This paper proposes a longitudinal protection scheme utilizing empirical wavelet transform(EWT)for a through-type cophase traction direct power supply system,where both sides of a traction network line exhibit a disti...This paper proposes a longitudinal protection scheme utilizing empirical wavelet transform(EWT)for a through-type cophase traction direct power supply system,where both sides of a traction network line exhibit a distinctive boundary structure.This approach capitalizes on the boundary’s capacity to attenuate the high-frequency component of fault signals,resulting in a variation in the high-frequency transient energy ratio when faults occur inside or outside the line.During internal line faults,the high-frequency transient energy at the checkpoints located at both ends surpasses that of its neighboring lines.Conversely,for faults external to the line,the energy is lower compared to adjacent lines.EWT is employed to decompose the collected fault current signals,allowing access to the high-frequency transient energy.The longitudinal protection for the traction network line is established based on disparities between both ends of the traction network line and the high-frequency transient energy on either side of the boundary.Moreover,simulation verification through experimental results demonstrates the effectiveness of the proposed protection scheme across various initial fault angles,distances to faults,and fault transition resistances.展开更多
The increasing scale and complexity of power systems require high performance and high reliability of power system protection.Protective relaying based on directional comparison with power line carrier or microwave ch...The increasing scale and complexity of power systems require high performance and high reliability of power system protection.Protective relaying based on directional comparison with power line carrier or microwave channels is the most suitable protection scheme for long distance EHV transmission lines and is widely used in power systems.The key element of such protection is a directional relay used to discriminate the fault direction.In order to overcome the disadvantages of conventional directional relays,the authors of this paper put forward the directional comparison carrier protection based on the artificial neural network(ANN).The protection is extensively tested using electromagnetic transient program (EMTP) under various electric power system operating and fault conditions.It is proved that the directional comparison carrier protection based on ANN,which can recognize various fault patterns of the protected transmission line(such as fault direction,fault phases etc.)correctly in any kind of operating and fault conditions and the whole process,is satisfactory for EHV transmission line protection.展开更多
Distributed generators now is widely used in electrical power networks, in some cases it works seasonally, and some types works at special weather conditions like photo voltaic systems and wind energy, and due to this...Distributed generators now is widely used in electrical power networks, in some cases it works seasonally, and some types works at special weather conditions like photo voltaic systems and wind energy, and due to this continuous changes in generation condition, the fault current level in network will be affected, this changes in fault current level will affect in the coordination between protection relays and to keep the coordination at right way, an adaptive protection system is required that can adaptive its setting according to generation changes, the fault current level in each case is evaluated using ETAP software, and the required relay setting in each case is also evaluated using Grey Wolf Optimizer (GWO) algorithm, and to select suitable setting which required in each condition, to select the active setting group of protection relay according to generation capacity, central protection unite can be used, and to improve protection stability and minimizing relays tripping time, a proposed method for selecting suitable backup relay is used, which leads to decrease relays tripping time and increase system stability, output settings for relays in all cases achieved our constrains.展开更多
The Milan Gobi area of the Golmud-Korla Railway in northwest China is located in the lower dispersal area of the mountain pass and has strong winds with evident double wind direction characteristics.This study introdu...The Milan Gobi area of the Golmud-Korla Railway in northwest China is located in the lower dispersal area of the mountain pass and has strong winds with evident double wind direction characteristics.This study introduced a novel sand fence deployment technique,termed‘folded linear deployment',designed to position the sand fence orthogonally to the two predominant wind directions for optimal protection.This study used wind tunnel and field tests to evaluate the wind and sand flow characteristics,as well as the windproof and sandresistant performance of folded linear HDPE(Highdensity polyethylene)board sand fences.The results suggest that the airflow around the fence creates clear zoning characteristics.The deceleration area on the BSF(backwind side of the sand fence)is much larger than that on the DSF(downwind side of the sand fence).Thus,sand particles are primarily deposited on the BSF.At different wind speeds,the airflow at 2 and 5 h on the DSF is not disturbed.The WSP(wind speed profile)presents a logarithmic distribution.The airflow is disturbed at 1-20 h on the BSF,and the WSP gradually deviates from the logarithmic law.However,as the airflow moves away from the fence,the WSP gradually approaches a logarithmic distribution.Meanwhile,the WPE(windproof efficiency)and SRE(sand-resistant efficiency)of the sand fence exceed 80%.In addition,the results of wind tunnel tests are compared with those of field tests.The overall dispersion is good,and the best dispersion is found at z/H=2.00,indicating good agreement between the two test results.This study provides a scientific basis for the design of sand hazard control measures,similar to the railway project in the Gobi Gale area.展开更多
The coordination correctness of Nuclear power plant current transformer (CT)/ voltage transformer (PT) polarity and relay protection is often verified through the dynamic test on the unit no load / load operating cond...The coordination correctness of Nuclear power plant current transformer (CT)/ voltage transformer (PT) polarity and relay protection is often verified through the dynamic test on the unit no load / load operating conditions. This paper proposes a test method to prevent and circumvent the failure of the dynamic test abnormality caused by the static power test before the plant power is applied and the whole group is started. Reduce the dynamic test workload and test difficulty, to ensure that the dynamic test safety risk control and control in the state.展开更多
A γ-TiAl alloy with nominal composition of Ti-47%Al(molar fraction) was directionally solidified in an alumina mould with an Y2O3 protective coating.The effects of processing parameters(melting temperature and int...A γ-TiAl alloy with nominal composition of Ti-47%Al(molar fraction) was directionally solidified in an alumina mould with an Y2O3 protective coating.The effects of processing parameters(melting temperature and interaction time) on the metal-coating interface,microstructure and chemical composition of the alloy were evaluated.The result shows that the Y2O3 protective coating exhibits an effective barrier capability to avoid direct contact between the mould base material and the TiAl melt,although the Y2O3 coating is found to suffer some erosion and be slightly dissolved by the molten TiAl due to the coating-metal interactions.The directionally solidified alloys were contaminated with Y and O,and Y2O3 inclusions were dispersed in the metal matrix.The reason for this metal contamination is the Y2O3 coating dissolution by the TiAl melt.One mode of the interaction between Y2O3 and the TiAl melt is dissolution of yttrium and atomic oxygen in the melt by reaction Y2O3(s)=2Y(in TiAl melt)+3O(in TiAl melt).Both the extent of alloy contamination and the volume fractions of Y2O3 inclusions depend on the melting temperature and the interaction time.展开更多
Taking lightning-protection engineering of Wuhan Changshankou landfill and incineration plants for the example,in this article,we have discussed the integrated technology of direct lightning protection by early stream...Taking lightning-protection engineering of Wuhan Changshankou landfill and incineration plants for the example,in this article,we have discussed the integrated technology of direct lightning protection by early streamer emission lightning rod,lifting lightning rod and mobile lightning rod. Additionally,lightning protection methods and measures of landfill with large receiving area of lightning strike and landfill gas and incineration plant with irregular landfill cell are explored.展开更多
This paper focuses on the transient protection of transmission line with FACTS Devices;the principle and mathematical model of static synchronous compensator (STATCOM) has been analyzed. And feasible control strategy ...This paper focuses on the transient protection of transmission line with FACTS Devices;the principle and mathematical model of static synchronous compensator (STATCOM) has been analyzed. And feasible control strategy has been proposed considering the voltage source inverter (VSI) as a core part of the FACTS components. The simulation results verify the rightness using electromagnetic transient simulation software PSCAD/EMTDC to set up electromagnetic transient model.展开更多
Since ancient times,lightning disasters have undoubtedly been an unstoppable threat to humanity.During thunderstorms,lightning often damages objects on the ground,such as buildings and structures.Since Franklin invent...Since ancient times,lightning disasters have undoubtedly been an unstoppable threat to humanity.During thunderstorms,lightning often damages objects on the ground,such as buildings and structures.Since Franklin invented the lightning rod in 1752,lightning rods have been used worldwide to prevent direct lightning strikes in various fields such as high-voltage power transmission lines,outdoor chemical sites,highways,land and sea wind farms,and forest lightning fire protection.It has been proven that lightning accidents still occur frequently in places where lightning rods are installed and the protective angle method is used.In order to further study the protective effect of lightning rods and identify the shortcomings of lightning rod protection,negative lightning strikes are taken as the research object,to analyze the limitations of lightning rods in preventing direct lightning strikes from the working principle of lightning rods.展开更多
The protective devices we developed for 500 kV transmission lineshave been implemented in UHV power systems in China for manyyears.The quality of the product and the principle of the system have stoodsevere tests in p...The protective devices we developed for 500 kV transmission lineshave been implemented in UHV power systems in China for manyyears.The quality of the product and the principle of the system have stoodsevere tests in practical operation.In this paper,the general characteristics of 500 kV lines in China aresystematically analysed.The requirements of protection on 500kV linesare specifically discussed,Two design schemes for 500kV protection areproposed,and the results of practical test and operation are given.Theyverified that the schemes proposed overcome the difficulties found inimported relay systems.展开更多
Co-ordination of directional over current relays(DOCR) requires the selection and setting of relays so as to sequentially isolate only that portion of the power system where an abnormality has occurred.The problem of ...Co-ordination of directional over current relays(DOCR) requires the selection and setting of relays so as to sequentially isolate only that portion of the power system where an abnormality has occurred.The problem of coordinating protective relays in electrical power systems consists of selecting suitable settings such that their fundamental protective function is met,given operational requirements of sensitivity,selectivity,reliability and speed.Directional over current relays are best suited for protection of an interconnected sub-station transmission system.One of the major problems associated with this type of protection is the difficulty in coordinating relays.To insure proper coordination,all the main/back up relay pairs must be determined.This paper presents an effective algorithm to determine the minimum number of break points and main/back up relay pairs using relative sequence matrix(RSM).A novel optimization technique based on evolutionary programming was developed using these main/back up relay pairs for directional over current relay coordination in multi-loop networks.Since the problem has multi-optimum points,conventional mathematics based optimization techniques may sometimes fail.Hence evolutionary programming(EP) was used,as it is a stochastic multi-point search optimization algorithm capable of escaping from the local optimum problem,giving a better chance of reaching a global optimum.The method developed was tested on an existing 6 bus,7 line system and better results were obtained than with conventional methods.展开更多
As the penetration of wind power into power grids increases,higher demands are made on the stability and protection of power systems.Unlike traditional synchronous generators,wind turbines are different on the short-c...As the penetration of wind power into power grids increases,higher demands are made on the stability and protection of power systems.Unlike traditional synchronous generators,wind turbines are different on the short-circuit and impedance characteristics,thus some problems exist in pilot protections of transmission lines connecting wind farms.When a single-phase fault occurs on a transmission line,the phase selector based on current-difference sudden-change may mistake the single-phase fault for a phase-to-phase fault.This paper studies the impedance characteristics of an asynchronous wind generator,and analyzes the behavior of a fault phase selector under different conditions.Then,the paper explains that inequality between positive and negative branch coefficients is the cause for the mal-operation of the fault phase selector.Finally,some simulations are done in MATLAB to validate analysis results.展开更多
基金supported by the National Natural Science Foundation of China(51767012)Curriculum Ideological and Political Connotation Construction Project of Kunming University of Science and Technology(2021KS009)Kunming University of Science and Technology Online Open Course(MOOC)Construction Project(202107).
文摘This paper proposes a longitudinal protection scheme utilizing empirical wavelet transform(EWT)for a through-type cophase traction direct power supply system,where both sides of a traction network line exhibit a distinctive boundary structure.This approach capitalizes on the boundary’s capacity to attenuate the high-frequency component of fault signals,resulting in a variation in the high-frequency transient energy ratio when faults occur inside or outside the line.During internal line faults,the high-frequency transient energy at the checkpoints located at both ends surpasses that of its neighboring lines.Conversely,for faults external to the line,the energy is lower compared to adjacent lines.EWT is employed to decompose the collected fault current signals,allowing access to the high-frequency transient energy.The longitudinal protection for the traction network line is established based on disparities between both ends of the traction network line and the high-frequency transient energy on either side of the boundary.Moreover,simulation verification through experimental results demonstrates the effectiveness of the proposed protection scheme across various initial fault angles,distances to faults,and fault transition resistances.
文摘The increasing scale and complexity of power systems require high performance and high reliability of power system protection.Protective relaying based on directional comparison with power line carrier or microwave channels is the most suitable protection scheme for long distance EHV transmission lines and is widely used in power systems.The key element of such protection is a directional relay used to discriminate the fault direction.In order to overcome the disadvantages of conventional directional relays,the authors of this paper put forward the directional comparison carrier protection based on the artificial neural network(ANN).The protection is extensively tested using electromagnetic transient program (EMTP) under various electric power system operating and fault conditions.It is proved that the directional comparison carrier protection based on ANN,which can recognize various fault patterns of the protected transmission line(such as fault direction,fault phases etc.)correctly in any kind of operating and fault conditions and the whole process,is satisfactory for EHV transmission line protection.
文摘Distributed generators now is widely used in electrical power networks, in some cases it works seasonally, and some types works at special weather conditions like photo voltaic systems and wind energy, and due to this continuous changes in generation condition, the fault current level in network will be affected, this changes in fault current level will affect in the coordination between protection relays and to keep the coordination at right way, an adaptive protection system is required that can adaptive its setting according to generation changes, the fault current level in each case is evaluated using ETAP software, and the required relay setting in each case is also evaluated using Grey Wolf Optimizer (GWO) algorithm, and to select suitable setting which required in each condition, to select the active setting group of protection relay according to generation capacity, central protection unite can be used, and to improve protection stability and minimizing relays tripping time, a proposed method for selecting suitable backup relay is used, which leads to decrease relays tripping time and increase system stability, output settings for relays in all cases achieved our constrains.
基金financially supported by the Chang Jiang Scholar and Innovation Team Development Plan of China(IRT_15R29)the Basic Research Innovation Group Project of Gansu Province,China(21JR7RA347)the Natural Science Foundation of Gansu Province,China(20JR10RA231)。
文摘The Milan Gobi area of the Golmud-Korla Railway in northwest China is located in the lower dispersal area of the mountain pass and has strong winds with evident double wind direction characteristics.This study introduced a novel sand fence deployment technique,termed‘folded linear deployment',designed to position the sand fence orthogonally to the two predominant wind directions for optimal protection.This study used wind tunnel and field tests to evaluate the wind and sand flow characteristics,as well as the windproof and sandresistant performance of folded linear HDPE(Highdensity polyethylene)board sand fences.The results suggest that the airflow around the fence creates clear zoning characteristics.The deceleration area on the BSF(backwind side of the sand fence)is much larger than that on the DSF(downwind side of the sand fence).Thus,sand particles are primarily deposited on the BSF.At different wind speeds,the airflow at 2 and 5 h on the DSF is not disturbed.The WSP(wind speed profile)presents a logarithmic distribution.The airflow is disturbed at 1-20 h on the BSF,and the WSP gradually deviates from the logarithmic law.However,as the airflow moves away from the fence,the WSP gradually approaches a logarithmic distribution.Meanwhile,the WPE(windproof efficiency)and SRE(sand-resistant efficiency)of the sand fence exceed 80%.In addition,the results of wind tunnel tests are compared with those of field tests.The overall dispersion is good,and the best dispersion is found at z/H=2.00,indicating good agreement between the two test results.This study provides a scientific basis for the design of sand hazard control measures,similar to the railway project in the Gobi Gale area.
文摘The coordination correctness of Nuclear power plant current transformer (CT)/ voltage transformer (PT) polarity and relay protection is often verified through the dynamic test on the unit no load / load operating conditions. This paper proposes a test method to prevent and circumvent the failure of the dynamic test abnormality caused by the static power test before the plant power is applied and the whole group is started. Reduce the dynamic test workload and test difficulty, to ensure that the dynamic test safety risk control and control in the state.
文摘A γ-TiAl alloy with nominal composition of Ti-47%Al(molar fraction) was directionally solidified in an alumina mould with an Y2O3 protective coating.The effects of processing parameters(melting temperature and interaction time) on the metal-coating interface,microstructure and chemical composition of the alloy were evaluated.The result shows that the Y2O3 protective coating exhibits an effective barrier capability to avoid direct contact between the mould base material and the TiAl melt,although the Y2O3 coating is found to suffer some erosion and be slightly dissolved by the molten TiAl due to the coating-metal interactions.The directionally solidified alloys were contaminated with Y and O,and Y2O3 inclusions were dispersed in the metal matrix.The reason for this metal contamination is the Y2O3 coating dissolution by the TiAl melt.One mode of the interaction between Y2O3 and the TiAl melt is dissolution of yttrium and atomic oxygen in the melt by reaction Y2O3(s)=2Y(in TiAl melt)+3O(in TiAl melt).Both the extent of alloy contamination and the volume fractions of Y2O3 inclusions depend on the melting temperature and the interaction time.
文摘Taking lightning-protection engineering of Wuhan Changshankou landfill and incineration plants for the example,in this article,we have discussed the integrated technology of direct lightning protection by early streamer emission lightning rod,lifting lightning rod and mobile lightning rod. Additionally,lightning protection methods and measures of landfill with large receiving area of lightning strike and landfill gas and incineration plant with irregular landfill cell are explored.
文摘This paper focuses on the transient protection of transmission line with FACTS Devices;the principle and mathematical model of static synchronous compensator (STATCOM) has been analyzed. And feasible control strategy has been proposed considering the voltage source inverter (VSI) as a core part of the FACTS components. The simulation results verify the rightness using electromagnetic transient simulation software PSCAD/EMTDC to set up electromagnetic transient model.
基金Supported by Lightning Multi-pulse Intelligent Monitoring System Optimization Technology Project of Guangdong Yuedian Dianbai Hot Water Wind Farm(SFC/DBW-Z-FW-23-006).
文摘Since ancient times,lightning disasters have undoubtedly been an unstoppable threat to humanity.During thunderstorms,lightning often damages objects on the ground,such as buildings and structures.Since Franklin invented the lightning rod in 1752,lightning rods have been used worldwide to prevent direct lightning strikes in various fields such as high-voltage power transmission lines,outdoor chemical sites,highways,land and sea wind farms,and forest lightning fire protection.It has been proven that lightning accidents still occur frequently in places where lightning rods are installed and the protective angle method is used.In order to further study the protective effect of lightning rods and identify the shortcomings of lightning rod protection,negative lightning strikes are taken as the research object,to analyze the limitations of lightning rods in preventing direct lightning strikes from the working principle of lightning rods.
文摘The protective devices we developed for 500 kV transmission lineshave been implemented in UHV power systems in China for manyyears.The quality of the product and the principle of the system have stoodsevere tests in practical operation.In this paper,the general characteristics of 500 kV lines in China aresystematically analysed.The requirements of protection on 500kV linesare specifically discussed,Two design schemes for 500kV protection areproposed,and the results of practical test and operation are given.Theyverified that the schemes proposed overcome the difficulties found inimported relay systems.
文摘Co-ordination of directional over current relays(DOCR) requires the selection and setting of relays so as to sequentially isolate only that portion of the power system where an abnormality has occurred.The problem of coordinating protective relays in electrical power systems consists of selecting suitable settings such that their fundamental protective function is met,given operational requirements of sensitivity,selectivity,reliability and speed.Directional over current relays are best suited for protection of an interconnected sub-station transmission system.One of the major problems associated with this type of protection is the difficulty in coordinating relays.To insure proper coordination,all the main/back up relay pairs must be determined.This paper presents an effective algorithm to determine the minimum number of break points and main/back up relay pairs using relative sequence matrix(RSM).A novel optimization technique based on evolutionary programming was developed using these main/back up relay pairs for directional over current relay coordination in multi-loop networks.Since the problem has multi-optimum points,conventional mathematics based optimization techniques may sometimes fail.Hence evolutionary programming(EP) was used,as it is a stochastic multi-point search optimization algorithm capable of escaping from the local optimum problem,giving a better chance of reaching a global optimum.The method developed was tested on an existing 6 bus,7 line system and better results were obtained than with conventional methods.
基金supported by National Basic Research Program of China(No.2009CB219704)National Natural Science Foundation of China (No. 50977061)National Natural Science Foundation of Tianjin City (No. 11JCYBJC07600)
文摘As the penetration of wind power into power grids increases,higher demands are made on the stability and protection of power systems.Unlike traditional synchronous generators,wind turbines are different on the short-circuit and impedance characteristics,thus some problems exist in pilot protections of transmission lines connecting wind farms.When a single-phase fault occurs on a transmission line,the phase selector based on current-difference sudden-change may mistake the single-phase fault for a phase-to-phase fault.This paper studies the impedance characteristics of an asynchronous wind generator,and analyzes the behavior of a fault phase selector under different conditions.Then,the paper explains that inequality between positive and negative branch coefficients is the cause for the mal-operation of the fault phase selector.Finally,some simulations are done in MATLAB to validate analysis results.