In order to get thermal flow field of direct air-cooled system,the hot water was supplied to the model of direct air-cooled condenser(ACC). The particle image velocimetery (PIV) experiments were carried out to get the...In order to get thermal flow field of direct air-cooled system,the hot water was supplied to the model of direct air-cooled condenser(ACC). The particle image velocimetery (PIV) experiments were carried out to get thermal flow field of a ACC under different conditions in low velocity wind tunnel,at the same time,the recirculation ratio at cooling tower was measured,so the relationship between flow field characteristics and recirculation ratio of cooling tower can be discussed. From the results we can see that the flow field configuration around cooling tower has great effects on average recirculation ratio under cooling tower. The eddy formed around cooling tower is a key reason that recirculation produces. The eddy intensity relates to velocity magnitude and direction angle,and the configuration of eddy lies on the geometry size of cooling tower. So changing the flow field configuration around cooling tower reasonably can decrease recirculation ratio under cooling tower,and heat dispel effect of ACC can also be improved.展开更多
The paper introduces thermal buoyancy effects to experimental investigation of wind tunnel simulation on direct air-cooled condenser for a large power plant. In order to get thermal flow field of air-cooled tower, PIV...The paper introduces thermal buoyancy effects to experimental investigation of wind tunnel simulation on direct air-cooled condenser for a large power plant. In order to get thermal flow field of air-cooled tower, PIV experiments are carried out and recirculation ratio of each condition is calculated. Results show that the thermal flow field of the cooling tower has great influence on the recirculation under the cooling tower. Ameliorating the thermal flow field of the cooling tower can reduce the recirculation under the cooling tower and improve the efficiency of air-cooled condenser also.展开更多
The natural wind plays disadvantageous roles in the operation of air-cooled steam condensers in power plant.It is of use to take various measures against the adverse effect of wind for the performance improvement of a...The natural wind plays disadvantageous roles in the operation of air-cooled steam condensers in power plant.It is of use to take various measures against the adverse effect of wind for the performance improvement of air-cooled condensers.Based on representative 2×600 MW direct air-cooled power plant,three ways that can arrange and optimize the flow field of cooling air thus enhance the heat transfer of air-cooled condensers were proposed.The physical and mathematical models of air-cooled condensers with various flow leading measures were presented and the flow and temperature fields of cooling air were obtained by CFD simulation.The back pressures of turbine were calculated for different measures on the basis of the heat transfer model of air-cooled condensers.The results show that the performance of air-cooled condensers is improved thus the back pressure of turbine is lowered to some extent by taking measures against the adverse impact of natural wind.展开更多
The cooling performance of air-cooled condenser(ACC)is susceptible to adverse impacts of ambient winds.In this work,three kinds of lateral double-layered deflectors installed under the ACC platform are proposed to wea...The cooling performance of air-cooled condenser(ACC)is susceptible to adverse impacts of ambient winds.In this work,three kinds of lateral double-layered deflectors installed under the ACC platform are proposed to weaken the unfavorable effects of cross winds.Through CFD simulation methods,the main parameters of thermo-flow performances of a 2×660 MW direct dry cooling system are obtained,by which it can be concluded that the deflectors can effectively reduce the inlet air temperatures while enhance the mass flow rates of upwind fans due to the guiding effect,especially at high wind speeds,while the improvement of cooling capacity of ACCs in the 0°wind direction is weak.The inclined-vertical deflectors are superior to others in performance improvement of ACCs for all cases,which can reduce the turbine back pressure by 12.15%when the wind speed is 12 m/s,so they can be applied to the performance enhancement of ACCs under windy conditions in practical engineering.展开更多
The typical configuration adopted by air-cooled condenser(ACC) in coal-fired power generating unit is the wave finned flat tube. The development of boundary layer between wave fins along long axis of flat tube can sup...The typical configuration adopted by air-cooled condenser(ACC) in coal-fired power generating unit is the wave finned flat tube. The development of boundary layer between wave fins along long axis of flat tube can suppress the air-side heat transfer enhancement to a great extent. It has been proved that the serrated fins can enhance heat transfer obviously by breaking the development of boundary layer periodically. In the present study,the discontinuous short wave fin was introduced to the flat tube to enhance the air-side heat transfer of ACC. Two different types of arrangements,i.e. staggered and in-line for discontinuous short wave fins on the flat tube,were designed. By numerical simulation,the heat transfer and flow performances of short wave fins were studied under different arrangements(in-line,staggered) ,and the influences on heat transfer and flow characteristics of rows of short wave fin and interrupted distance between discontinuous short wave fins were revealed numerically. The results indicated that,compared with the original continuous wave fin,the discontinuous short wave fin effectively improved the air-side heat transfer of flat tube under the air flow velocities in the practical application of engineering. Moreover,the increment of pressure loss of air-side flow was restricted for the discontinuous short wave fins because of the reduction of contact areas between the air flow and fin surface.展开更多
文摘In order to get thermal flow field of direct air-cooled system,the hot water was supplied to the model of direct air-cooled condenser(ACC). The particle image velocimetery (PIV) experiments were carried out to get thermal flow field of a ACC under different conditions in low velocity wind tunnel,at the same time,the recirculation ratio at cooling tower was measured,so the relationship between flow field characteristics and recirculation ratio of cooling tower can be discussed. From the results we can see that the flow field configuration around cooling tower has great effects on average recirculation ratio under cooling tower. The eddy formed around cooling tower is a key reason that recirculation produces. The eddy intensity relates to velocity magnitude and direction angle,and the configuration of eddy lies on the geometry size of cooling tower. So changing the flow field configuration around cooling tower reasonably can decrease recirculation ratio under cooling tower,and heat dispel effect of ACC can also be improved.
文摘The paper introduces thermal buoyancy effects to experimental investigation of wind tunnel simulation on direct air-cooled condenser for a large power plant. In order to get thermal flow field of air-cooled tower, PIV experiments are carried out and recirculation ratio of each condition is calculated. Results show that the thermal flow field of the cooling tower has great influence on the recirculation under the cooling tower. Ameliorating the thermal flow field of the cooling tower can reduce the recirculation under the cooling tower and improve the efficiency of air-cooled condenser also.
基金supported by the National Basic Research Program of China ("973" Project) (Grant No.2009CB219804)
文摘The natural wind plays disadvantageous roles in the operation of air-cooled steam condensers in power plant.It is of use to take various measures against the adverse effect of wind for the performance improvement of air-cooled condensers.Based on representative 2×600 MW direct air-cooled power plant,three ways that can arrange and optimize the flow field of cooling air thus enhance the heat transfer of air-cooled condensers were proposed.The physical and mathematical models of air-cooled condensers with various flow leading measures were presented and the flow and temperature fields of cooling air were obtained by CFD simulation.The back pressures of turbine were calculated for different measures on the basis of the heat transfer model of air-cooled condensers.The results show that the performance of air-cooled condensers is improved thus the back pressure of turbine is lowered to some extent by taking measures against the adverse impact of natural wind.
基金The National Natural Science Foundation of China(Grant No.51476055,51821004)the National Basic Research Program of China(Grant No.2015CB251503)the Fundamental Research Funds for the Central Universities(Grant No.2018QN036)are gratefully acknowledged for supporting this research.
文摘The cooling performance of air-cooled condenser(ACC)is susceptible to adverse impacts of ambient winds.In this work,three kinds of lateral double-layered deflectors installed under the ACC platform are proposed to weaken the unfavorable effects of cross winds.Through CFD simulation methods,the main parameters of thermo-flow performances of a 2×660 MW direct dry cooling system are obtained,by which it can be concluded that the deflectors can effectively reduce the inlet air temperatures while enhance the mass flow rates of upwind fans due to the guiding effect,especially at high wind speeds,while the improvement of cooling capacity of ACCs in the 0°wind direction is weak.The inclined-vertical deflectors are superior to others in performance improvement of ACCs for all cases,which can reduce the turbine back pressure by 12.15%when the wind speed is 12 m/s,so they can be applied to the performance enhancement of ACCs under windy conditions in practical engineering.
基金supported by the National Basic Research Program of China ("973" Program) (Grant No.2009CB219804)
文摘The typical configuration adopted by air-cooled condenser(ACC) in coal-fired power generating unit is the wave finned flat tube. The development of boundary layer between wave fins along long axis of flat tube can suppress the air-side heat transfer enhancement to a great extent. It has been proved that the serrated fins can enhance heat transfer obviously by breaking the development of boundary layer periodically. In the present study,the discontinuous short wave fin was introduced to the flat tube to enhance the air-side heat transfer of ACC. Two different types of arrangements,i.e. staggered and in-line for discontinuous short wave fins on the flat tube,were designed. By numerical simulation,the heat transfer and flow performances of short wave fins were studied under different arrangements(in-line,staggered) ,and the influences on heat transfer and flow characteristics of rows of short wave fin and interrupted distance between discontinuous short wave fins were revealed numerically. The results indicated that,compared with the original continuous wave fin,the discontinuous short wave fin effectively improved the air-side heat transfer of flat tube under the air flow velocities in the practical application of engineering. Moreover,the increment of pressure loss of air-side flow was restricted for the discontinuous short wave fins because of the reduction of contact areas between the air flow and fin surface.