morphology structures of insulation produced by normal technology are of better uniform, while the crystallinity of the inner and outer layer of the insulation is lower than that of the middle one. The melting enthalpy AHm of materials displays the difference of the crystal morphologies sensitively. The difference of crystallizing morphology in different layers of the high-voltage power cable insulation can be improved by heating process. But the uniforming of morphology of the insulation by heating process requires sufficient ttanperature and time. The effect of the on-line stress-relaxation equipment used widely by cable works now should be doubted. The test results of WAXD reveal that thermal stress changes the interplanar distances in the crystal region. So the radical stress in the insulation is tensile mainly.
基金The project was successively supported by the National Natural Science Foundation of China(No. 5880104, No. 59543002 and No. 59773030).
文摘The recent developments in the photoinitiated cross-linking of polyethylene and the significant breakthrough of its industrial application are reviewed. The enhanced photo-initiation system, the dynamics of photoinitiated crosslinking, the optimum conditions, the crystal morphological structures and related properties, and the photo- and thermo-oxidation stability of photocrosslinked polyethylene (XLPE) materials have been elucidated systematically. A new technique for producing photocrosslinked XLPE-insulated wire and cable is described in detail. It can be expected that the future applications of photocrosslinking technique of polyolefins will be very promising.
基金The project was supported by the Shanghai Committee of Science and Technology (No. 045211024).
文摘To improve the water tree resistance of PE, linear low-density polyethylene (LLDPE) was compounded with sodium acrylate (NaAA) for in situ polymerization, in which NaAA was fbrmed through the neutralization of acrylic acid (AA) with sodium hydroxide (NaOH) before adding dicumyl peroxide (DCP) to initiate the in situ graft polymerization and homo polymerization. A series of LLDPE/NaAA compounds were investigated for their water absorption ratio (WAR) measurement, water treeing, mechanical and dielectric properties. The results strongly suggest that NaAA can improve the water tree resistance of LLDPE. In addition, the LLDPE/NaAA compounds possess satisfactory mechanical properties and dielectric properties. Characterization of LLDPE/NaAA compounds by using Fourier transform infrared spectrometry (FTIR) suggests that the neutralization and polymerization reaction could be achieved effectively. Using adequate DCP content is the key factor for controlling the polymerization of NaAA with precise conversion ratio.
基金Major Research Project of Shanghai City(No. 045211024)
文摘The degradation of crosslinked polyethylene (XLPE) cable insulation during service, such as thermo-oxidation and water treeing may lead to a premature electrical breakdown of the XLPE insulation cables. Therefore, it is necessary to optimize the period of replacement to evenly distribute the replacement cost by ascertaining the deterioration degree. Estimation of the aging degree is at present the most important task for diagnosis of the residual lifetime of the power cable insulation. This paper presents a study on the changes in the dielectric properties of the thermally aged XLPE cables in the frequency range from 0.07~10 MHz. Based on electrical and physicochemical characterization, some new "dactylograms" for the thermally aged XLPE cable insulation have been proposed.
文摘热塑性聚乙烯基电缆绝缘材料具有优于交联聚乙烯(cross-linked polyethylene,XLPE)的电气和机械性能,有望成为新一代绿色环保的电缆绝缘材料。在电缆结构设计中,保守的安全绝缘厚度使得电缆的生产成本增加,降低绝缘层的击穿电场强度;并且在电缆实际运行过程中,绝缘材料往往工作在70~90℃高温环境下;因此针对新型绝缘材料,温度及厚度对其击穿电场强度的影响研究具有工程实际意义。以线性低密度聚乙烯(linear low density polyethylene,LLDPE)/高密度聚乙烯(high density polyethylene,HDPE)共混绝缘材料为研究对象,进行不同温度下(30、70、90、105℃)及不同厚度下的工频击穿实验,研究温度和厚度对其交流击穿的影响。测试结果表明:相较于XLPE绝缘材料,70L-30H(即LLDPE与HDPE在配比为7∶3的情况下熔融共混得到的绝缘材料)具有较高的工频击穿电场强度,在低于工况温度环境下,其击穿电场强度的温度稳定性较高;然而70L-30H的工频击穿电场强度受厚度影响程度略高,但在相同厚度下其击穿电场强度仍明显高于XLPE。上述研究可为热塑性聚乙烯基电缆绝缘材料研发提供参考。